Instruction manual ADMR
41
is
11. Check whether there is a burner pressure regulator (1) attached to the gas
control, or simply a blank plate (5).
Note
If the supply pressure for a gas category is the same as the burner pressure
(see the gas data table
(3.4.3 "Gas data")
) then the gas control must be fitted
with a blank plate with cork gasket. A burner pressure that deviates in
comparison to the supply pressure requires the use of a burner pressure
regulator with rubber gasket. Each conversion kit contains all the necessary
components.
12. If the blank plate or burner pressure regulator need to be replaced:
-
Unscrew the connector (4) of the gas control.
-
If necessary, remove the blank plate or burner pressure regulator (5)
or burner pressure regulator (1).
-
If necessary, fit the blank plate or burner pressure regulator supplied
with the conversion kit.
-
Fit the connector (4) of the gas control.
13. Check the supply pressure and burner pressure
(3.11 "Checking the supply
pressure and burner pressure")
.
14. Remove the sticker showing the new gas category from the conversion kit,
and attach it below the appliance's rating plate. This clearly indicates that the
appliance may no longer be run on the gas for which it was originally
supplied.
15. Start the appliance
(9.1 "Starting and running")
.
Содержание ADMR-115
Страница 4: ...4 Instruction manual ADMR gis...
Страница 8: ...Table of contents 8 Instruction manual ADMR...
Страница 12: ...Introduction 12 Instruction manual ADMR 1 gis...
Страница 38: ...Installation 38 Instruction manual ADMR 3 is...
Страница 56: ...Shutting down 56 Instruction manual ADMR 10 gis...
Страница 64: ...Main menu 64 Instruction manual ADMR 11 gis...
Страница 78: ...is Instruction manual ADMR 78...
Страница 80: ...Maintenance frequency 80 Instruction manual ADMR 14 is...
Страница 86: ...Performing maintenance 86 Instruction manual ADMR 15 s...
Страница 94: ...Appendices 94 Instruction manual ADMR 17 is...
Страница 96: ...Instruction manual ADMR 96...