IP system - Accessories
Art. 2505
- Installation instructions
Art.2505
CloudBox
2 inputs - 2 outpus
IP relay module
Made in Italy
L1
P2
P3
P1
LAN
L2
RELAY 1
C1
NC1
NO1
RELAY 2
C2
NC2
NO2
+1
2V
GND
POWER
RS485
A B GND
INPUTS
IN1 IN2 GNDI
OPEN
RS485 BUS
TERMINATION
CLOSE
I
H
C
E
B
L
D
F
G
A
A
Fig. 1
Front
G
Fig. 2
Left side
DESCRIPTION
2 inputs - 2 outpus IP relay module.
LEGEND
A
Mobile connection terminals
B
Relays status LEDs
C
L1
LED
D
P1
button for manual activation of relay 1
E
L2
LED
F
P2
button for manual activation of relay 2
G
PoE Ethernet interface with power LED
H
P3
button bootloader mode
I
RS485 termination jumper
L
Inputs status LEDs
L1 AND L2 LEDS - STATUS INDICATIONS
L1
and
L2
,
C
and
E
) indicates the state of connections to the various services.
L1
Slow flashing
The gateway is absent
Fast flashing
Videx Cloud
service is absent
OFF
All services are properly
connected
L2
Slow flashing
The device is in “maintenace
mode” forced by Wizard
software
OFF
The device is in normal working
mode
L1
and
L2
Both fast flashing
The device is in “bootloader”
mode
RELAYS AND INPUTS STATUS LEDS
These LEDs (
B
and
L
) indicate
when a relay or a input is energized.
P1 AND P2 BUTTONS
MANUAL ACTIVATION OF RELAYS
P1
and
P2
buttons (
,
D
and
F
) are used for manually ac-
tivate a relay.
If the relay activates for a specific time it will remain actived for
the specified time.
If the relay operates in latch mode it will enable and disable
every time the button is pressed.
P3 BUTTON
BOOTLOADER MODE
P3
button (
,
H
) is used to start the “bootloader” mode:
1. Remove the mains;
2. Press and keep pressed
P3
button;
3. Restore the mains:
L1
and
L2
LED’s are flashing fast to indicate
that the device is in “bootloader” mode.
POE ETHERNET INTERFACE
The Ethernet connector (
G
) is a standard RJ45 with PoE function. A red LED is placed close to the connector and indicates
that the power supply is present, whether it is from PoE or via the connection terminals.
RS485 BUS TERMINATION SWITCH
The switch
I
sets the RS485 bus termination when connected to other RS485 devices.
By default the switch is set to the open position (lower position).
When more than one RS485 device is connected to the device in series on the RS485 bus
terminals then the switch can be set to the closed position (upper position) and only set
to the closed position on the end of line devices.
RS485 open
Move the switch
I
to the lower
position
RS485 closed
Move the switch
I
to the upper
position
Art. 2505
2 inputs - 2 outputs IP relay module
Rev.0.1