12.4 Remove constant force spring. Bend shield wires back upon cable jacket 1" (25 mm). Cut excess shield wire
and discard (
Figure 17
).
6 3/4" (171 mm)
1" (25 mm)
Semi-Conductive Jacket
Fold Back Shield Wires
Depth Of Terminal Lug + Growth Allowance
Figure 17
12.5 Remove semi-conductive jacket to dimension shown in
Figure 18
.
NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring cut 80% through
jacket. Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CON JACKET.
Remove constant force spring.
NOTE: It is imperative to remove all remnants of the semi-conductive jacket, even if the semi-conductive jacket
comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.
Depth Of Terminal Lug + Growth Allowance
4 3/4" (121 mm)
1" (25 mm)
Semi-Conductive Jacket
Cut Line
Constant Force Spring
Fold Back Shield Wires
2" (51 mm)
Figure 18