background image

14

if the blower prover does not activate after 15 seconds. This
time allows the blower relay to activate, the blower to come up
to speed, and the response from the blower prover to be filtered.

User Settings Screen:
Each setpoint or user setting has either a limited selection of
values, or a limited range of values.  The Up/Down keys are
used to change values.  After changing an item, the Select key
is pressed to accept the change, or the Menu key is pressed to
reject the change and restore the item to its original value.
The following setpoints can be changed:

Operating Setpoint:
This setpoint sets the base temperature for the control algorithm.

OPERATING SETPOINT ADJUSTMENT PROCEDURE

The system has a standard programmable Operating Setpoint
range of 70°F (21°C) to 190°F (88°C) for a VW and of 70°F
(21°C) to 220°F (104°C) for a VB for either a Remote or inlet
probe depending on selection. The user can easily change
the Operating Setpoint at any time by using the following
procedure. When any configuration or setpoint is changed
(and the Select key touched), the new value is IMMEDIATELY
saved to non-volatile memory. The factory default setting is
145°F (49°C).

1. Press the MENU key.

2. Scroll the ">" with the DOWN key next to the USER

SETTING SCREEN.

3. Press the SELECT key.

4. Scroll the ">" with the DOWN key until it is pointing to

OPERATING SETPOINT.

5. Press the SELECT key.

6. Use the UP or DOWN key to select the value you wish to enter.

7. Press the SELECT key to accept and store the new value.

High Limit:
The outlet temperature probe contains both an ECO switch
and a thermistor for temperature measurement. The sensed
outlet temperature is used for the automatically resettable
High Limit setpoint. If the sensed outlet temperature exceeds
the High Limit setpoint, a "soft lockout" condition will occur and
the burner will be shut off. This fault condition is automatically
cleared when the temperature drops below the high limit
setpoint minus the high limit differential.

AUTO HIGH LIMIT SETPOINT ADJUSTMENT PROCEDURE/
OUTLET TEMPERATURE PROBE

The High Limit setpoint has a range of 90°F (32°C) to 210°F  (99°C)
for a VW and a range of 90°F (32°C) to 235°F (113°C) for a VB.
Use the following procedure to change the automatically resettable
High Limit Setpoint:

1. Press the MENU key.

2. Scroll the ">" with the DOWN key next to USER SETTING SCREEN.

3. Press the SELECT key.

4. Scroll the ">" with the DOWN key until it is pointing to HIGH

LIMIT SETPOINT.

5. Press the SELECT KEY.

6. Use the UP and DOWN key to select the value you wish to enter.

7. Press the SELECT key to accept and store the new value.

High Limit Differential:
The outlet temperature must be below the automatic High Limit
setpoint minus the High Limit Differential setpoint before  a call
for heat can be generated.

HIGH LIMIT DIFFERENTIAL SETPOINT ADJUSTMENT
PROCEDURE

The High Limit Differential Setpoint has a range of 1°F to 50°F for
all models. Use the following procedure to change the High Limit
Differential Setpoint:
1. Press the MENU key.

2. Scroll the ">" with the down key next to USER SETTING SCREEN.

3. Press the SELECT key.

4. Scroll the ">" with the DOWN key until it is pointing to HIGH

LIMIT DIFFERENTIAL SETPOINT.

5. Press the SELECT key.

6. Use the UP or DOWN key to select the value you wish to enter.

7. Press the SELECT key to accept and store the new value.

Operating Differential Setpoints:
Each of the two stages has an independent Operating
Differential setpoint.

Temperature Units:

Temperature can be displayed in either °F or °C units.

Post Circulate Delay Time:

The time circulation pump will stay on after the burner is
turned off. The time in seconds is adjustable with the
following values: 45, 90, 180 or continuous.  If the
continuous value is selected the pump will remain on at
all times and the post circulate state time will be set at 45
seconds.

Network Address:

This is a unique number assigned to this boiler to
differentiate it from other boilers or water heater on the same
A. O. Smith proprietary network. A valid  Network Address
can be any number from 0 to 31. It is set by default to zero,
which is an invalid address. The boiler will not communicate
until it is changed to a valid and unique number. This prevents
two units from trying to respond to the same request from
the PC or supervisory network device.

Configuration Settings Screen:

Displays the status of the dipswitches installed on all
boards as described earlier.

Log & System Info Screen:

Displays the following information:
Elapsed hours of operation (Total time system has been
powered up)

Number of running minutes (Number of minutes system has
been in the run mode)

Содержание 1000 SERIES 100

Страница 1: ...ng Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be per...

Страница 2: ...the requirements of the National Fuel Gas Code as it relates to the installation of gas fired boilers The qualified installer must have a thorough understanding of this instruction manual Service Age...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...trol assembly provided on the boiler met safe lighting and other performance criteria Detailed installation diagrams are found in this manual These diagrams will serve to provide the installer a refer...

Страница 5: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Страница 6: ...6 CONNECTION DIAGRAM...

Страница 7: ...7...

Страница 8: ...8 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Страница 9: ...9 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Страница 10: ...m and contains the system fuses The MCB also contains an external communications system to allow for connection to a PC a modem an EMS system or something similar Through this connection multiple boil...

Страница 11: ...flame rod is missing or shorted the flame will not be detected OUTPUTS FROM MCB RELAY CONTACT OUTPUT Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an aud...

Страница 12: ...tivated screens Within each of the screens helpful information can be displayed by pressing the Help button The LED s visually inform the user about the mode the system is in The touch switches allow...

Страница 13: ...ppropriate time then the sequence moves to the Inter Purge state for 15 seconds and the FCB heat sequence is repeated If flame is still not detected after the third try the process declares a fault ju...

Страница 14: ...ure to change the automatically resettable High Limit Setpoint 1 Press the MENU key 2 Scrollthe withtheDOWNkeynexttoUSERSETTINGSCREEN 3 Press the SELECT key 4 Scroll the with the DOWN key until it is...

Страница 15: ...rds in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of the...

Страница 16: ...ins on the connector at the end of the probe cable The value should be approximately 0 ohms when the temperature of the probe is less than 220 F Low Water Water level is too low Flashing HARD Caused b...

Страница 17: ...reasonably quiet operation during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports If the preceding burner characteristics are not evident check for acc...

Страница 18: ...ower adapter by first removing the four 4 bolts and subsequently the blower gaskets The blower should be free to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber...

Страница 19: ...specified by the manufacturer of the product Inspect the installed device to insure that it does not cause condensate to remain in the boiler or vent for any reason VENTING MAINTENANCE It is recommen...

Страница 20: ...20 NOTES...

Страница 21: ......

Страница 22: ...22 NOTES...

Страница 23: ...e or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limitati...

Страница 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 433 2545 www hotwater com E Mail parts hotwater com...

Отзывы: