7. CONTROL

MODBUS failure codes

Code Name

Meaning

01

Illegal function

The requested function is not supported by server

02

Illegal data address

The entered address is out of the range supported by server

03

Illegal data value

The transmitted data is not valid

04

Device failure

An unremovable failure occured while executing the request

05

Confirmation

Code intended for use at programming. The server reports the reception of a valid request but 

the execution will take a longer timeu

06

Device is busy

Code intended for use at programming. The server is busy with executing a long-standing 

command

08

Memory parity failure

Code intended for use at work with files. Server discovered a parity failure while trying to 

read the file

Supported telegrams Modbus, Modbus Module*

MODBUS failure coder

Code Name

Meaning

03

READ HOLDING REGISTER   

according to Modbus standard

04

READ INPUT REGISTER

according to Modbus standard

06

WRITE REGISTER  

according to Modbus standard

16

WRITE MULTIPLE REGISTERS

according to Modbus standard

Examples of communication:

Operational data reading:

 It is possible to read all operational data of the unit from addresses 15000 to 15008.

Example 1: 

Start of the unit, flow rate 60%. 

address → value

21000  →  0x01

21001  →  60 (max. flow rate = address 10002)

Turning off the unit:
21000  →  0x00

Содержание IC-ModBus

Страница 1: ...INSTALLATION AND SERVICE MANUAL IC ModBus EN H04 0221 0216 00 1 1 P04 0221 0216 00 ...

Страница 2: ...e properly read the whole manual The manufacturer reserves the right to make changes including the technical documentation without prior notice Please save this manual for future use The service manual is a part of the product Conformity declaration The product has been designed manufactured placed on the market complies with all applicable regulations and is in compli ance with the requirements o...

Страница 3: ... supplier Never try to put a damaged product into operation If a product is not unpacked immediately after delivery it has to be stored in a dry interior with a maximum tempera ture range from 5 C to 40 C This product should not be used by persons including chil dren whose physical sensory or mental disability or lack of experience and knowledge is insufficient for the safe use of the product if t...

Страница 4: ...ss since 1995 5 TECHNICAL SPECIFICATIONS Type Number of phases pcs Voltage V Frequency Hz Max fans current A Weight kg IC M AC5 04 1 230 50 60 4 13 5 IC M AC5 07 1 230 50 60 7 15 IC M AC5 16 1 230 50 60 16 23 4 DIMENSIONS Dimensions for wall mounted regulation ...

Страница 5: ...disassembling The regulator is attached using screws and dowels on a wall or bolts There must not be any flammable materials within a distance of 100 mm from the regulator TECHNICAL INFORMATION After installation of the regulator on the wall we recommend se parating the inner part electronics transformer from the regula tion box for easier manipulation 1 2 6 3 ELECTRICAL WIRING AND ELECTRICAL ASSE...

Страница 6: ...driver 10005 17 TACHO EC motor IC ModBus is ready for control of AC and EC motors 6 4 DESCRIPTION OF CONNECTORS Description electric heat Description water heat L Power supply phase 230V N Neutral bridge N Grounding bridge PE L Fan Fan control phase output Heat 1 Heating degree 1 electric heat output 230V with Imax 3A Controlling voltage of the actua ting mechanism water heat output 230V Heat 2 He...

Страница 7: ...ELECTRIC HEAT 6 6 EXAMPLE OF WIRING OF SHUTTER WITH WATER HEAT L FAN L L L Heat1 Heat2 L1 L2 L3 L FAN L L L Heat1 Heat2 Servodrive water valve Fan motor IC ModBus BMS External con tact Input Temperature sensor Input IC ModBus Fan motor Electric heat 1 level 2 level PE N BMS External contact Input Temperature sensor Input PE N ...

Страница 8: ...between the characters must not be longer than 1 5 character The beginning and end of the message is identified according to the bus rest longer than 3 5 character The RTU frame format is shown in the picture General structure of telegram hex Beginning Address Function Data CRC End 3 5 characters 8 bits 8 bits N 8 bits 16 bits 3 5 characters Data block length Size of ADU on RS 485 253 bytes PDU ad...

Страница 9: ...ster read only Factory reset no effect 15000 UnitStatus 0 OFF 1 ON 2 COOLDOWN 0 2 15001 Sensor Status 1 TempEXT1_Error 0 TempEXT1_OK 0 1 15002 StatusDI1 1 DI_open 0 DI_closed 0 1 15003 StatusDI2 1 DI_TACHO_pulzy 0 DI TACHO_error 0 1 15004 AirFlowFanManual 0 OFF 1 20 1 speed 21 40 2 speed 41 60 3 speed 61 80 4 speed 81 100 5 speed 0 100 15005 AirFlowFanManualEC 0 OFF 1 100 PWM 0 100 15006 PowerPost...

Страница 10: ...e to process it normally it returns a normal answer to the client If a server does not receive a request due to a communication failure it does not return any answer On the side of the client the time limit for answer receipt expires If a server receives a request but detects a communication failure parity CRC it does not return any answer On the side of client the time limit for answer receipt ex...

Страница 11: ...intended for use at programming The server is busy with executing a long standing command 08 Memory parity failure Code intended for use at work with files Server discovered a parity failure while trying to read the file Supported telegrams Modbus Modbus Module MODBUS failure coder Code Name Meaning 03 READ HOLDING REGISTER according to Modbus standard 04 READ INPUT REGISTER according to Modbus st...

Страница 12: ...ntact our customer service or technical support department Contact 2VV s r o Fáblovka 568 533 52 Pardubice Czech Republic Internet http www 2vv cz Copyright 2VV All rights reserved The producer is not responsible for damages incurred on the device which were caused by an inexpert installation and service which are contrary with the manual and conventions during installation and service of ventilat...

Отзывы: