2iB SC10 Скачать руководство пользователя страница 4

 


 

Measured current when pump is snoring = 50% (50 Amps) 

Current Window = 10% (10 Amps) 

So, the Stop Current Setpoint is loaded with 50% + 10% = 60% (60 Amps) 

The Current Window should be set to enable a Stop Current Setpoint to be set in between the Normal Running Current and the 
Snoring Current. 

If on the next pump run the measured snoring current is 55% (55Amps) then this will still be detected as snoring and the pump 
will be stopped.  

Single Phase Motors 

Snore detection works identically on single-phase motors as it does on three-phase motors.  Note however that on smaller motors 
(single- or three-phase) the variation of current with load will be smaller which may make the setup more critical.  In particular, 
the Current Window setting may need to be smaller.  Take a note of the current reading displayed on the SC10 and compare that 
for normal operation and snoring and use this as a guide. 

5.

 

SC10 Set Up 

The initial set up of the relay is done by setting these parameters: 

1.

 

CT Current Range 

2.

 

Pump Cycle Time 

3.

 

Alarm Relay Activation Conditions 

4.

 

Float Switch Contact Status 

5.

 

Current Window % 

6.

 

Stop Current Setpoint 

5.1

 

Current Range & Current Transformer Selection 

The SC10 uses a 4-20mA Current Transformer (CT) to measure the motor current.  The selected current transformer rated primary 
current  should  be  close  to  the  full  load  current  of  the 
connected  load  for  optimal  accuracy  but  should  not 
exceed it. Multiple turns of the motor phase wire could 
be made through the CT to better match the motor rated 
current to the CT. 

In the circumstance that this isn’t achievable there are 
four current range dip switch selections available 100%, 
50%, 25% and 12.5% that increases the current percentage display providing full scale set point ranging setting 

 i.e. if you have a 0-100 CT with a 50 Amp full load current the output is 
only 4mA to 12mA and the percentage of current displayed will only be 
50% by switching dip switch 2 (50%) on it increases the display range 
resolution to 100% providing full range selection. 

Tip:  For  best  accuracy,  use  (1)  Multiple  turns  through  the  CT  or  (2) 
Selectable range on the CT in preference to (3) Setting a lower range on the 
SC10. 

See also section 11 Examples of CT Range and Setup for Starter Panels. 

Single Phase Motors.  See also the note about single-phase motors in section 4.1 Snoring Detection Explained

5.2

 

Pump Run Time Target 

When the SC10 is first commissioned a pump run time target should be set, 
the  run  time  selection  should  reflect  the  time  the  sump  or  container  is 
currently taking to empty by the installed pump.   The stop or pause time 
duration is controlled by the SC10 controller and will vary based on run and 
stop  history  and  programmed  adaptive  control  algorithm  to  attempt  to 
achieve  the  target  run  time.    Setting  a  pump  cycle  time  target  via  DIP 
switches. 

Tip: If the level in the sump rises too high then select a shorter Cycle Time.  
Conversely if you want the level to rise higher before the pump starts then 
select a longer Cycle Time. 

Current Range 

SW 

Setting 

 

Off 

Off 

100% (default) 

 

Off 

On 

50% 

 

On 

Off 

25% 

 

On 

On 

12.5% 

Pump Run Time Target 

SW 

Setting 

 

Off 

Off 

Off 

3 min 

 

Off 

Off 

On 

5 min  (default) 

 

Off 

On 

Off 

8 min 

 

Off 

On 

On 

15 min 

 

On 

Off 

Off 

30 min 

 

On 

Off 

On 

1 h 

 

On 

On 

Off 

2 h 

 

On 

On 

On 

4 h 

Содержание SC10

Страница 1: ...SC10 Single Pump Controller Installation and User Manual ...

Страница 2: ...ations To ensure accuracy and reliability screened twisted pair cable is to be used for connection of the Current Transducer for measuring the pump motor current 3 2 Remote Snoring Setup Controls for Operator Safety The Stop Current Setpoint can be set and adjusted using pushbuttons on the front of the pump starter control panel This enables the pump setup commissioning and setpoint adjustment to ...

Страница 3: ...elps clear the impellor and the suction strainer of debris reducing the chance of blockage and cavitation as well as increasing the flow rate and efficiency Start up of the SC10 The SC10 will normally start the pump 30 Seconds after start up The pump will run until a stop condition is reach snoring is detected or the stop low float is activated This pump start will not occur if the stop low float ...

Страница 4: ...CT In the circumstance that this isn t achievable there are four current range dip switch selections available 100 50 25 and 12 5 that increases the current percentage display providing full scale set point ranging setting i e if you have a 0 100 CT with a 50 Amp full load current the output is only 4mA to 12mA and the percentage of current displayed will only be 50 by switching dip switch 2 50 on...

Страница 5: ...6 7 8 9 on front of SC10 CT Fault diagnostic monitoring of CT Sump Low Sump High Failed to Run pump called to run no current detected 5 5 Stop Low Level Switch Invert If a low level switch is used then the switch contact status needs to be set to normally open or closed Ref DIP Switch 10 on front of SC10 Tip If both the High and Low Level Switches are the same and their contacts close when the flo...

Страница 6: ...int Adjustment An additional adjustment method is by using the up and down buttons independently By pushing the up or down button it will adjust the stop current threshold to the user s desired value as a percentage of CT current Note This settings is non volatile It is stored through power cycles of the SC10 6 Display and LED Indication 6 1 Current Display PA PAUSING Pump is Pausing CL CLEANING P...

Страница 7: ...nected to terminals 7 and 9 Ensure installed 4 20mA CT is correct range for installed load The pump stops although it is not snoring Ensure the inhibit low float input is not activated Stop current setpoint requires adjustment as it is set too high Adjust the stop current setpoint to a lower value If using the Set functionality during commissioning then adjust the Current Window to a lower value T...

Страница 8: ...ides 24VDC drive for CT Operating Temp 0 55 degrees Celsius Run Relay Contact Rating 5 A 48 VAC Resistive 1 5 A 48 VAC Pilot duty AC12 Alarm Contact Rating 5 A 48 VAC Resistive 1 5 A 48 VAC Pilot duty AC12 Dimensions W 106 5mm x H 90 50 mm x D 59mm Material PC ABS Mounting 35mm Din rail mounted Weight 300 g Certification EN 61000 6 3 2007 A1 AC FCC Part 15B 90 5mm ...

Страница 9: ...9 9 SC10 Connections See section 12 Reference for terminal identification Figure 1 SC10 Front Panel Figure 2 Connections ...

Страница 10: ...el PanelStart Remote Start Start Inputs Stop Inputs 5 Overload Reset Remote Set Point Up Remote Set Point Down Remote Threshold Set DIN Common O L 2 Emergency Stop 2 3 4 5 6 7 8 9 10 11 K1 Pump Run DIN 1 DIN 2 DIN 3 DIN 4 DIN 5 4 20mA 4 20mA 1 6 12 13 14 15 16 17 18 19 20 21 24 VAC A 24 VAC N 22 23 24 25 26 27 28 29 31 32 33 34 35 36 37 38 Ref Line 8 Ref Line 7 Ref Line 23 OL Ref Line 11 24 VAC A ...

Страница 11: ...nts in a few different ways Rated Current FLC Amps CT Rating Amps SC10 Current Range At Rated Current SC10 will Display Range DIP Switches SW 1 SW 2 An Example Optimal setup for an 8kW Pump Based on 11 1 above Option 1 As above 8 6 20 100 off off 30 30 of the range really is a bit low It would be best to adjust the range to increase the measurement Option 2 Change the Range Setting on the SC10 8 6...

Страница 12: ... Run Relay 4 5 Alarm Relay 6 7 Pump Current CT 4 20mA 8 9 Digital Inputs DIN Common 10 DIN 1 Start High Float 11 DIN 2 Stop Low Float 12 DIN 3 Up Pushbutton 13 DIN 4 Down Pushbutton 14 DIN 5 Set Pushbutton 15 DIN 8 Remote Config Mode 18 No Connection 19 27 Do not use AIN Loop Power 28 Modbus RTU RS485 A 29 B 30 Earth 31 No Connection 32 36 LED Indicators Power On Power is Present Flash Unit starti...

Страница 13: ...ses will be ignored Addressing Modbus addresses are indexed from 1 in the following table The address in the Modbus packet is 1 less than that address There is inconsistency between Modbus implementations about whether the addresses start from 0 or 1 so if you are not reading the value that you expect then consider reading the previous or next address Register Address Coil Discrete Address Read On...

Страница 14: ...p Fails to Run Pump Run Relay Active but no current was detected 6 Unused 7 Unused 8 Unused 9 RO Pump Control State 0 Initial State 1 Pump Pausing waiting for Pause Timer to expire 2 Pump Running 3 Low Level active Pump Stopped 4 High Level active Pump Running 5 Pump is pausing to flush pump 6 Pump is starting Pump not yet running 10 RO Pump Current Percentage with 1 decimal place e g 125 12 5 11 ...

Страница 15: ...llowing conditions are met 1 Redistributions of source code must retain the above copyright notice this list of conditions and the following disclaimer 2 Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribution 3 The name of the author may not be used to e...

Страница 16: ...B Pty Ltd 4 Barkala St Wellington Point QLD Australia Tel 61 7 3822 1005 Fax 61 7 3822 1008 support 2ib com au www 2ib com au 2018 2IB Pty Ltd All Rights Reserved SC10 Installation and User Manual V20180709 ...

Отзывы: