when an error is detected. It will also go to this screen upon
power-up if an error was still valid when power was turned off.

NOTE: Errors are cleared from this screen by pressing the
"select" key.

Error History Screen:

This screen displays a list of the last 9 errors (with time stamps)
that have occurred.  The last error to occur is displayed first.  If a
new error occurs this screen is presented to display the error.

Reload Defaults Screen:

From this screen the user can restore the factory default values
for screen adjustable configurations by pressing the Select key.
The values restored are as follows:

GW Models
Oper Setpnt (Operating Setpoint) - 145° F (63° C)
Stage1 Diff (Operating Setpoint Differential) = 3° F (2° C)
Stage2 Diff (Operating Setpoint Differential) = 6° F (3° C)
Hi Limit (High LImit Setpoint) = 210° F (99° C)
Hi Limit Dif (High Limit Differential) = 20° F (11° C)

GB Models
Oper Setpnt (Operating Setpoint) = 190° F (88° C)
Stage1 Diff (Operating Setpoint Differential) = 3° F (2° C)
Stage2 Diff (Operating Setpoint Differential) = 6° F (3° C)
Hi LImit (High LImit Setpoint) = 230° F (110° C)
Hi Limit Dif (High Limit Differential) = 20° F (11° C)

Both Models
Tempert Units (Temperature Units) = F
Post Cir Secs (Post Circulation pump delay = 45 seconds
Network Address (Network Address) =  (none)

UIM Touch Switches

Below the LCD display are five touch switches or keys, that the
operator uses to operate the system.

Menu Key:
Pressing this key activates the menu screen where the other
screens can be accessed.

Select Key:
This key performs several functions.  Screens can be selected
from the menu screen by pressing this key when the">" appears
next to the screen desired.

On the User Settings screen items that appear next to a ">"
symbol can be selected with this key.  If a setpoint configuration
item is selected, the ">" will then flash slowly to indicate that the
item has been selected.  The Up and Down keys are then used
to change its value.

From the Current Error Screen this key is used to reset the
system from an error:

Up and Down Keys:
These keys are used to move upwards and downwards in
screens to reach a desired item and to change setpoints and
user settings.  They have an auto increment/decrement feature
for some of the configurations and values.  When you first press
one of the keys and value changes by 1 count, then wait 1/2
second and changes slowly until the key is released or if held
for 3 or more seconds it will change the value quickly.

Help Key:
Pressing the Help key from any screen displays helpful
information about that screen.  From the menu screen, general
help information is displayed as to how to use the user interface.
To return to the previous screen press the Help or Select keys,
or press Menu key to go to the menu screen.  If a small down
arrow appears in the lower right hand corner then there is off
screen content below what is displayed.  Press the down arrow
to scroll down to this information.  After scrolling down an up
arrow will appear in the upper right hand corner to indicate off
screen content above what is displayed.

UIM LED's

The three LED's to the right of the LCD indicate the status of the
overall system.  The red LED indicates that a fault has been detected
and the system has stopped running.  It is on continuously for soft
faults and flashes for hard faults.  The Yellow LED indicates that
the boiler is in a ready mode waiting for a call for heat command.
When on continuously the Green LED indicates that the system is
in the heating mode.  If it is flashing it indicates that the UIM is in the
initialization mode and the touch switches are being calibrated.

On these boilers there are also eight LED's on the lower right that
indicate the state of the individual FCB's. The red LED's are only on
when the main red LED is on and indicate which FCB has the error.
The green LED indicates when flame is proved on that particular
stage, unless the dipswitch for sensing flame is turned off. Then
the LED indicates that the gas valve has turned on.

Fault Messages and Troubleshooting Guide

The EMC5000 system does excessive self-diagnostics and
displays detected faults on the UIM display in an easy to read
manner.  There are approximately 80 different faults that can be
detected.  Some of the faults are caused by internal problems and
some by external causes.  The faults create different types of system
lockouts (shut down).  Hard lockouts are serious problems that
require the user to manually restart system.  Soft lockouts can be
reset by the user or after 60 minutes the system will automatically
clear the error and restart.  Auto Reset lockouts will monitor the
cause of the fault and if the fault clears itself the system reset itself.
The fault is recorded and the system immediately resets itself.
The following table shows the fault messages and some possible
troubleshooting hints:

TROUBLESHOOTING IGNITION SYSTEM

Fault  Messages and Lockout Status (* = stage number: 1, 2, 3, or 4)

FAULT DISPLAYED

DESCRIPTION

RED LED

LOCKOUT

“Display Fail”

Communications with UIM interrupted

Continuous

Auto Reset

Check communication cable to UIM.  Try moving to other Internal Communications connector on CCB.
Also check the connectors where the cable is plugged in for best connecting wires.

“Comm. Fail Stg.*”

Communications with FCB interrupted

Continuous

Auto Reset

Same as above.  Also try swapping FCB and UIM communications cables.

“Low AC Voltage”

Line voltage less than 90 vac

Continuous

Auto Reset

Check incoming power line for loss of voltage.  May also be caused by a power line brown-out (momentary
loss of voltage)

Содержание 400 Series

Страница 1: ...tion and or operation of this boiler Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS CONTENTS PAGE DIMENSIONS CAPACITIESDATA 2 3...

Страница 2: ...ater Conn Gas Inlet Model Natural Gas Natural Gas Propane Gas Propane Gas Inches cm Inches cm Size GW GB 1000 990 000 289 95 990 000 289 95 10 25 4 8 20 3 2 1 2 NPT 2NPT GW GB 1300 1 300 000 380 74 1...

Страница 3: ...62 9 31 6 80 3 82 208 3 15 5 39 4 39 75 101 58 25 148 15 9 40 83 16 40 64 57 3 145 5 GBO GWO 1500 30 76 2 31 6 80 3 89 226 15 5 39 4 39 75 101 58 25 148 15 9 40 83 16 40 64 64 3 163 3 GBO GWO 1850 27...

Страница 4: ...TALLATION TO AVOID POSSIBLE ERRORS AND MINIMIZE TIME AND MATERIALS COST SEE FIGURES 1 THROUGH 5 AND TABLES 1 2 AND 3 This design complies with the current edition of ANSI Z21 13 CSA 4 9 for Gas Fired...

Страница 5: ...ery system will have one Central Control Board CCB one Power Distribution Board PDB one User Interface Module UIM and either two or three Flame Control Boards FCB depending on the model The Control Bo...

Страница 6: ...switch provides 120VAC from the line source to the boiler COMBUSTION AIR BLOWER Provides air for combustion process The blower settings are adjustable through the use of the air shutter however blower...

Страница 7: ...the lowest rated working pressure of any system component and a discharge capacity exceeding the total input of the water boilers supplying water to the storage tank Locate the T P relief valve a in t...

Страница 8: ...Control Board Flame Control Boards Power Distribution Board and wiring harnesses is provided through a panel on the left side of the unit A minimum service clearance of 18 46 0 cm is required These b...

Страница 9: ...unicating with the outdoors through vertical ducts two permanent openings located in the above manner shall be provided Each opening shall have a free area of not less than one square inch per 4000 Bt...

Страница 10: ...ve boiler vent collar Vent pressure should be maintained between 0 02 W C and 0 04 W C to assure proper operation For appliances with a draft hood check for spillage with mirror smoke or other device...

Страница 11: ...gas meters regulators and relief equipment 4 The minimum distance from inside corner formed by two exterior walls is 6 feet 1 8 m but 10 feet 3 1 m is recommended where possible 5 Maintain a minimum...

Страница 12: ...of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints TABLE 10 STANDARD VERTICAL VENTING CATEGORY I Extending venting over 70 feet 21 3 m may re...

Страница 13: ...gas vent pipes listed for use with Category III gas burning heaters such as stainless steel Saf T Vent by Heat Fab Inc available from A O Smith 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone...

Страница 14: ...vent terminal The horizontal portion of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints Figure 8 APPLIANCE CERTIFIED EXHAUST VENT MAXIMUM AIR...

Страница 15: ...2515 Pipe joints must be positively sealed TABLE 13 DIRECT VENT HORIZONTAL EXHAUST CONFIGURATIONS Figure 9 APPLIANCE CERTIFIED EXHAUST MAXIMUM AIR INTAKE AIR INTAKE MAXIMUM MODEL CATEGORY EXHAUST VENT...

Страница 16: ...condensation within the boiler on cold starts This condensing of water vapor in the combustion area can be prevented if a portion of the system water flow is diverted past the boiler to cause an incre...

Страница 17: ...le boilers manifolded for reverse return flow The system bypass would be installed from boiler outlet to suction side of pump The boiler piping system of a hot water heating boiler connected to heatin...

Страница 18: ...he tank probe as the controlling probe Second Dip Switch SW1 1 must be set to the OFF position to limit the maximum tank probe temperature for GW applications Failure to do this will void the warranty...

Страница 19: ...WATER FLOW SWITCH PROTECTS THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE PIPE TO OPEN DRAIN X FACTORY INSTALLED ON UNIT SUPPLIED WITH UNIT FIELD INSTALLED INSTALL THERMAL EXP...

Страница 20: ...ED DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATUREAT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 26 IF HIGHER PREHEAT TEM PERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTE...

Страница 21: ...92 2 841 2 577 2 372 2 197 2 109 1 962 1 757 1 611 1 464 1 347 Length of Pipe in Feet Metres Nominal Iron Pipe Size Cap 10 Ft 20 Ft 30 Ft 40 Ft 50 Ft 60 Ft 70 Ft 80 Ft 90 Ft 100 Ft 125 Ft 150 Ft 175 F...

Страница 22: ...and30Amps TABLE 18 Orifice Size for Natural and Propane LP Gases U S and Canada Installations for high altitude up to 4 500 ft 1 372 m Drill Size Input Rating Number of Model BTU HR Burners Natural 4...

Страница 23: ...23 GB GW 2100 GB GW 2500 GB GW 1000 1500 GAS MANIFOLD ASSEMBLY GB GW 1850 Figure 14 GB GW 1000 2500 Gas Manifold Assembly Diagrams...

Страница 24: ...24 GENESIS GB GW 1000 2500 SERIES 400 WIRING DIAGRAM FIGURE 15...

Страница 25: ...25...

Страница 26: ...26 GENESIS GB GW 1000 2500 SERIES 400 SCHEMATIC DIAGRAM FIGURE 16...

Страница 27: ...27...

Страница 28: ...28 Figure 17 CCB CENTRAL CONTROL BOARD...

Страница 29: ...29 Figure 18 FCB FLAME CONTROL BOARD Diagram...

Страница 30: ...30 Figure 19 PDB POWER DISTRIBUTION BOARD Diagram...

Страница 31: ...Installation 1 Close the systems drain valve 2 Open a nearby hot water faucet to permit the air in the system to escape 3 Fully open the cold water inlet pipe valve allowing the heater and piping to...

Страница 32: ...OLLER TO THE LOWEST SETTING 2 TURN POWER SWITCH ON APPLIANCE TO OFF POSITION 3 REMOVEACCESSPANELTOEXPOSEGASCONTROL IF YOU CANNOT REACH YOUR GAS SUPPLIER CALL THEFIREDEPARTMENT C USE ONLYYOUR HAND TO P...

Страница 33: ...A QUALIFIED SERVICETECHNICIANTOINSPECTTHEAPPLIANCEAND TOREPLACEANYPARTOFTHECONTROLSYSTEMAND ANYGASCONTROLWHICHHASBEENUNDERWATER E DO NOT OPERATEAPPLIANCE UNLESS UNIT IS FILLED WITH WATERAND WATER LINE...

Страница 34: ...dition occur the control will shut down the burner and display a red fault light as well as indicate the cause of the fault on the display The operating programs for the system are stored in permanent...

Страница 35: ...l Normally open switch that closes when the IRI Gas Valve is operating correctly This input is enabled disabled by a dipswitch on the CCB Flame Sensor Flame CCB required Returns a signal to the microp...

Страница 36: ...ns If a switch is changed power must be cycled before the change will take effect The status of all dipswitches can be observed on the system status screen on the UIM CCB FCB Dipswitches Dipswitches F...

Страница 37: ...om the controlling probe inlet or tank to the setpoint temperature If the temperature is less than the operating setpoint minus the differential temperature and the thermostat input is closed then a c...

Страница 38: ...l which means that it will begin heating the water when the temperature sensed by the control probe inlet or tank falls below the operating setpoint minus the differential setpoint for stage 1 It will...

Страница 39: ...been satisfied or the Thermostat is opened the sequence moves to Post Circulate and then back to Idle If a fault occurs at any time the process jumps out of sequence and goes directly to the appropri...

Страница 40: ...iter hardware failure If the igniter does reach the minimum required amp draw of 2 8 amps the gas valve circuit is energized and the system advances to Flame Check status Check for Flame State The gas...

Страница 41: ...and minutes This error remain displayed as long as it is still valid When cleared it is moved to the Error History Screen The system will automatically jump to this screen OPERATING SETPOINT ADJUSTME...

Страница 42: ...keys or press Menu key to go to the menu screen If a small down arrow appears in the lower right hand corner then there is off screen content below what is displayed Press the down arrow to scroll do...

Страница 43: ...checked by disconnecting the outlet probe from the CCB and reading the resistance across the two active pins on the connector at the end of the probe cable The value should be approximately 0 ohms whe...

Страница 44: ...rner venturi and ports are free of foreign matter 4 Clean burners with bristle brush and or vacuum cleaner DO NOT distort burner ports 5 Reinstall burners in unit Ensure that all the screws on the bur...

Страница 45: ...y The installer must provide a filtering system in the air inlet to the boiler if dust dirt or construction dirt can be pulled into the boiler through the inlet air piping Periodically clean air filte...

Страница 46: ...einstall return header casting Flush system Note Removal of the heat exchanger is not required CAUTION IF HEAT EXCHANGER MAINTENANCE REQUIRES TUBING REPLACEMENT SPECIAL PROVISIONS SHALL BE TAKEN TO EN...

Страница 47: ...WARRANTIES Implied warranties including any warranty of merchantability imposed on the sale of this boiler under state law are limited to one 1 year duration for the boiler or any of its parts Some st...

Страница 48: ...48 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 433 2545 www hotwater com E Mail parts hotwater com...

Отзывы: