3M DBI-SALA 2100041 Скачать руководство пользователя страница 9

9

3.0 INSTALLATION

 

;

The owner of this equipment may contact 3M Technical Services with any questions regarding equipment installation, use, 

or inspection.

 

;

Installation of the DBI-SALA Concrete Bolt Anchor must be performed or supervised by a Competent Person

 

for Non-

Certified Anchorages. A Qualified Person

1

 shall supervise the design, selection, installation, use, and inspection of Certified 

Anchorages.

3.1 PLANNING:

 Plan your Fall Protection system prior to installation of the Concrete Bolt Anchor. Account for all factors that 

may affect your safety before, during and after a fall. Consider all requirements, limitations and specifications defined in 

Section 2 and Table 1. Select a concrete location that is free of any cracks or other defects that could affect the strength 

of the concrete structure.

1

 

;

3M shall make available upon request information that is necessary for the design and planning of systems.

3.2 

INSTALLING THE CoNCrETE BoLT ANCHor:

  The Concrete Bolt Anchor can be installed in concrete meeting the 

anchorage requirements specified in Table 1. See Figure 7 for proper loading of the Concrete Bolt Anchor. Figure 8 

illustrates installation of the Concrete Bolt Anchor. To install the Concrete Bolt Anchor:
1.  Mark the location for the placement of the Concrete Bolt Anchor. Observe minimum edge distance and spacing 

requirements as specified in Figure 9. 

2. 

Use a rotary hammer and an 18-mm, 11/16-inch, or 3/4-inch bit to drill a hole to a depth of 4 1/8 in (10.5 cm). 

Clean the hole using a blow-out bulb or compressed air. The hole must be free of debris for the Concrete Bolt Anchor 

to develop full strength.

3.  Use a hammer to drive the Concrete Bolt Anchor into the hole. The Concrete Bolt Anchor must be seated firmly 

against the D-Ring Bracket. Do not expand the anchor bolt by hand before installation.

4.  Tighten the bolt using a 24 mm wrench. The red cap will shear off at the appropriate torque and the green seal on 

the bolt head indicates that the anchor has tightened properly. A torque wrench is not required for installation. When 

the red cap has sheared off the anchor, no further adjustment is necessary.

 

;

Do not use an impact driver or drill for installation of the Concrete Bolt Anchor. Only a wrench should be used for 

torquing of the Concrete Bolt Anchor.

4.0 USE

4.1 

BEForE EACH USE:

 Verify that your work area and Fall Protection system meet all criteria defined in these instructions. 

Verify that a formal Rescue Plan is in place. Inspect the Concrete Bolt Anchor per the ‘

User

’ inspection points defined on 

the “

Inspection and Maintenance Log

”. If inspection reveals an unsafe or defective condition, or if there is any doubt about 

its condition for safe use, remove the Concrete Bolt Anchor from service immediately. Clearly tag the system “DO NOT 

USE”. See Section 5 for more information.

4.2 

FALL ArrEST CoNNECTIoNS:

 The Concrete Bolt Anchor is designed for use in several applications. The connector is in 

compliance with ANSI Z359.18 Type A. The product applications are: 

• 

Attachment of a Fall Arrest system:

 Full Body Harness and connecting subsystem, such as an SRD or Energy-

Absorbing Lanyard. See Figure 10a. 

• 

restraint:

 Full Body Harness and lanyard or restraint line. See Figure 10b.

• 

Work Positioning:

 Full Body Harness, positioning lanyard and a back-up Fall Arrest system. See Figure 10c.

• 

Suspension:

 Full Body Harness, boatswains’s chair or seat board, and a back-up Fall Arrest system.

• 

rescue system:

 Configured, depending on the type of rescue, to an anchorage. 

4.3 rEMoVAL:

 The Concrete Bolt Anchor can be removed by loosening the bolt with a 19 mm wrench. Parts of the Concrete 

Bolt Anchor bolt will remain in the hole permanently. After removal, the hole should be filled with grout or sealant to 

prevent reuse of the hole. The bolt cannot be reused and must be destroyed after removal.

4.4 rEUSE:

 The flanged spacer and D-ring components may be reused if they have not been subjected to a fall force. The 

replacement bolt model numbers are shown in Figure 1. Refer to the previous section for removal instructions. Assemble 

the Concrete Bolt Anchor using DBI-SALA supplied parts as seen in Figure 2. The components should be assembled on the 

bolt in the following order: flat washer, D-ring bracket, flanged spacer, black plastic spacer, expansion sleeve, and cone 

nut. The D-ring bracket must fit over the flanged spacer and rotate freely. Two tabs on the plastic spacer must engage the 

matching slots on the expansion sleeve as seen in Figure 2. Do not expand the anchor bolt by hand prior to installation. 

5.0 INSPECTION

 

;

After product has been removed from service, it may not be returned to service until a Competent Person confirms in 

writing that it is acceptable to do so.

5.1 

INSPECTIoN FrEQUENCY:

 The product shall be inspected before each use by an authorized person and, additionally, 

by a Competent Person other than the user at intervals of no longer than one year. A higher frequency of equipment use 

and harsher conditions may require increasing the frequency of Competent Person inspections. The frequency of these 

inspections should be determined by the Competent Person per the specific conditions of the worksite.

1  Qualified Person:

 An individual with a recognized degree or professional certificate, and extensive experience in Fall Protection. This indi

-

vidual must be capable of design, analysis, evaluation, and specification in Fall Protection.

Содержание DBI-SALA 2100041

Страница 1: ...OSHA A B C D 2104560 x1 x1 4 44 in 11 28 cm 1 09 in 2 77 cm 3 02 in 7 67 cm 5 83 in 14 81 cm 2104568 x1 x1 4 44 in 11 28 cm 1 09 in 2 77 cm 3 02 in 7 67 cm 5 83 in 14 81 cm 2100041 x0 x1 4 44 in 11 28 cm 2100066 x0 x10 4 44 in 11 28 cm C D ANSI Z359 18 Type A OSHA 1926 502 OSHA 1910 140 ...

Страница 2: ...2 2 A C B D E F G H 3 4 C B A FC B C FC ...

Страница 3: ...A B C D E F G A B C 7 8 1 s s c c d 2 4 1 8 in 10 5 cm 18 mm 11 16 in 3 4 in 3 4 9 c 15 0 in 38 1 cm h 6 25 in 15 9 cm s 10 0 in 25 4 cm y 4 13 in 10 5 cm d 18mm 11 16 in 3 4 in 3000 psi 20 7 MPa h c s c y d ...

Страница 4: ... concrete Tighten bolt until red cap shears off No further adjustment is necessary after red cap shears off INSTALLATION Step 1 Step 2 Step 3 Step 4 Step 5 Concrete minimum compressive strength 3000 psi Not for use in lightweight concrete hollow block brick grout or stone 9501359 REV D Hole Depth 4 1 8 in INSPECTION Inspect anchor before each use Green seal on bolt head indicates proper installati...

Страница 5: ...ible and meet the requirements of applicable standards including the ANSI Z359 or other applicable fall protection codes standards or requirements Always consult a Competent or Qualified Person before using these systems CONCRETE ANCHORS Do not use device in wet or uncured concrete hollow block stone wood or other substrates or materials CONCRETE ANCHORS Prior to installation of device in an exist...

Страница 6: ...tified to ANSI Z359 18 2017 have also been tested in compliance with the requirements of ANSI Z359 7 ANSI compliance and testing covers only the product and does not extend to the anchorage structure or substrate to which the product is attached Anchorage Strength Structure must meet dimensional requirements from Figure 9 Anchorage strength must comply with Section 2 1 requirements If the user is ...

Страница 7: ...tached to an anchorage the strengths stated above must be multiplied by the number of systems attached to the anchorage See ANSI Z359 2 for more information 2 2 PERSONAL FALL ARREST SYSTEM Figure 1 illustrates the application of this Anchorage Connector Personal Fall Arrest Systems PFAS used with the system must meet applicable Fall Protection standards codes and requirements The PFAS must incorpo...

Страница 8: ...ty Connectors hooks carabiners and D rings must be capable of supporting at least 5 000 lbf 22 2 kN Connectors must be compatible with the anchorage or other system components Do not use equipment that is not compatible Non compatible connectors may unintentionally disengage see Figure 5 Connectors must be compatible in size shape and strength If the connecting element to which a snap hook or cara...

Страница 9: ...eveals an unsafe or defective condition or if there is any doubt about its condition for safe use remove the Concrete Bolt Anchor from service immediately Clearly tag the system DO NOT USE See Section 5 for more information 4 2 FALL ARREST CONNECTIONS The Concrete Bolt Anchor is designed for use in several applications The connector is in compliance with ANSI Z359 18 Type A The product application...

Страница 10: ...nce or scheduled for maintenance should be tagged DO NOT USE These equipment tags should not be removed until maintenance is performed 6 1 CLEANING Periodically clean the Concrete Bolt Anchor s metal components with a soft brush warm water and a mild soap solution Ensure parts are thoroughly rinsed with clean water 6 2 SERVICE Only 3M or parties authorized in writing by 3M may make repairs to this...

Страница 11: ...the requirements of Table 1 Verify that the concrete is free of any cracks or damage Fall Protection Equipment Additional Fall Protection equipment that is used with the system should be installed and inspected per the manufacturer instructions Serial Number s Date Purchased Model Number Date of First Use Corrective Action Maintenance Approved By Next inspection due Date Corrective Action Maintena...

Страница 12: ...quire product be returned to its facility for evaluation of warranty claims This warranty does not cover product damage due to wear abuse misuse damage in transit failure to maintain the product or other damage beyond 3M s control 3M will be the sole judge of product condition and warranty options This warranty applies only to the original purchaser and is the only warranty applicable to 3M s fall...

Отзывы: