7. CONTROL
Service hardware:
Intended for additional functions setup (READ/WRITE)
Address
Name
Info
Min. Value
Max. Value
Default
Service register - (Factory reset no effect)
25000
Modbus1
Modbus adress port 1
1
247
1
25001
HeaterCoolDownTime
minutes
1
5
5
25002
HeaterCoolDownFlow
%
Factory_Driver 10003
Factory_Driver 10002
20
25003
LostCommunicattion-
Protect
0
1
0
info:
(Status register - READ ONLY)
Address
Name
Info
Min. Value
Max. Value
Default
Status register - read only (Factory reset no effect)
15000
UnitStatus
0-OFF
1-ON
2-COOLDOWN
0
2
15001
Sensor Status
1 - TempEXT1_Error
0 - TempEXT1_OK
0
1
15002
StatusDI1
1 - DI_open
0 - DI_closed
0
1
15003
StatusDI2
1 - DI_TACHO_pulzy
0 - DI-TACHO_error
0
1
15004
AirFlowFanManual
0% = OFF
1%-20% = 1. speed
21% - 40% = 2. speed
41% - 60% = 3. speed
61% - 80% = 4. speed
81% - 100% = 5. speed
0
100
15005
AirFlowFanManualEC
0% = OFF
1% - 100% = % PWM
0
100
15006
PowerPostheater1
Electric version:
0% = OFF, 1% až 50% = Heat1, 51% až 100% = Heat2
Water version:
0% = OFF, 1 až 100% = Heat1
0
100
15007
TempEXT1
°C (temp * 10)
-400
1000
15008
TempEXT1
°F (temp * 10)
-400
2120
Address
Name
Info
Min. Value
Max. Value
Default
10007
Modbus Baudrate
0-4800
1-9600
2-19200
3-38400
0
3
1
10008
Modbus Parity
0-NONE
1-ODD
2-EVEN
0
2
2