background image

5

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters
installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned
or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:

INSTALLATION OF CARBON MONOXIDE DETECTORS

  At the time of installation of the side wall horizontal vented gas fueled

equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-
up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe
that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling,
building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner
to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a
battery operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS

  Each carbon monoxide detector as required in accordance with the above

provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.

SIGNAGE 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum

height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

INSPECTION 

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the

installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS

: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54
as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building, or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

 When the manufacturer of Product

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

  When the manufacturer

of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue
gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.

INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

Содержание 1000 SERIES 100

Страница 1: ...ng Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be per...

Страница 2: ...the requirements of the National Fuel Gas Code as it relates to the installation of gas fired boilers The qualified installer must have a thorough understanding of this instruction manual Service Age...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...trol assembly provided on the boiler met safe lighting and other performance criteria Detailed installation diagrams are found in this manual These diagrams will serve to provide the installer a refer...

Страница 5: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Страница 6: ...6 CONNECTION DIAGRAM...

Страница 7: ...7...

Страница 8: ...8 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Страница 9: ...9 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Страница 10: ...m and contains the system fuses The MCB also contains an external communications system to allow for connection to a PC a modem an EMS system or something similar Through this connection multiple boil...

Страница 11: ...flame rod is missing or shorted the flame will not be detected OUTPUTS FROM MCB RELAY CONTACT OUTPUT Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an aud...

Страница 12: ...tivated screens Within each of the screens helpful information can be displayed by pressing the Help button The LED s visually inform the user about the mode the system is in The touch switches allow...

Страница 13: ...ppropriate time then the sequence moves to the Inter Purge state for 15 seconds and the FCB heat sequence is repeated If flame is still not detected after the third try the process declares a fault ju...

Страница 14: ...ure to change the automatically resettable High Limit Setpoint 1 Press the MENU key 2 Scrollthe withtheDOWNkeynexttoUSERSETTINGSCREEN 3 Press the SELECT key 4 Scroll the with the DOWN key until it is...

Страница 15: ...rds in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of the...

Страница 16: ...ins on the connector at the end of the probe cable The value should be approximately 0 ohms when the temperature of the probe is less than 220 F Low Water Water level is too low Flashing HARD Caused b...

Страница 17: ...reasonably quiet operation during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports If the preceding burner characteristics are not evident check for acc...

Страница 18: ...ower adapter by first removing the four 4 bolts and subsequently the blower gaskets The blower should be free to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber...

Страница 19: ...specified by the manufacturer of the product Inspect the installed device to insure that it does not cause condensate to remain in the boiler or vent for any reason VENTING MAINTENANCE It is recommen...

Страница 20: ...20 NOTES...

Страница 21: ......

Страница 22: ...22 NOTES...

Страница 23: ...e or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limitati...

Страница 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 433 2545 www hotwater com E Mail parts hotwater com...