4.3 Installer Menu
Installer Menu Options
(Press and hold
▼
AND
▲
for
5 seconds
for installer menu)
Description
Menu Screen
Sub Menus
Installer Menu
INSTALLER MENU
PRESS >
Press and hold
▼
AND
▲
for
5 seconds
for installer
menu, you will then see this screen, press
►
to
continue to installer menu.
View Readings
INSTALLER MENU
View Readings
View Readings
AC Volts: 245V
AC Volts
Shows AC mains voltage at present.
The display will update approximately every 2 seconds.
View Readings
Grid I: 12.5A
Grid I
Shows AC mains current at clamp.
The display will update approximately every 2 seconds.
View Readings
Load I: 8.2A
Load I
Shows AC mains current applied to load.
The display will update approximately every 2 seconds.
View Readings
Temperature: 38C
Temperature
Shows internal temperature on the immerSUN.
The display will update approximately every 2 seconds.
Clamp
INSTALLER MENU
Clamp (Wired)
Clamp Type
The clamp type is shown, the clamp type can only be
changed by resetting the unit.
Cascade
INSTALLER MENU
Cascade (Off)
Cascade Mode
When cascading several immerSUN's to control several
loads, Cascade should be set to ON
Set Load
The output can be set
to a given percentage
for testing purposes
INSTALLER MENU
Set Load (Auto)
SET LOAD
>Auto<
Auto (Normal mode)
Set output to automatically track exported power.
SET LOAD
>100%<
Manual
Manually set output power for testing purposes only.
Relay Function
The internal multi-
function relay can be
set to operate as one
of 8 different functions.
(The currently enabled
option is shown in
brackets).
See appropriate wiring
diagram for chosen
relay function
INSTALLER MENU
Relay (OFF)
RELAY FUNCTION
>When Heating<
When Heating
Relay is on when output is heating water.
RELAY FUNCTION
>Two Heaters<
Two Heaters (2 Heater)
Use relay to switch load output between two heaters.
Heater no.1 output takes priority (see wiring diagram).
Heater no.2 output only heats when no.1 is fully heated.
NB: When heating no.2, the output is switched back to
heater no.1 every 15mins to check if more heat is
required.
RELAY FUNCTION
>Water Boost<
Water Boost (Boost)
Relay controls boiler to heat water when in water boost
mode, rather than using the immersion heater.
RELAY FUNCTION
>De-strat Pump<
De-stratification Pump (De-strat)
Relay controls cylinder de-stratification pump.
Pump is activated when immersion thermostat opens
and runs until thermostat closes again.
(The immersion thermostat is checked only once a
minute so there may be a delay before the pump stops).
16