www.75f.io       888.590.8995 x2

 

Mount  the  Smart  Node

  use  two #8-

1.5”  Sheet  metal  screws. 

Mount 

the  controller  so  that  the  antenna  points  straight  up.  The  controller 
may be mounted on the chassis of the unit or on the plenum. 

Mounting  the  Pressure  transmitter.

  The  transmitter  is  factory 

calibrated  and  should  be  installed  vertically  with  the  brass  fittings 
pointing  downward  and  the  arrow  on  the  label  pointing  upward.  If 
the unit must be installed flat there may be a zero shift. The shift can 
be corrected with the  zero-adjustment located inside the enclosure. 

To  adjust  the  zero,  both  pressure  ports  must  be  open  to  the 
atmosphere. If the span needs to be adjusted, please contact ACI. 

Mount the Interior Pickup Port 

through a ceiling tile.  

 

Mount the Exterior Pickup Port 

to the side of the RTU where it will not 

impede any door opening and in no direct vacuum like the OA intake 

or near any exhaust port.  
 

|

 

WIRING

 

 

 

24VAC

24VAC

Pickup 

Port

Exterior

Pickup 

Port

Interior

Fig.3

 

Содержание A/DP2 Series

Страница 1: ...olumn 75F solutions can regulate the pressure differential when the Pressure Sensor Package Solution is used in conjunction with a 75F Outside Air Optimization Package PRECAUTIONS Failure to wire devi...

Страница 2: ...ackage pressure control is possible SPECIFICATIONS 75F Pressure Controller Supply Voltage 24VAC Input 0 10VDC Operating Environment 41 F 122 F Enclosure Rainproof type 3R non metallic enclosure A DP2...

Страница 3: ...on the label pointing upward If the unit must be installed flat there may be a zero shift The shift can be corrected with the zero adjustment located inside the enclosure To adjust the zero both press...

Страница 4: ...below Wiring the A DP2 Use 18 3AWG to run power from the 75F controller to the pressure sensor as shown in Fig 3 The power for the A DP2 is internally connected so that the controller will power the A...

Страница 5: ...e Smart Node should read default room 1 Press the Right button on the Smart Node until Advertising is displayed 2 2 With the CCU Tablet within 20 of the Smart Node press Pair Pressure Sensor from Setu...

Страница 6: ...w tab will appear titled Summary In the Summary tab look at the Pressure Sensor section and check that there are rational values being displayed for the differential pressure Typical differential pres...

Страница 7: ...ied foam is missing No pressure value If there is no differential pressure value displayed in the system summary first use your voltmeter to check that there is a DC signal of 5VDC being sent to the c...

Отзывы: