A.M.I. PH001 Скачать руководство пользователя страница 4

A.M.I.

A.M.I.

3, Rue de la Garenne - Z.I. de Vernon 

27950 SAINT MARCEL - FRANCE

tél. : +33 (0)2 32 51 47 16

Fax : +33 (0)2 32 21 13 73

http://www.ami-control.com

 : [email protected]

1/L

1

2/L

2

3/L

3

4/L

4R

5/L

4V/B

6 TL Ext

.

7/-0V

8/+5V

L1 L2 L3 VR

L4

VV VB

1

8

45 

+/- 0,

3

45 +/- 0,3

PAN45-01-00

PAN45-01-00

48

1 -

2 -

3 -

4 -

48

5

45 à 50

48

0,5A

L2
L3

Raccordement triphasé avec ou sans neutre

L1

N

CHARGE

0,5A

Raccordement monophasé

L1

N

CHARGE

A

B

53

8 mm 

max.

144 x 144 mm

14

L

1

8

75

7,5

60

68

CONNECTIONS :

DIMENSIONS :

CARACTERISTICS :

ASSEMBLY / DISASSEMBLY :

COMMANDE:

- PH001 

: Phase rotation controller in 380V 

or 220v single phase, DIN box.

- PAN45-01-00 

: 4 LEDs display, 48x48, 5V 

voltage, mounting on the front of the cabinet, 

supplied with RJ45 cable L = 2.00m (other 

length on request).

Assembly (A) of the housing on the 

profi le and disassembly (B)

PH001

PAN45-01-00

Three phase

PH / PH

Single phase

PH / N

Supply

Nominal :

Minimum :

Consumed strength :

Frequency :

150V- 480V

150V

150V-280V

150V

Powered by the PH001 box in 5V 

through the RJ45 cable

2VA

45-55Hz

Settings :

Under pressure :

On voltage :

Asymmetry % :

Time delay :

Start-up times :

300V - 380V

380V - 480V

5% - 25%

173V - 220V

220V - 277V

1s

<1s 

Instant protection

Loss of rotation :

Yes

No

On voltage :

Umax > +10% of the setting

or > 277v PH/N or 480v PH/PH

Asymmetry % :

Asymmetry > +25%

No

Time delay :

0,5s

Output contact :

Rated / Max intensity :

Rated / Max cut-off  voltage :

Max cut-off  power :

Number of operations :

Contact material :

Insulation between power supply 

and contacts :

1RT

8A / 10A

250Vac / 400Vac

2500VA / 300W

1x10

7

AgSnO2

5KV / 1mn

Enclosures

Protection :

Material :

Resistance to fl ame :

Humidity in use / storage :

Operating temperature :

Storage temperature :

Surface insulation :

IP20

UL94 V2 class

90% non-condensing / 70%

-20°C / +60°C

-20°C / +70°C

10

15 

Ohms/cm

IP65 on front

polyamide PA66 30gf

UL94 V2 class

90% non-condensing / 70%

-20°C / +60°C

-20°C / +70°C

10

15

 Ohms/cm

Commissioning:

- Position the settings by turning all potentiometers fully 

clockwise.

- Apply the voltage setting and check the phase rotation 

display.

- Since this is correct, reduce the Umax detection threshold 

by turning the potentiometer anti-clockwise.

As soon as the detection is displayed, bring the setting a few 

degrees clockwise.

- Do the same for the other Umin and asymmetry settings.

- Adjust the timing as needed.

In single-phase, the «overvoltage» and «undervoltage» as 

well as «time delay» detections are active.

Phase rotation and asymmetry / loss of neutral are

inactive.

Quick connection between 

the PAN45-01-00 front 

display unit and the DIN 

PH001 unit (cable supplied 

with the PAN45-01-00).

PH1

PH2

PH3

Status

PH1

PH2

PH3

Status

LOAD

LOAD

Three-phase connection with or without neutral

Single-phase connection

Protection by 3 fuses 

is compulsory.

Crossing neutral with a 

phase can destroy the 

device