background image

28

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

hot water odor

On occasion, hot water may develop a strong odor. If this occurs 

drain the heater completely, flush thoroughly, and refill. If the problem 

persists, chlorination of the heater and replacement of magnesium 

anodes with aluminum anodes may correct the condition.
Occasionally water softener companies recommend removal of 

heater anodes for odor reasons.
unauthorized removal of the anode(s) will void the warranty.  For 

further information contact your dealer.

anode rod inspection

Property Damage Hazard

Avoid water heater damage.

Inspection and replacement of anode rod required.

CAUTION

The anode rod is used to protect the tank from corrosion. Most 

hot water tanks are equipped with an anode rod. The submerged 

rod sacrifices itself to protect the tank. Instead of corroding the 

tank, water ions attack and eat away the anode rod. This does 

not affect water’s taste or color. The rod must be maintained to 

keep the tank in operating condition.
Anode deterioration depends on water conductivity, not necessarily 

water  condition.  A  corroded  or  pitted  anode  rod  indicates  high 

water conductivity and should be checked and/or replaced more 

often than an anode rod that appears to be intact. Replacement 

of a depleted anode rod can extend the life of your water heater. 

Inspection should be conducted by a qualified service agency, and 

at a minimum should be checked annually after the warranty period.
Artificially  softened  water  is  exceedingly  corrosive  because  the 

process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water 

heater tank.
The anode rod should be inspected after a maximum of three years 

and annually thereafter until the condition of the anode rod dictates 

its replacement. Anode replacement is not covered by warranty.

note:

 Artificially softened water requires the anode rod to be 

inspected annually.

draining and flushing

Burn harzard.

Hot water discharge.

Keep  hands   clear  of  drain

valve  discharge.

It is recommended that the water heater storage tank be drained 

and  flushed  every  6  months  to  reduce  sediment  buildup.  The 

water heater should be drained if being shut down during freezing 

temperatures. See Features And Components in this manual for 

the location of the water heater components described below.

to drain the water heater storage tank:

1.  Turn off the gas and electrical supply to the water heater.

2.  Turn off the gas supply at the Main Gas shutoff Valve if the 

water heater is going to be shut down for an extended period.

3.  Ensure the cold water inlet valve is open.

4.  Open a nearby hot water faucet and let the water run until 

the water is no longer hot.

5.  Close the cold water inlet valve to the water heater.

6.  Connect a hose to the water heater drain valve and terminate 

it to an adequate drain.

7.  open the water heater drain valve and allow all the water to 

drain from the storage tank.

8.  Close the water heater drain valve when all water in the 

storage tank has drained.

9.  Close the hot water faucet opened in Step 4.

10.  If the water heater is going to be shut down for an extended 

period, the drain valve should be left open.

to flush the water heater storage tank:

1.  Turn off the electrical supply to the water heater.

2.  Ensure the cold water inlet valve is open.

3.  Open a nearby hot water faucet and let the water run until 

the water is no longer hot. Then close the hot water faucet.

4.  Connect  a  hose  to  the  drain  valve  and  terminate  it  to  an 

adequate drain.

5.  Ensure  the  drain  hose  is  secured  before  and  during  the 

entire flushing procedure. Flushing is performed with system 

water pressure applied to the water heater.

6.  Open the water heater drain valve to flush the storage tank.

7.  Flush the water heater storage tank to remove sediment and 

allow the water to flow until it runs clean.

8.  Close the water heater drain valve when flushing is completed.

9.  Remove the drain hose.

10.  Fill the water heater - see Filling The Water Heater in this manual.

11.  Turn on the electrical supply to place the water heater back 

in operation.

12.  Allow the water heater to complete several heating cycles to 

ensure it is operating properly.

recommended procedure for periodic 

remoVal of lime deposits from tank type  

commercial water heaters

The amount of calcium carbonate (lime) released from water is 

in direct proportion to water temperature and usage, see chart.  

The higher the water temperature or water usage, the more lime 

deposits  are  dropped  out  of  the  water.  This  is  the  lime  scale 

which forms in pipes, heaters and on cooking utensils.

Содержание BTC 201

Страница 1: ...15 Low Lead Content Thank you for buying this energy efficient water heater We appreciate your confidence in our products WARNING If the information in these instructions is not followed exactly a fir...

Страница 2: ...Troubleshooting 33 Water Piping Diagrams 34 Manifold Kits 49 Limited Warranty 50 Notes 51 2 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Safety Information 4 Precautions...

Страница 3: ...ate of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State...

Страница 4: ...ment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or ser...

Страница 5: ...system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the...

Страница 6: ...water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fir...

Страница 7: ...manual resetting of high limit control preceded by higher than usual water temperature is evidence of high limit switch operation The following is a possible reason for high limit switch operation A m...

Страница 8: ...60 F 33 C 70 F 39 C 80 F 44 C 90 F 50 C 100 F 56 C 110 F 61 C 120 F 67 C 130 F 72 C 140 F 78 C BTR C 151 150 000 NAT 32 Gal 80 GPH 727 485 364 291 242 208 182 162 145 132 121 112 104 44 kW Hr NAT 121...

Страница 9: ...CONSTRUCTION MODEL A RIGHT SIDE B LEFT SIDE C BACK D CEILING BTR C 151 201 0 0 0 12 30 5 cm Locating the Water Heater Property Damage Hazard All water heaters eventually leak Do not install without ad...

Страница 10: ...ion to come within 9 inches 23 cm of floor within 2 inches 5 cm of bottom cover to prevent blockage of combustion air flow to the burners DO NOT cover the instruction manual Keep it on the side of the...

Страница 11: ...rating label under any circumstances Note Due to the input rating reduction at high altitudes the output rating of the appliance is also reduced and should be compensated for in the sizing of the equi...

Страница 12: ...37 kPa from static to dynamic pressure to provide good performance Pressure drops that exceed 1 5 W C 0 37 kPa may cause rough starting noisy combustion or nuisance outages Increases or spikes in sta...

Страница 13: ...al expansion tank installed See Water Line Connections on page 19 and the Water Piping Diagrams beginning on page 34 Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valv...

Страница 14: ...ems and Thermal Expansion on page 13 If you do not understand these instructions or have any questions regarding the Temperature Pressure Relief Valve call the toll free number listed on the back cove...

Страница 15: ...which the appliances are installed through openings not furnished with doors are considered a part of the unconfined space Makeup air requirements for the operation of exhaust fans kitchen ventilatio...

Страница 16: ...uare inches 645 cm2 Outdoor Air Through One Opening Figure 14 Alternatively a single permanent opening commencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 14 Th...

Страница 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in thi...

Страница 18: ...Number of Heaters Combined Input btu hr Manifold and Common Vent Diameter Inches 2 300 000 8 7 7 7 7 6 6 6 3 450 000 9 9 9 8 8 7 7 7 4 600 000 10 10 10 9 9 8 8 7 MODEL 201 Input 182 000 and 199 900 b...

Страница 19: ...nections The water piping installation must conform to these instructions and to all local code authority having jurisdiction Good practice requires that all heavy piping be supported Read and observe...

Страница 20: ...eat to this fitting Do not allow pipe dope to contact the plastic tube during installation Tube Inlet Installation Figure 18 TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE...

Страница 21: ...LECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION If any of the original wire as supplied with the appliance must be replaced use only type 105 C thermoplastic...

Страница 22: ...ne be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap must be incorporated in the piping see Figure 20 The sedimenttrapmustber...

Страница 23: ...Gas Line Leak Testing on page 22 and repair any leaks found Start Up Initial Start Up Required Test Equipment U tube manometer pressure gauge or digital manometer Recommended range 20 W C 5 kPa Note...

Страница 24: ...ressure to each water heater within the minimum and maximum supply pressure requirements listed in Table 3 on page 8 with all gas fired appliances connected to a common gas main firing at full capacit...

Страница 25: ...to the Silicon Nitride Igniter 11 From the time the Silicon Nitride Igniter s power is shut off the Ignition Control Board waits 3 more seconds to monitor the Flame Sensor 12 If the Flame Sensor does...

Страница 26: ...26 Sequence of Operation Flow Chart Description of this flow chart can be found in the SEQUENCE OF OPERATION section found on page 25 Figure 23...

Страница 27: ...er through the heater where the thermostat senses the drop in water temperature and activates main burner operation of the appliance If the storage tank temperature control is out of calibration repla...

Страница 28: ...heater storage tank be drained and flushed every 6 months to reduce sediment buildup The water heater should be drained if being shut down during freezing temperatures See Features And Components in...

Страница 29: ...ve handling instructions on label of product being used Tank Cleanout Procedure The following practices will ensure longer life and enable the unit to operate at its designed efficiency 1 Once a month...

Страница 30: ...flush with cool water If irritation persists get medical attention If swallowed give 1 or 2 glasses of water or milk and call physician Get immediate medical attention for eyes Keep out of reach of ch...

Страница 31: ...e thermostat calling for heat It is possible that the high limit E C O has functioned to shut off the appliance See High Limit page 7 High Limit Switch for reset procedure Contact your service agent i...

Страница 32: ...s bacteria is nontoxic to humans d An excess of active hydrogen in the tank This is caused by the corrosion protective action of the anode Hot water odor may be eliminated or reduced in some water hea...

Страница 33: ...call a qualified service agency Delime heater Ticking or metallic sounds Expansion and contraction normal Pounding or water hammer Air chambers in piping have become waterlogged Thermal expansion tank...

Страница 34: ...s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CI...

Страница 35: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Страница 36: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Страница 37: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Страница 38: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Страница 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Страница 40: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Страница 41: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Страница 42: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Страница 43: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Страница 44: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT...

Страница 45: ...r than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL...

Страница 46: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Страница 47: ...emperature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEM...

Страница 48: ...Temperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE...

Страница 49: ...49 Manifold Kits MANIFOLD KITS TWO UNIT MANIFOLD KIT PART NO 9003426205 THREE UNIT MANIFOLD KIT PART NO 9003427205 FOUR UNIT MANIFOLD KIT PART NO 9003428205 MODEL DIMENSIONS A 151 201 45 0...

Страница 50: ...also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES s t s o c r e h t o l l a r o f e l b i s...

Страница 51: ...51 Notes...

Страница 52: ...www hotwater com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2012 A O Smith Water Heater Company All rights reserved...

Отзывы: