SETUP
LEREF "Verzeichnis Ueberschrift" \* MERGEFORMAT Index
Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift
dem Text zuzuweisen, der hier angezeigt werden soll.
Contents
We take care of it.
Type of oil cooling (inner cooling medium)
The following options are available:
0
ON: Stands for ONAN or ONAF cooling
0
OF: Stands for OFAF or OFWF cooling
0
OD: Stands for ODAF or ODWF cooling
0
ON/OF: Stands for switching between ON and OF cooling. In this case, at least one con-
trollable oil pump is available:
0
ON/OD: Stands for switching between ON and OD cooling. In this case, one device to
steer the oil and at least one controllable oil pump are available.
The 'Transformer parameters' and 'Temperature limits' menus each have two additional pa-
rameter tabs for the oil pumps when cooling modes ON/OF and ON/OD are activated.
IEC Formula
The following options are available:
0
IEC 60354
0
IEC 60076
The parameter determines the algorithm used to calculate the hot-spot temperature.
Fan assignment
5.3.2
To enable users to assign a specific fan to a cooling stage or let the system decide which fan
to activate for a cooling stage, the Transformer Monitor offers the choice between:
0
fixed
and
0
cyclical
If the parameter 'fixed' is chosen the fans are assigned to a specific cooling stage, fan 1 will
always be switched on for cooling stage 1. Over a long period of operation, this setting will
result in a high operating time and thus wear of fan 1, whereas that of the higher cooling
stages will be very small.
If 'cyclical' is chosen for the fan assignment, the controller decides which fan is switched on
in proportion to the total operating time of each cooling stage. Over the service life, this al-
gorithm achieves a more or less equal operating time for all fans.