background image

4

to flow.  

THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR

THE FAUCET AT THE TIME IT IS OPEN.

INSULATION BLANKETS

Insulation blankets available to the general public for external use
on gas water heaters are not necessary with A.O. Smith water heater.
The purpose of an insulation blanket is to reduce the standby heat
loss encountered with storage tank water heaters.  Your A.O. Smith
water heater meets or exceeds the ASHRAE/IES 90.1b-1992
standards with respect to insulation and standby loss requirement
making an insulation blanket unnecessary.

  

WARNING

Should you choose to apply an insulation blanket to this heater, you
should follow these instructions.  Failure to follow these instructions
can result in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top of the water heater, as this will

interfere with safe operation of the draft hood.

Do not cover the outer door, thermostat or temperature &

pressure relief valve.

Do not allow insulation to come within 2" (51 mm) of the floor to

prevent blockage of combustion air flow to the burner.

Do not cover the instruction manual.  Keep it on the side of the

water heater or nearby for future reference.

Do obtain new warning and instruction labels from A.O. Smith

for placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain it

does not sag, thereby obstructing combustion air flow.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES
ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN
THE FIELD INVOLVED.  PLUMBING, AIR SUPPLY, VENTING AND
GAS SUPPLY WORK ARE REQUIRED.

LOCATING THE HEATER

When installing the heater, consideration must be given to proper
location.  Location selected should be as close to the stack or
chimney as practicable, with adequate air supply and as
centralized with the piping system as possible.

  

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER
AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,
OPERATED OR REPAIRED.  FLAMMABLE VAPORS ARE HEAVY
AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE
HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE OR
EXPLOSION. 

 SOME LOCAL CODES PERMIT OPERATION OF GAS

APPLIANCES IF INSTALLED 18 INCHES (457 mm) OR MORE
ABOVE THE FLOOR.  THIS MAY REDUCE THE RISK IF LOCATION
IN SUCH AN AREA CANNOT BE AVOIDED.

DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A
CARPETED FLOOR.  A FIRE HAZARD MAY RESULT. 

 Instead the

water heater must be placed on a metal or wood panel extending
beyond the full width and depth by at least 3 inches (76 mm) in any
direction.  If the heater is installed in a carpeted alcove or closet,
the entire floor shall be covered by the panel.  Also, see the drain
requirements.

THIS HEATER SHALL BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

   

WARNING

FLAMMABLE ITEMS

, PRESSURIZED CONTAINERS OR ANY

OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER.  OPEN
CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE HEATER.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT
WILL BE SUBJECT TO FREEZING.

THE HEATER SHOULD BE LOCATED IN AN AREA WHERE
LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT
RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER
FLOORS OF THE STRUCTURE.

WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER.
Such pans should be fabricated with sides at least 2" (51 mm)
deep, with length and width at least 2" (51 mm) greater than the
diameter of the heater and must be piped to an adequate drain.
The pan must not restrict combustion air flow.

Drain pans suitable for these heaters are available from your
distributor or A. O. Smith Water Products Company, 5621 West
115th Street, Alsip, IL 60803.  In Canada contact A.O. Smith
Enterprises, LTD., 768 Erie Street, Stratford, Ontario,
Canada N5A 6T3.

For appliance installation locations with elevations above
2000 feet (610 meters), refer to HIGH ALTITUDE INSTALLATIONS
section of this manual for input reduction procedure.

HIGH ALTITUDE INSTALLATIONS

 

  WARNING

INSTALLATIONS ABOVE 2000 FEET (610 METERS) REQUIRE
REPLACEMENT OF THE BURNER ORIFICE IN ACCORDANCE
WITH SECTION 8.1.2 OF THE NATIONAL FUEL GAS CODE (ANSI
Z223.1).  FOR CANADIAN INSTALLATIONS CONSULT CANADIAN
INSTALLATIONS CODES AND CAN/CSA B149.1-00.  FAILURE TO
REPLACE THE ORIFICE WILL RESULT IN IMPROPER AND
INEFFICIENT OPERATION OF THE APPLIANCE RESULTING IN
THE PRODUCTION OF INCREASED LEVELS OF CARBON
MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD
RESULT IN SERIOUS PERSONAL INJURY OR DEATH.

You should contact your gas supplier for any specific changes
which may be required in your area.

As elevation above sea level is increased, there is less oxygen
per cubic foot of air.  Therefore, the heater input rate should be
reduced at high altitudes for satisfactory operation with the reduced
oxygen supply.  Failure to make this reduction would result in an
overfiring of the heater causing sooting, poor combustion and/or
unsatisfactory heater performance.

Содержание BT- 65

Страница 1: ...TENANCE LIMITED WARRANTY Thank you for buying this energy efficient water heater from A O Smith Water Products Company We appreciate your confidence in our products ADIVISION OFA O SMITH CORPORATION M...

Страница 2: ...itions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 in Canada CAN CSA B 149 1 00 Both are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 For C...

Страница 3: ...ERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILUREAND RISK OFASPHYXIATION Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calciu...

Страница 4: ...TER DIRECTLY ON A CARPETED FLOOR A FIRE HAZARD MAY RESULT Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches 76 mm in any d...

Страница 5: ...E LATEST EDITION OF THE NATIONALFUELGAS CODE ANSI Z223 1 NFPA54 FOR CANADACONSULT CAN CSA B149 1 00 KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS GASOLINEANDOTHERFLAMMABLES VAPORSAND LIQ...

Страница 6: ...nt connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace the vent pipe should enter the smaller common vent or chimney at a point...

Страница 7: ...IONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED WARNING TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE TEMPERATURE REGULATION ON PAGE 11 IF HIG...

Страница 8: ...ptable for the purpose in locating the leaks DO NOT USE MATCHES CANDLES FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE FIGURE4 GASPIPINGANDDIRTLEGINSTALLATION DISCONNECTTHE HEATERAND ITS MANUALGA...

Страница 9: ...FOR STEPS TO BE TAKEN Before lighting the pilot and operating the heater the following conditions must exist Entire system filled with water Air purged from all lines and no leaks gas and water All ga...

Страница 10: ...l If you don t smell gas go to next step 6 Remove or open inner door located below gas control unit 7 Find pilot follow metal tube from gas control The pilot is located in front of the burner or on th...

Страница 11: ...of use to exceed the thermostat setting by up to 30 F 17 C If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing point of...

Страница 12: ...cteristics 1 Provide complete combustion of gas 2 Cause rapid ignition and carryover of flame across entire burner 3 Give reasonably quiet operation during ignition burning and extinction 4 Cause no e...

Страница 13: ...22mm in diameter with a 1 8 3mm diameter steel core wire running down the center of the anode material THE ANODE SHOULD BE REPLACED when the 1 8 3mm diameter core wire is visible as this means that t...

Страница 14: ...operation is evidence of poor vent action Possible causes are too long a vent pipe or improper chimney operation 3 If the leakage is from the temperature and pressure relief valve or its discharge pi...

Страница 15: ...is warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non...

Страница 16: ...16 PRODUCT SERVICE DIVISION 5621 W 115TH STREET ALSIP IL 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 E MAIL parts hotwater com www hotwater com REPLACEMENTPARTS...

Отзывы: