A.M.I. PH001 Скачать руководство пользователя страница 2

PAN45-01-00

(PAN45-01-00)

OFF ON

Vert

Green

3

2

1

Rouge

Red

3

2

1

Jaune

Yellow

3

2

1

Magenta

3

2

1

Cyan

3

2

1

Blanc

White

3

2

1

Eteint

Off 

3

2

1

Bleu

Blue

3

2

1

Switch

(PAN45-01-00)

PAN45-01-00 DISPLAY BOX :

SETTING THE LED COLOR :

RJ45 cable

standard length : 2.00m

ACHIEVEMENT OF LABELS :

OPERATION :

The PAN45-01-00 allows you to indicate the installation status, without 

having to open the cabinet door.

It is intended to report the display states on the front while ensuring 

galvanic separation from the power grid. The front IP65 safety box is 

supplied with «very low voltage» (5Vdc by 1kV isolated converter and 3kV 

optocouplers located in the PH001 box).

The colors of the LEDs PH1, 

PH2, PH3 are selectable.

 7 colors possible.

Three-phase installation, 

with only one phase present 

correct (PH2) and without 

neutral connected, the 

display is turned off .

Three-phase installation, with only 

one phase present correct (PH2) and 

neutral connected :

- whithout voltage return, the display 

will be in running light eff ect.

- with voltage return, the other phases 

will be displayed under voltage.

The LEDs are of the CMS tri-LEDs type. For each channel, a switch located at the rear, 

allows you to select a display color for among 7 :

Red, Green, Yellow, Blue, White, Cyan, Magenta

The diff erent possible diplays :

without neutral

with neutral

Use

Three phase 

without neutral

The neutral terminal is not used.

Three phase with 

neutral

Connection of neutral is not compulsory. 

The connected neutral allows display in all 

situations, including in the event that only 

one phase is present.

This avoids having a display off  when a 

dangerous voltage is present.

Single phase

The 3 phase terminals are connected

together and connected to the phase.

The neutral terminal is connected to 

neutral.

L1

L1

L1

L2

L2

L2

L3

L3

L3

Status

Status

Status

PH1

PH2

PH3

Status

PH1

PH2

PH3

Status

PH1

PH2

PH3

Status

PH1

PH2

PH3

Status

PH1

PH2

PH3

Status

The labels are simple sheets of paper which slip into a transparent pocket included in the tickness

of the facade. A blank label is provided with each device.

They can be done by hand, or edited on a color printer (laser or inkjet).

PC software allows you to create them, include an image, save and duplicate the creations.

This software is free and downloadable form our website :

www.ami-control.com

Possibility of printing on plastic sheets for countries with high humidity.

The box is operational as soon as :

- a voltage of 150V Ph/Ph minimum between two phases present in three-phase assembly.

- a voltage of 120V Ph/Ph minimum between two phases present and the neutral connected

in three-phase + neutral mounting.

- a voltage of 150V Ph/N between phase and neutral in single phase connection.

With a correct phase rotation and with all voltages within the adjustment limits, the signaling will be a follows :

- the phase indication LEDs (L1, L2, L3, PH1, PH2, PH3) are ON steady.

- the «Status» LED is lit in GREEN steady.

- the output relay is normally activated.

In the following explanations, no account is taken of the presence of induced voltage or of voltage return on the 

absent phase. To simplify, the measurements and examples are made from channel 2 (L2, PH2).

Indicate FAST blinking

Indicate SLOW blinking

In DIN 48x48 format, with bracket mounting, it has 4 high-brightness LEDs.

The fi rst 3 LEDs are used to display the state of each phase, as well as to indicate the 

direction of rotation. The 4th LED displays whether the power grid is usable or not, as 

well as the type of fault found. (see on the next page, the diff erent possible displays).

- Quick connection by extra fl exible RJ45 cable, supplied with the box.

- Possibility to select a color among 7 for each of the fi rst 3 LEDs.

- Removable front label wich can be easily created by the user.