78-8135-6695-3-C
12.2 Clean and lubricate O-ring.
12.3 Replace dome and engage latch over dome ear
as shown.
12.4 Fully close latch to seat dome onto the base.
12.5 Assembled unit can be flash tested at 5.8 PSI (40kPa)
MAX.
Caution
Vent pressure after flash testing.