9. TROUBLESHOOTING
ATTENTION!
● Before and during maintenance and repairs,
the unit must be disconnected from the power
supply, which must be locked, and the service
switch in 0 position (off).
● Do not perform repairs if you aren’t sure or don’t
know the exact procedure; contact a specialised
service!
● Malfunctions are usually signalled with a mes
-
sage on the display. See table below.
TECHNICAL DATA
Description
Unit's be
-
haviour
Likely problem
Solution
4 – Supply fan error Unit is not
working
Overheated fan or defect on
thermal contact of inlet fan
Determine the cause of the overheating (de
-
fective bearing, short-circuit...) or replace the
engine.
5 – Exhaust fan
error
Unit is not
working
Overheated fan or defect on
thermal contact of inlet fan
Determine the cause of the overheating (de
-
fective bearing, short-circuit...) or replace the
engine
6 - Inlet filter
clogged
Unit is ven
-
tilating
Clogged filter
If the unit does not have a pressure sensor for
the filter, RESET the clogged filter according to
the manual.
7 – Exhaust filter
clogged
Unit is ven
-
tilating
Clogged filter
Check the condition of the filter, or replace it. If
the unit does not have a pressure sensor for the
filter, RESET the clogged filter according to the
manual.
8 - Failure in pre
-
heating 1
Unit is ven
-
tilating
Preheated electric exchang
-
er or damaged sensor Open
exchanger’s thermostat
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
preheating for damages.
9 - Failure in ex
-
changer 1
Unit is ven
-
tilating
Preheated electric exchang
-
er or damaged sensor Open
exchanger’s thermostat
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
reheating for damages.
10 - Failure in ex
-
changer 2
Unit is ven
-
tilating
Preheated electric exchang
-
er or damaged sensor Open
exchanger’s thermostat
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
reheating for damages.
11 - Failure in pre
-
heating 2
Unit is ven
-
tilating
Preheated electric exchang
-
er or damaged sensor Open
exchanger’s thermostat
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
preheating for damages.