CAPSCREW TORQUE (FOOT-POUND)

CAPSCREW

HEAD

CAPSCREW DIAMETER

TYPE

MARKING

1

/

4

5

/

16

3

/

8

7

/

16

1

/

2

5

/

8

3

/

4

7

/

8

1

SAE Grade 2

6

13

25

38

60

120

190

210

300

Brass

Stainless Steel

or

4

10

17

27

42

83

130

200

300

SAE Grade 5

10

20

35

60

90

180

325

525

800

SAE Grade 8

13

28

46

75

115

225

370

590

895

DEALER SERVICING

If  trouble  occurs  that  cannot  be  rectified  contact  your  local 

AC Fire Pump Systems representative. He will need the fol-

lowing information in order to give you assistance.
1. Complete nameplate data of pump and motor.

2. Suction and discharge pipe pressure gauge readings.
3. Ampere draw of the motor.
4. A sketch of the pump hook-up and piping.

RECOMMENDED SPARE PARTS

The pumps covered by this manual have been designed and

built with certain replaceable wearing parts. The recommended

inventory of spare parts depends upon the installation and the

importance of continued operation.
For normal service, with repairs to be made in the field, the fol-

lowing parts are recommended for stock.

1 set of packing rings (complete)

1 shaft sleeve

2 sets of wearing rings (if provided)

1 set of gaskets

1 lantern ring

Parts should be ordered as far in advance of their use as pos-

sible since circumstances beyond the control of the company 

RECOMMENDED SPARE PARTS

may reduce existing stock. Not all parts are stocked and must

be manufactured for each order.
To  facilitate  rapid  handling  of  your  order  for  spare  parts,  be

sure to include the following information:
1. Serial number of the pump.
2. Quantity of each part.
3. Name of part.
4. Material  desired.  (Parts  will  be  furnished  in  original

materials unless specified as a material change. All material

substitutions should be discussed with the factory.)

Содержание 1580 series

Страница 1: ...Series 1580 In Line Mounted Centrifugal Fire Pumps INSTRUCTION MANUAL AC2516 REVISION D INSTALLER PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE ...

Страница 2: ......

Страница 3: ...t installation with the fewest number of bends or elbows in the suction pipe The installation must be evaluated to determine that the Net Positive Suction Head Available NPSHA meets or exceeds the Net Positive Head Required NPSHR as stated by the pump performance curve WARNING Falling Object Hazard Eyebolts or lifting lugs if provided are for lifting only the components to which they are attached ...

Страница 4: ......

Страница 5: ... the suction valve closed or throttled This could result in cavita tion Cavitation will cause the pump performance to fall off and also overtime can cause impeller and or casing damage NOTE On 6x6x91 2 and 6x6x11 there will be volute and stuff box wear rings CAUTION Seal Damage Hazard Do not run pump dry seal damage may occur Failure to follow these instructions could result in property damage and...

Страница 6: ...hould be allowed to continue for a period of time before further tightening of the glands Take up gland bolts uniformly one flat at a time An adequate leakage rate is not one single value for all pumps and installations but is the amount required to provide adequate cooling and lubrication The required leakage will be largely influenced by operating pressure fluid temperature shaft speed etc For f...

Страница 7: ...ertain replaceable wearing parts The recommended inventory of spare parts depends upon the installation and the importance of continued operation For normal service with repairs to be made in the field the fol lowing parts are recommended for stock 1 set of packing rings complete 1 shaft sleeve 2 sets of wearing rings if provided 1 set of gaskets 1 lantern ring Parts should be ordered as far in ad...

Страница 8: ...qualified personnel LIMITATIONS The warranty does not cover defects that are caused by these situations Deficient maintenance Improper installation Modifications or changes to the product that are made without consulting an A C Fire Pump authorized representative Incorrectly executing repair work Normal wear and tear A C Fire Pump assumes no liability for these situations Bodily injuries Material ...

Отзывы: