Page 44
We take care of it.
No. Explanation
1
Connection for customer input cable L1IN/L2IN/L3IN
2
Connection for customer cable N (TN-S/TT-System)
3
Connection for customer cable PEN (TN-C-System)
4
Connection for customer cable PE (TN-S/TT-System)
5
Connection for customer output cable L1OUT/L2 OUT /L3 OUT
6
C-profile rail 30x15 for fixing the cables
d1
Centre distance C-profile rail to connection points 300mm
Table 5-15 Designation of the figures:
No.
Frame clamp
Flat connection
1-5
UKH 70 Feature D31
16 - 70 mm² (Cu); 50/70 mm² (Al-se)
RBO 10 Feature D51
M10 (6 - 150 mm²)
UKH 95 Feature D32
25 - 95 mm² (Cu); 70/95 mm² (Al-se)
RBO 12 Feature D52
M12 (25 - 240 mm²)
UKH 150 Feature D33
35 - 150 mm² (Cu); 120 / 150 mm² (Al-se)
RBO 16 Feature D53
M16 (50 - 300 mm²)
UKH 240 Feature D34
70 - 240 mm² (Cu); 185 / 240 mm² (Al-se)
Table 5-16 Design of the terminal points