Page 15
Basic description of the Transformer Monitor
LEREF "Verzeichnis Ueberschrift" \* MERGEFORMAT Index
Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift
dem Text zuzuweisen, der hier angezeigt werden soll.
Inhaltsverz
Oil temperatures (TC/Transformer)
4.2.1
The temperature can either be displayed as bars or numerically. With the help of the setup
menu the maximum temperatures for the transformer and the tap-changer can be set. If
the temperature in the tap-changer tank is required, a mA value has to be supplied to the
voltage regulator via an analogue input.
Winding currents and winding temperature
4.2.2
The “windings” display mode provides information on the present current flowing through
the windings and the hot-spot temperature calculated from it or provided from a winding
temperature measurement device like the REG-FO.
Oil level (TC/Transformer)
4.2.3
Press '→' to access the next screen and display the fill lev-
els for the transformer tanks and the TC vessel (TC
tap
changer). The oil level in the transformer and the tap
changer can only be displayed if the controller is supplied
with the corresponding sensor data from the transformer
and the tap changer. In the simplest case, the fill level is
supplied to the controller as an analogue signal. Scaling is
done from the menu. The bar flashes when the limits are exceeded. In addition the level
alarm is available as relay and LED output function as well as SCADA indication. A black non-
flashing column indicates that the 'fill level is OK'.
Overload Prediction
4.2.4
Press '→' to access the next screen and display the possible overload and the time within
which the over temperature will be reached.
Possible overload
This screen provides information about the transformer's load capacity. It indicates the load
that the transformer can carry as a percentage without exceeding the maximum winding
temperature at the end of the window (Time to max temperature).
Time to over temperature
This screen displays the time after which the maximum winding temperature will be
reached at the current load.
Two dashes are displayed if the temperature limit is not reached at the current load. The
same applies when the temperature limit has already been reached or exceeded.