background image

5

PRIMING AND STARTING

Before  starting  the  pump,  the  pump  body  must  be  full  of 

liquid. Manual priming may be required if the system does not

automatically  fill  the  pump  body  with  liquid.  Vent  plugs  are

provided on the pump body to vent the air. While venting the

air from the pump body, the pump shaft should be rotated a

few times by hand.

The pump should be started with the discharge valve closed

and the suction valve fully open. After the pump is up to oper-

ating speed the discharge valve should be opened slowly.
IMPORTANT: The  pump  should  never  be  operated  with  the

suction  valve  closed  or  throttled. This  could  result  in  cavita-

tion.  Cavitation  will  cause  the  pump  performance  to  fall-off

and also, overtime, can cause impeller and/or casing damage.

NOTE: On 6x6x9

1

/

2

and 6x6x11 there will be volute and stuff

box wear rings.

CAUTION: Seal Damage Hazard

Do not run pump dry, seal damage may occur. Failure

to follow these instructions could result in property damage

and/or moderate personal injury.

Shaft

Slinger

Packing Gland

Cover Plate

Cap Screw

Impeller

Washer

Volute Cap

Screw

Flush Line

Impeller Key

Bracket

Gland Bolt

Packing Rings

Lantern Ring

Drip Drain

Cover Plate

Volute Gasket

Impeller

Lock Washer

Impeller

Impeller Cap Screw

Volute

Shaft Sleeve

FIGURE 5

CROSS SECTION OF SERIES 1580 INLINE MOUNTED CENTRIFUGAL FIRE PUMP

Содержание 1580 series

Страница 1: ...Series 1580 In Line Mounted Centrifugal Fire Pumps INSTRUCTION MANUAL AC2516 REVISION D INSTALLER PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE ...

Страница 2: ......

Страница 3: ...t installation with the fewest number of bends or elbows in the suction pipe The installation must be evaluated to determine that the Net Positive Suction Head Available NPSHA meets or exceeds the Net Positive Head Required NPSHR as stated by the pump performance curve WARNING Falling Object Hazard Eyebolts or lifting lugs if provided are for lifting only the components to which they are attached ...

Страница 4: ......

Страница 5: ... the suction valve closed or throttled This could result in cavita tion Cavitation will cause the pump performance to fall off and also overtime can cause impeller and or casing damage NOTE On 6x6x91 2 and 6x6x11 there will be volute and stuff box wear rings CAUTION Seal Damage Hazard Do not run pump dry seal damage may occur Failure to follow these instructions could result in property damage and...

Страница 6: ...hould be allowed to continue for a period of time before further tightening of the glands Take up gland bolts uniformly one flat at a time An adequate leakage rate is not one single value for all pumps and installations but is the amount required to provide adequate cooling and lubrication The required leakage will be largely influenced by operating pressure fluid temperature shaft speed etc For f...

Страница 7: ...ertain replaceable wearing parts The recommended inventory of spare parts depends upon the installation and the importance of continued operation For normal service with repairs to be made in the field the fol lowing parts are recommended for stock 1 set of packing rings complete 1 shaft sleeve 2 sets of wearing rings if provided 1 set of gaskets 1 lantern ring Parts should be ordered as far in ad...

Страница 8: ...qualified personnel LIMITATIONS The warranty does not cover defects that are caused by these situations Deficient maintenance Improper installation Modifications or changes to the product that are made without consulting an A C Fire Pump authorized representative Incorrectly executing repair work Normal wear and tear A C Fire Pump assumes no liability for these situations Bodily injuries Material ...

Отзывы: