2iB SC10 Скачать руководство пользователя страница 2

 


 

1.

 

Safety 

SAFETY WARNINGS: 

 

Always isolate the power supply before performing any installation work. 

 

Always isolate the power supply before attempting to trace a fault as the pump connected may start without 

warning. 

 

The installation shall be performed by an authorised electrician according to local safety regulations. 

 

The SC10 must only be used on pumping equipment that is capable of running dry for short durations. 

 

The  SC10  is  not  to  be  used  in  Hazardous  Areas  or  Locations  (such  as  areas  with  Explosive  or  Flammable  Gas  or  Dust 
Environments). 

 

There are no operator serviceable parts inside.  Modification may negatively impact safety and may void warranty. 

2.

 

Unpacking, Inspection and Recycling 

The delivery comprises of: 

 

1 x SC10 Pump Control Unit 

 

1 x SC10 Installation and Operations Manual.  (This document.) 

 

1 x SC10 Quick Reference Guide 

If any of these items are missing or damaged at the time of delivery, please contact 2iB Pty Ltd. Please retain the product packaging 
and return the product for inspection if damaged. 

A 4-20mA CT is required for snore control operation.  This can be purchased separately from 2IB. 

3.

 

Installation 

3.1

 

Important Installation Requirements 

 

To avoid damage:  If the Power Supply is to be earthed then terminal no. 2 (-) may be earthed, but not terminal no. 1 
(+). 

 

Check that the rated voltage of SC10 corresponds with the supply line voltage. The SC10 is mounted on a standard 35 
mm DIN rail. Ensure that you use the SC10 within its Technical Specifications – see section 8 Specifications. 

 

To ensure accuracy and reliability screened twisted-pair cable is to be used for connection of the Current Transducer for 
measuring the pump motor current. 

3.2

 

Remote Snoring Setup Controls for Operator Safety 

The Stop Current Setpoint can be set and adjusted using pushbuttons on the front of the pump starter / control panel.  This enables 
the pump setup, commissioning and setpoint adjustment to be performed without the electrical hazards entailed in opening the 
pump starter / control panel doors. 

As shown in section 9 SC10 Connections the pushbuttons can be connected to digital inputs on the SC10.  It is recommended to 
connect / provide pushbuttons for: 

 

Up (Setpoint Adjustment) 

 

Down (Setpoint Adjustment) 

 

Set (Set the Stop Current Setpoint) 

 

Start (Pump Start – needed for commissioning) 

If you wish to prevent unauthorised personnel making adjustments then you can install these pushbuttons behind a lockable door 
or cover. 

3.3

 

Front-Mounting of SC10 to View Operating Current and Access Pushbuttons 

In  addition  to  the  standard  mounting  of  the  SC10  on  a  DIN  Rail  inside  the  cabinet,  two  alternative  mounting  options  can  be 
considered: 

 

A window can be built into the starter cabinet door and the SC10 can be mounted forward of the back-plate / gear-tray 
(or on the rear of the door) so that the current display is visible from outside of the panel. 

 

The SC10 can be mounted so that the front of the SC10 protrudes through the door (similar to circuit breakers) thus 
providing access to the current display as well as the buttons.  Note that the SC10 is neither dust, nor water resistant so 
an  outer  door  or  cover  will  be  required.    (WARNING:  Please  take  into  account  local  and  site  electrical  safety 
requirements.) 

Содержание SC10

Страница 1: ...SC10 Single Pump Controller Installation and User Manual ...

Страница 2: ...ations To ensure accuracy and reliability screened twisted pair cable is to be used for connection of the Current Transducer for measuring the pump motor current 3 2 Remote Snoring Setup Controls for Operator Safety The Stop Current Setpoint can be set and adjusted using pushbuttons on the front of the pump starter control panel This enables the pump setup commissioning and setpoint adjustment to ...

Страница 3: ...elps clear the impellor and the suction strainer of debris reducing the chance of blockage and cavitation as well as increasing the flow rate and efficiency Start up of the SC10 The SC10 will normally start the pump 30 Seconds after start up The pump will run until a stop condition is reach snoring is detected or the stop low float is activated This pump start will not occur if the stop low float ...

Страница 4: ...CT In the circumstance that this isn t achievable there are four current range dip switch selections available 100 50 25 and 12 5 that increases the current percentage display providing full scale set point ranging setting i e if you have a 0 100 CT with a 50 Amp full load current the output is only 4mA to 12mA and the percentage of current displayed will only be 50 by switching dip switch 2 50 on...

Страница 5: ...6 7 8 9 on front of SC10 CT Fault diagnostic monitoring of CT Sump Low Sump High Failed to Run pump called to run no current detected 5 5 Stop Low Level Switch Invert If a low level switch is used then the switch contact status needs to be set to normally open or closed Ref DIP Switch 10 on front of SC10 Tip If both the High and Low Level Switches are the same and their contacts close when the flo...

Страница 6: ...int Adjustment An additional adjustment method is by using the up and down buttons independently By pushing the up or down button it will adjust the stop current threshold to the user s desired value as a percentage of CT current Note This settings is non volatile It is stored through power cycles of the SC10 6 Display and LED Indication 6 1 Current Display PA PAUSING Pump is Pausing CL CLEANING P...

Страница 7: ...nected to terminals 7 and 9 Ensure installed 4 20mA CT is correct range for installed load The pump stops although it is not snoring Ensure the inhibit low float input is not activated Stop current setpoint requires adjustment as it is set too high Adjust the stop current setpoint to a lower value If using the Set functionality during commissioning then adjust the Current Window to a lower value T...

Страница 8: ...ides 24VDC drive for CT Operating Temp 0 55 degrees Celsius Run Relay Contact Rating 5 A 48 VAC Resistive 1 5 A 48 VAC Pilot duty AC12 Alarm Contact Rating 5 A 48 VAC Resistive 1 5 A 48 VAC Pilot duty AC12 Dimensions W 106 5mm x H 90 50 mm x D 59mm Material PC ABS Mounting 35mm Din rail mounted Weight 300 g Certification EN 61000 6 3 2007 A1 AC FCC Part 15B 90 5mm ...

Страница 9: ...9 9 SC10 Connections See section 12 Reference for terminal identification Figure 1 SC10 Front Panel Figure 2 Connections ...

Страница 10: ...el PanelStart Remote Start Start Inputs Stop Inputs 5 Overload Reset Remote Set Point Up Remote Set Point Down Remote Threshold Set DIN Common O L 2 Emergency Stop 2 3 4 5 6 7 8 9 10 11 K1 Pump Run DIN 1 DIN 2 DIN 3 DIN 4 DIN 5 4 20mA 4 20mA 1 6 12 13 14 15 16 17 18 19 20 21 24 VAC A 24 VAC N 22 23 24 25 26 27 28 29 31 32 33 34 35 36 37 38 Ref Line 8 Ref Line 7 Ref Line 23 OL Ref Line 11 24 VAC A ...

Страница 11: ...nts in a few different ways Rated Current FLC Amps CT Rating Amps SC10 Current Range At Rated Current SC10 will Display Range DIP Switches SW 1 SW 2 An Example Optimal setup for an 8kW Pump Based on 11 1 above Option 1 As above 8 6 20 100 off off 30 30 of the range really is a bit low It would be best to adjust the range to increase the measurement Option 2 Change the Range Setting on the SC10 8 6...

Страница 12: ... Run Relay 4 5 Alarm Relay 6 7 Pump Current CT 4 20mA 8 9 Digital Inputs DIN Common 10 DIN 1 Start High Float 11 DIN 2 Stop Low Float 12 DIN 3 Up Pushbutton 13 DIN 4 Down Pushbutton 14 DIN 5 Set Pushbutton 15 DIN 8 Remote Config Mode 18 No Connection 19 27 Do not use AIN Loop Power 28 Modbus RTU RS485 A 29 B 30 Earth 31 No Connection 32 36 LED Indicators Power On Power is Present Flash Unit starti...

Страница 13: ...ses will be ignored Addressing Modbus addresses are indexed from 1 in the following table The address in the Modbus packet is 1 less than that address There is inconsistency between Modbus implementations about whether the addresses start from 0 or 1 so if you are not reading the value that you expect then consider reading the previous or next address Register Address Coil Discrete Address Read On...

Страница 14: ...p Fails to Run Pump Run Relay Active but no current was detected 6 Unused 7 Unused 8 Unused 9 RO Pump Control State 0 Initial State 1 Pump Pausing waiting for Pause Timer to expire 2 Pump Running 3 Low Level active Pump Stopped 4 High Level active Pump Running 5 Pump is pausing to flush pump 6 Pump is starting Pump not yet running 10 RO Pump Current Percentage with 1 decimal place e g 125 12 5 11 ...

Страница 15: ...llowing conditions are met 1 Redistributions of source code must retain the above copyright notice this list of conditions and the following disclaimer 2 Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribution 3 The name of the author may not be used to e...

Страница 16: ...B Pty Ltd 4 Barkala St Wellington Point QLD Australia Tel 61 7 3822 1005 Fax 61 7 3822 1008 support 2ib com au www 2ib com au 2018 2IB Pty Ltd All Rights Reserved SC10 Installation and User Manual V20180709 ...

Отзывы: