background image

UniPOS                                                                        Duct Smoke Detector 

УКВ

-02 

 

Passport                                                                                                            page 4 
Revision 01.10                                                                                                       of 4

 

 

MAINTENANCE 

        The maintenance must be performed by an authorized person and includes 
the service schedule of the device itself and the included in it fire detector and 
remote indicator in accordance with their instruction manuals. Additional cleaning 
the body of the duct detectoris is required. 
 

CONDITIONS OF STORAGE, OPERATION  AND TRANSPORT 

1. Storage 

 

o

 Indoor 

compartments 

o

 

Strorage Temperature Range   -  from minus 10 

о

С

 to plus 40 

о

С

 

o

 

Storage Relative Humidity        -  up to 65 %      

2.  Operation   

o

 

Enclosed spaces where there are no aggressive fumes  

o

 

Operating Temperature  Range  - from minus 10 

o

C to plus  55 

о

o

 

Operating Humidity  Range        - from 20% to 90% at 40 

о

3. Transportation 

Product has to be  transported in closed vehicles in  factory packaging.  

 

WARRANTY 

The warranty period is 18 months from the date of sale providing . 
The manufacturer guarantees the normal operation of the device providing that the 
installation requirements from this Instructional manualhave been observed.  
Manufacturing company bears no warranty liabilities for damages caused by 
mechanical damage,  improper use of the device or amendments and modifications 
made after production. The manufacturer carries a warranty liability only  for 
damages caused by company's negligence or  fault . 
 

 
 
 

UniPOS

47, “San Stefano” Str., 5800 Pleven, BULGARIA

phone +359 64 891111, +359 64 891 100, fax +359 64 891 110

e-mail: [email protected]

Mladost 1, bl.79B, entr.2, ap.17, 1784 Sofia, BULGARIA

phone/fax +359 2 9744469, +359 2 9743925

e-mail: [email protected]

www.unipos-bg.com

UniPOS                                                                        Duct Smoke Detector 

УКВ

-02 

 

Passport                                                                                                            page 1 
Revision 01.10                                                                                                       of 4

 

DUCT SMOKE DETECTOR 

TYPE YKB-02

К

 (YKB-02A) 

Instruction Manual 01.10 

 

 

GENERAL DESCRIPTION 

 Duct smoke detector YKB-02  is designed to detect the presence of smoke in  
airstream of ductwork sections or ventilating compartments by the smoke detector 
mounted in it. 
Depending on the type of the  fire detector mounted , the 
duct smoke detector is produced in two variants - 
for Conventional Fire Alarm Systems (YKB-02K)  and for 
Addressable Fire Alarm Systems (YKB-02A). 
 In the device is mounted an optical-smoke fire detector type: 
              -FD8030 for Conventional Systems 
                                     or 
             -FD7130  for Addressable Systems 
 In order to  conrol the condition of the integrated  fire 
detector,  on the housing  of the duct  smoke detector is 
mounted an outboard  LED Remote Indicator RI31. 

 

Fig.1 

 

Product design is based on the laws of Aerodynamics. 
Part of the air flow runs through the opening holes ( pos.7, Fig 4 ) of the inlet tube    
( pos.8, Fig.4 ) and passes through the duct  smoke detector as reduces its speed 
and goes out through the outlet tube ( pos.9, Fig 4 ).The mounted mechanichal 
filters  stop the large particles from the airflow and thus they protect the sensitive 
element of the fire detector from dust contamination. 
 In case of smoke in the main air conduit, part of this smoke goes through the duct 
smoke detector and activates the fire detector. The latter sends signal to the Fire 
Control Panel and the outboard Remote indicator. 

TECHNICAL DATA 

 

Speed of the airflow into the air conduit  

                          - 0,5 ÷ 20 m/s 

Existence of a mechanical filter of the input and the output      - Yes 
Base type of fire mounted  detector                                           - DB8000D (DB7100) 
Type of the Fire Detector                                                           - FD8030 (FD7130) 
Type of  the mounted Remote Indicator                                    - Rl31 
Option for installation of different type smoke detectors            - Yes 
Dimensions (without  the inlet tube , the outlet tube and the 
nozzles)                                           

(200x120x114)mm 

Inlet  tube dimensions                                                                ø22 

х

 200 mm 

Outlet tube dimensions                                                              ø22 

х

 70 mm 

Weight 1,3

 

kg 

 

LABOUR PROTECTION REQUIREMENTS 

The personnel authorized to conduct the mountage and the technical service should 
be aware of the construction  of the device  its operational mode  and the common 
requirements of  workplace security. 

 

Reviews: