background image

8

2VV.

 Creating innovative solutions for you and your business since 1995.

INPUTS AND OUTPUTS

Inputs:

RT - Room thermostat
NOTE: Not used for ambient version of controller
• 

Input is set to connect an external, potential-free contact of room thermostat to switching on / off heating outputs H1 and H2 

according state of room thermostat

• 

Controller responds to the connected/disconnected contact on the input (switching on / off heating), fan continues to run normally 

• 

Default connection: connected contact (electrical bridge)

• 

Connected contact = Heating outputs H1 or H1and H2 is ON if heating is set to be used

• 

Disconnected contact = Heating outputs H1, H2 is OFF, even if heating is set to be used

DOOR – Door contact (room thermostat, external switch)
• 

Input is set to connect an external, potential-free door contact or room thermostat or external switch, to switch ON/OFF fan output 

and heating outputs.  

• 

Controller responds to the connected/disconnected contact on the DOOR input, switching on / off whole controlled product. After 

OFF command is received the 5 seconds overrunning time is applied and then controlled product is set to OFF mode.

• 

Default connection: disconnected contact (without electrical bridge)

• 

Connected contact = product is switched to OFF (overrunning time is applied)

• 

Disconnected contact = controlled product runs on preset fan speed value and heating output 

Outputs:

HEAT 1 – H1 (potential free output on board connected with terminal COM - Relay)
NOTE: Not used for ambient version of controller
• 

Controlled heating equipment of the controlled product is connected to terminal H1 - e.g.: 1st stage of heating by contactor

• 

Terminal COM is designated as input for control signal of the heating. Maximum load of relay contact is 230V/5A (Control signal 

for heat can be used according installation needs e.g. 24VAC, 24VDC, 230VAC, depend on ON/OFF actuator selection)

• 

Connection output H1 is handled as 1st heating stage (contactor control signal or three-way valve opening phase)

• 

H1 output is switching power led to terminal COM

Functionality:
• 

HEAT 1  (H1) output is active only when control voltage to the ec fan speed output overcorss value 1,7V at last. (WARNING: Be 

sure that controlled EC fan in the product is able to start before 1,7V control signal, to avoid start heating earlier then fan starts!!!) 

• 

HEAT 1  (H1) output is active when starting 1st stage of heating as well as at start of 2nd heating stage HEAT 2 (H2) = HEAT 

outputs are switched in cascade

• 

HEAT 1 (H1) output is inactive in case room thermostat contact connected to ROOM THERMOSTAT (RT) input is disconnected.

HEAT2 – H2 (potential free output on board connected with terminal COM - Relay)
NOTE: Not used for ambient version of controller
• 

Controlled heating equipment of the controlled product is connected to terminal H2 - e.g.: 2nd stage of heating by contactor

• 

Terminal COM is designated as input for control signal of the heating. Maximum load of relay contact is 230V/5A (Control signal 

for heat can be used according installation needs e.g. 24VAC, 24VDC, 230VAC, depend on ON/OFF actuator selection)

• 

Connection output H2 is handled as 2nd heating stage (contactor control signal or three-way valve opening phase)

• 

H2 output is switching power led to terminal COM

Functionality:
• 

HEAT 2  (H2) output is active only when control voltage to the EC fan speed control output overcross 5V. 

• 

HEAT 2  (H2) output is active when 2nd heating stage is selected and fan control signal value overcross the limit for 2nd heating 

stage enable. Then HEAT 2 (H2) output is activated. HEAT outputs are switched in cascade, it means that H1 output is active 

when H2 is active.

• 

HEAT 2 (H2) output is inactive in case room thermostat contact connected to ROOM THERMOSTAT (RT) input is disconnected.

0-10V/GND FAN speed output: Terminals: 0-10V, GND (Analog EC Fan Control Output)

• 

Output designed for stepless of EC fans control in range 0-10V signal. Maximum starting voltage signal for EC fan must be lower 

or equal to 1,7V, because 1,7V is the value when Heat 1 output is activated.

• 

Heat 2 output is activated when fan speed control signal overcross 5V. 

• 

The maximum number of EC fans connected to this output is 10.

WARINING: Be sure that controlled EC fan in the product is able to start before 1,7V control signal, to avoid start heating 

earlier then fan starts!!!

WARINING: Length and execution of fan speed control signal cabling has influence of voltage drop of the signal 0-10V! 

Measure voltage of the control signal, on fan speed control input on the controlled fan to be sure that fan starts before 

heating outputs are activated. 

Содержание AirGENIO

Страница 1: ...Installation and operation instructions EN AirGENIO BASIC EC controller...

Страница 2: ......

Страница 3: ...carefully Proceed exactly according to the instructions stated here in order to install controller properly and safely Do not put the device into operation unless you are thoroughly acquainted with al...

Страница 4: ...troller from the box DEVICE DESCRIPTION INTRODUCTION AirGENIO BASIC EC controller is designed to control the air curtains and heating units with electric or water coils using manual heating control an...

Страница 5: ...an speed heating enabled Heat level 1 and 2 enable 4 High fan speed heating enabled Heat level 1 and 2 enable 5 Heat switch Water heater Heat level 1 Electric heater Heat level 1 and 2 1 2 3 4 5 OPERA...

Страница 6: ...NTROLLER SWITCH FOR 1ST HEAT STAGE FACTORY CONNECTED S COM OF INTERNAL HEAT SWITCH FACTORY CONNECTED S2 SWITCH FOR 2ND HEAT STAGE FACTORY CONNECTED RT ROOM THERMOSTAT DI SWITCHING ON OFF HEAT OUTPUTS...

Страница 7: ...lled EC fan in the product is able to start before 1 7V control signal to avoid start heating earlier then fan starts HEAT 1 H1 output is active when starting 1st stage of heating as well as at start...

Страница 8: ...ative solutions for you and your business since 1995 WIRING EXAMPLES BASIC EC AGBA1 M ECx xx E2 with two EC fans and electric heater with two steps of heating BASIC EC AGBA1 M ECx xx V1 with two EC fa...

Страница 9: ...10 2VV Creating innovative solutions for you and your business since 1995 BASIC EC AGBA1 M ECx xx S0 with two EC fans BASIC EC AGBA1 M ECx xx V1 with two EC fans Electric heater with one step...

Страница 10: ...PERATION When disposing of the controller follow relevant regulations on waste disposal It is best to dispose of components at a specialised collection point to ensure recyclable materials are reused...

Отзывы: