U.S. REQUIREMENTS

Ratings specified by manufacturers for most appliances apply for
elevations up to 2000 feet (610 m).  For elevations above 2000 feet
(610 m), ratings must be reduced at the rate of 4% for each 1000
feet (305 m) above sea level.  For example, if a heater is rated at
65,000 Btuh (19 Kw) at sea level, to rate the heater at 4000 feet
(1219 m), you subtract 4 (once for each thousand feet) x.04
(4% input reduction) x 65,000 (original rating) from the original
rating.  Therefore, to calculate the input rating at 4,000 feet (1219
m): 4 x .04 x 65,000 = 10,400 Btuh (3.0 Kw), 65,000
(19 Kw) - 10,400 (3.0 Kw) = 54,600 Btuh (16 Kw).  At 6000 feet
(1829 m) the correct input rating should be 49,400 Btuh (14.5 Kw).

CANADIAN REQUIREMENTS

Appliances with inputs up to and including 400,000 BTU
must be    factory equipped with orifices for operation at specific
elevations.  Standard (sea level) orifices permit operation up to
2000' (610 m) elevation. For operation between 2000' (610 m) and
4500' (1370 m) specify "HIGH ALTITUDE OPERATION" when
ordering the heater(s). For operation above 4500' (2370 m) consult
factory before ordering.

Field conversion for operation at altitudes other than that
specified on the heater rating plate is not permitted.

The input reduction is primarily achieved by reducing the size of
the main burner orifices.  To do this, the main burner orifices require
replacement with orifices sized for the particular installation
elevation.  Correct orifice sizing and parts may be obtained from
A.O. Smith Water Products Company.  When ordering, be sure to
state the model number and the altitude of the location where the
water heater is being installed.

Upon completion of derating of the heater, adjustment to the gas
pressure regulator may be required.  See CHECKING THE INPUT
section in this manual for inlet and manifold pressure
requirements.

Also due to the input rating reduction required at high altitudes, the
output rating of the appliance is reduced and should be
compensated for in the sizing of the equipment for application.

CLEARANCES

These heaters are approved  for installation on combustible flooring
in a closet having a ceiling 18" (457 mm) above top cover and with
clearances to combustible construction of 6" (152 mm) from flue
or vent connector, 1" (25 mm) at the sides and rear and
4" (102 mm) to front to prevent a possible fire hazard condition.  A
minimum of 4" (101.6 mm) shall be allowed for installation of
serviceable parts.

HARD WATER

Where hard water conditions exist, water softening or the threshold
type of water treatment is recommended.  This will protect the
dishwashers, coffee urns, water heaters, water piping and other
equipment.

Contact your dealer or qualified service technician for more
information on this product.

AIR REQUIREMENTS

REFER TO THE LATEST EDITION OF THE "NATIONAL FUEL GAS
CODE" ANSI Z223.1/NFPA 54.  FOR CANADA CONSULT CAN/CSA
B149.1-00.

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE
MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS AND
LIQUIDS.

DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATING AIR.

  

WARNING

FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR
COMBUSTION AND VENTILATION.  AN INSUFFICIENT SUPPLY
OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION
PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY BE
HAZARDOUS TO LIFE.  SUCH A CONDITION OFTEN WILL
RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING
CARBONING OR SOOTING OF THE COMBUSTION CHAMBER,
BURNERS AND  FLUE TUBES AND CREATES A RISK OF
ASPHYXIATION.

Where an exhaust fan is supplied in the same room with a heater,
sufficient openings for air must be provided in the walls.

UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO
THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION.  SOOTING MAY RESULT IN SERIOUS DAMAGE
TO THE HEATER AND RISK OF FIRE OR EXPLOSION.

UNCONFINED SPACE

In buildings of conventional frame, brick, or stone construction,
unconfined spaces may provide adequate air for combustion,
ventilation and draft hood dilution.

If the unconfined space is within a building of tight construction
(buildings using the following construction: weather stripping, heavy
insulation, caulking, vapor barrier, etc.), air for combustion,
ventilation and draft hood dilution must be obtained from outdoors.
The installation instructions for confined spaces in tightly
constructed buildings must be followed to ensure adequate air
supply.

CONFINED SPACE

When drawing combustion and dilution air from inside a
conventionally constructed building to a confined space, such a
space shall be provided with two permanent openings, ONE IN
OR WITHIN 12 INCHES (30.50 cm) OF THE ENCLOSURE TOP
AND ONE IN OR WITHIN 12 INCHES (30.50 cm) OF THE
ENCLOSURE BOTTOM.  Each opening shall have a free area of at
least one square inch per 1000 Btuh (2202.8 mm

2

/KW) of the total

input of all appliances in the enclosure, but not less than
100 square inches (645 cm

2

).

If the confined space is within a building of tight construction, air for
combustion, ventilation, and draft hood dilution must be obtained
from outdoors.  When directly communicating with the outdoors or
communicating with the outdoors through vertical ducts, two
permanent openings, located in the above manner, shall be
provided.  Each opening shall have a free area of not less than one
square inch per 4000 Btuh (550.7 mm

2

/KW)  of the total input of all

appliances in the enclosure.  If horizontal ducts are used, each
opening shall have a free area of not less than one square inch
per 2000 Btuh (1101.4 mm

2

/KW) of the total input of all appliances

in the enclosure.  For Canadian installations consult CAN/CSA
B149.1-00.

COMBINATION WATER (POTABLE)

HEATING AND SPACE HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

Содержание BT- 65

Страница 1: ...TENANCE LIMITED WARRANTY Thank you for buying this energy efficient water heater from A O Smith Water Products Company We appreciate your confidence in our products ADIVISION OFA O SMITH CORPORATION M...

Страница 2: ...itions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 in Canada CAN CSA B 149 1 00 Both are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 For C...

Страница 3: ...ERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILUREAND RISK OFASPHYXIATION Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calciu...

Страница 4: ...TER DIRECTLY ON A CARPETED FLOOR A FIRE HAZARD MAY RESULT Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches 76 mm in any d...

Страница 5: ...E LATEST EDITION OF THE NATIONALFUELGAS CODE ANSI Z223 1 NFPA54 FOR CANADACONSULT CAN CSA B149 1 00 KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS GASOLINEANDOTHERFLAMMABLES VAPORSAND LIQ...

Страница 6: ...nt connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace the vent pipe should enter the smaller common vent or chimney at a point...

Страница 7: ...IONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED WARNING TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE TEMPERATURE REGULATION ON PAGE 11 IF HIG...

Страница 8: ...ptable for the purpose in locating the leaks DO NOT USE MATCHES CANDLES FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE FIGURE4 GASPIPINGANDDIRTLEGINSTALLATION DISCONNECTTHE HEATERAND ITS MANUALGA...

Страница 9: ...FOR STEPS TO BE TAKEN Before lighting the pilot and operating the heater the following conditions must exist Entire system filled with water Air purged from all lines and no leaks gas and water All ga...

Страница 10: ...l If you don t smell gas go to next step 6 Remove or open inner door located below gas control unit 7 Find pilot follow metal tube from gas control The pilot is located in front of the burner or on th...

Страница 11: ...of use to exceed the thermostat setting by up to 30 F 17 C If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing point of...

Страница 12: ...cteristics 1 Provide complete combustion of gas 2 Cause rapid ignition and carryover of flame across entire burner 3 Give reasonably quiet operation during ignition burning and extinction 4 Cause no e...

Страница 13: ...22mm in diameter with a 1 8 3mm diameter steel core wire running down the center of the anode material THE ANODE SHOULD BE REPLACED when the 1 8 3mm diameter core wire is visible as this means that t...

Страница 14: ...operation is evidence of poor vent action Possible causes are too long a vent pipe or improper chimney operation 3 If the leakage is from the temperature and pressure relief valve or its discharge pi...

Страница 15: ...is warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non...

Страница 16: ...16 PRODUCT SERVICE DIVISION 5621 W 115TH STREET ALSIP IL 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 E MAIL parts hotwater com www hotwater com REPLACEMENTPARTS...

Отзывы: