7

2VV.

 Creating innovative solutions for you and your business since 1995.

CONTROL DESCRIPTION

Controller allows:

• 

Control EC motors by stepless 0-10V output

• 

Control the power of the heating in range OFF/1st stage/2nd stage, by potential free relay outputs with maximum load of relay 

230V/5A. NOTE: Not available for ambient version of controller

• 

Connect door contact or external swich (turning OFF whole product after contact opening)

• 

Connect the room thermostat (turn OFF the heater after contact opening) - 

NOTE: Not available for ambient version of controller

TERMINAL

FUNCTIONALITY

DESCRIPTION

S1

INPUT FOR  INTERNAL

HEAT SWITCH OF CONTROLLER

SWITCH FOR 1ST HEAT STAGE (FACTORY CONNECTED)

S

COM OF INTERNAL HEAT SWITCH (FACTORY CONNECTED)

S2

SWITCH FOR 2ND HEAT STAGE (FACTORY CONNECTED)

RT

ROOM THERMOSTAT

DI SWITCHING ON/OFF HEAT OUTPUTS ONLY 

(FACTORY CONNECTION = EL. BRIDGE)

COM

COM HEATING

INPUT  FOR HEAT. CONTROL SIGNAL (MAX. LOAD 230V/5A)

H1

1ST HEATING STAGE

OUTPUT OF 1ST HEATING STAGE

H2

2ND HEATING  STAGE

OUTPUT OF 2ND HEATING STAGE

DOOR

DOOR CONTACT

(EXT CTRL, ROOM THERMOSTAT)

DI SWITCHING ON/OFF

 WHOLE CONTROLLER 

(FAN AND HEATING)

0-10V DC

 0-10V FAN SPEED

OUTPUT FOR FAN SPEED CONTROL 

(MAX. 10PCS)

GND

 GND FAN SPEED

~230V

L - 230VAC

POWER SUPPLY 230V

N - 230VAC

NOTE: Terminals S1, S, S2, RT, COM, H1, H2 not used for ambient version of controller. Ambient version supports only fan control and 

connection of external contact on terminals DOOR. (Door switch, external control switch,...)

Содержание AirGENIO

Страница 1: ...Installation and operation instructions EN AirGENIO BASIC EC controller...

Страница 2: ......

Страница 3: ...carefully Proceed exactly according to the instructions stated here in order to install controller properly and safely Do not put the device into operation unless you are thoroughly acquainted with al...

Страница 4: ...troller from the box DEVICE DESCRIPTION INTRODUCTION AirGENIO BASIC EC controller is designed to control the air curtains and heating units with electric or water coils using manual heating control an...

Страница 5: ...an speed heating enabled Heat level 1 and 2 enable 4 High fan speed heating enabled Heat level 1 and 2 enable 5 Heat switch Water heater Heat level 1 Electric heater Heat level 1 and 2 1 2 3 4 5 OPERA...

Страница 6: ...NTROLLER SWITCH FOR 1ST HEAT STAGE FACTORY CONNECTED S COM OF INTERNAL HEAT SWITCH FACTORY CONNECTED S2 SWITCH FOR 2ND HEAT STAGE FACTORY CONNECTED RT ROOM THERMOSTAT DI SWITCHING ON OFF HEAT OUTPUTS...

Страница 7: ...lled EC fan in the product is able to start before 1 7V control signal to avoid start heating earlier then fan starts HEAT 1 H1 output is active when starting 1st stage of heating as well as at start...

Страница 8: ...ative solutions for you and your business since 1995 WIRING EXAMPLES BASIC EC AGBA1 M ECx xx E2 with two EC fans and electric heater with two steps of heating BASIC EC AGBA1 M ECx xx V1 with two EC fa...

Страница 9: ...10 2VV Creating innovative solutions for you and your business since 1995 BASIC EC AGBA1 M ECx xx S0 with two EC fans BASIC EC AGBA1 M ECx xx V1 with two EC fans Electric heater with one step...

Страница 10: ...PERATION When disposing of the controller follow relevant regulations on waste disposal It is best to dispose of components at a specialised collection point to ensure recyclable materials are reused...

Отзывы: