TThe Xtralis Model VPS-VEA-115UL and VPS-VEA-230UL are power supplies that convert a 120VAC / 60Hz or  

230VAC / 50Hz respectively input to 24VDC nominal output (see specifications). They are intended for use in applications 

requiring UL Listing for Fire Protective Signaling. The units must be installed in accordance with the National Electric Code 

(NFPA70), the National Fire Code (NFPA72), and all other applicable local codes necessary for compliance with the local 

authority having jurisdiction. 
Space is provided in the VPS-VEA-115UL and VPS-VEA-230UL power supply cabinet for up to two 12V / 35AH or 

 

36AH batteries (configured for 24V). For a larger standby capacity in a single VESDA-E VEA installation or when more than 

one VESDA-E VEA detector is to be powered, use model VEA-BAT battery enclosure to house up to two 12V / 35AH or 

36AH batteries or use a UL1481, ULC-S527 or UL864 Listed enclosure

.

Operation Overview

The VPS-VEA-115UL and VPS-VEA-230UL is a power supply intended to power the VESDA-E VEA Detector Base 

Unit plus up to two (2) VESDA-E VEA Detector Stacks (see battery table). A power failure indication is provided via a 

dry relay contact (Form C) which transfers due to:
1.  AC input loss, 
2.  a low AC input voltage, 
3.  a loss of battery voltage, 
4.  a short circuit of the battery leads or 
5.  a short circuit of any of the DC power outputs. 
Refer to the wiring diagram located on the VEA unit for proper connections.

Note

: The screw terminals can accommodate up to two wires each, provided the wires sit under the terminal 

clamp on opposite sides of the screw.

Power Supply Capacity and Recommended Battery Requirements

Battery requirements and recommendations for typical power supply loads.

VESDA-E VEA Configuration

Power Supply/Alarm Load

24 hours of standby operation and 30 

minutes of alarm

Base Configuration 1xVEA-040-A00/A10 + 

 

1x VER-A40-040-STX

1A/1.8A

24V/35AH or 36AH

Add 1xVEA-020/040-STX + 1xVER-A40-040-

STX to the Base Configuration

1.9A/3.4A

24V/70AH or 72AH

Add 2xVEA-020/040-STX + 2xVER-A40-040-

STX to the Base Configuration

2.8A/5A

24V/105AH or 108AH

For use with the Listed VESDA-E VEA Detector Base Units and VESDA-E VEA Detector Stacks

Max. charging current 5.3A. Max. AMP/HOUR capacity battery for charging 108AH.

Input

VPS-VEA-115UL: 

120VAC / 2.0A/60Hz

VPS-VEA-230UL: 

230VAC / 1.0A/50Hz

In-rush:  

4.1A

Input Fuse

5A / 250V, Bussman P/N SR-5. To replace fuse (F1), disconnect power to unit, wait 5 seconds, remove fuse by lifting 

it. Insert new fuse into its socket.

Output

27VDC / 2.8A

Continuous, 27VDC / 5A alarm

Installation Instructions for 

 

VESDA Power Supply Model VPS-VEA-115UL and VPS-VEA-230UL