Basic description of the Transformer Monitor
LEREF "Verzeichnis Ueberschrift" \* MERGEFORMAT Index
Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift
dem Text zuzuweisen, der hier angezeigt werden soll.
Contents
We take care of it.
4.4
Statistics
Please press the
<ESC>
but-
ton
(alternatively <MENU>
and <F4>) to go to the Moni-
tor
Main
screen.
All the tap changer’s activi-
ties are recorded in Statistics
< F3 >.
The total number of tap changes (65 in the example) and the total number of tap changes
under load (26 in the example) are recorded in STATISTICS –1.
This mode also provides information about which tap has been changed and how often.
These statistics give detailed information on the transformer setting.
Example: If there are only three or four tap positions in use, it usually indicates that either
the permissible deviation or the time factor for the control is not optimally adjusted.
An improvement in the settings leads to a reduction of the switching operations and there-
fore to longer maintenance intervals under certain circumstances.
The situation shown above can be analyzed as follows:
0
The tap changer was in operation 65 times in total, where only 26 switching operations
were carried out under load.
0
The tap changer is currently in position 2 and a current is flowing which is larger than
5% of the set current.
Load current indication by the double arrow
The double arrow symbol turns into a single arrow symbol if the current is below 5% of the
nominal current.
A second type of display can be selected by pressing < F1 >.
The historical graphics in STATISTICS -2 give the operator a qualitative impression of the
operations of the tap changer. The data is taken from the recordings in STATISTICS –1.