background image

www.tridonic.com

1

Subject to change without notice. Information provided without guarantee.

Data sheet 10/20-EM091-6

Emergency lighting units

EM converterLED

Product description

•  Emergency lighting LED Driver with DALI interface 

and automatic test function

•  For self-contained emergency lighting
•  For LED modules with a forward voltage of 10 – 54 V
•  SELV for output voltage < 60 V DC
•  Low profile casing (21 x 30 mm cross-section)
•  For luminaire installation
•  Nominal life-time up to 100,000 h
•  5-year guarantee

Properties

•  Non maintained operation
•  DALI interface for controlled testing and monitoring
•  1, 2 or 3 h rated duration
•  Operating time selectable with plug (duration link)
•  Compatible with most constant current LED Drivers (see 5.4)
•  3-pole technology: 2-pole LED module changeover 

and delayed power switching for the LED Driver

•  Automatic shutdown of output if LED load is out of range
•  Constant power output
•  Addressing function, patented („EZ easy addressing“)
•  Two-colour status display LED
•  Electronic charge system
•  Deep discharge protection
•  Short-circuit-proof battery connection
•  Polarity reversal protection for battery provided by 3-pole 

connector

•  Automatic detection of the connected battery technology  

(NiMH or LiFePO

4

 batteries)

Tests:

•  Status of the battery
•  Status of the LED
•  Function test
•  Duration test

Batteries

•  High-temperature cells
•  NiMH or LiFePO4 batteries
•  LA or 18650 cells

•  4-year design life for NiMH batteries

•  1-year guarantee for NiMH batteries

•  4 – 8 years design life for LiFePO

4

 batteries

•  3-year guarantee for LiFePO

4

 batteries

•  For battery compatibility refer to chapter „Battery selection“

È

Standards

, page 5

Wiring diagrams and installation examples

, page 6

EM converterLED PRO MH/LiFePO4 50 V

PRO series

 

Содержание EM converterLED ST 202 MH/LiFePO4 50V

Страница 1: ...D module changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Addressing function patented EZ easy addressing Two colour status display LED Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by 3 pole connector Automatic detect...

Страница 2: ...0 pc s 1 600 pc s 0 07 kg Specific technical data Type Battery technology Rated duration Typ λ at 230 V 50 Hz Typ output power P emergency Mains current in charging operation Rated power in charging operation Initial charge Fast recharge Trickle charge2 Initial charge Fast recharge Trickle charge2 EM converterLED PRO 202 MH LiFePO4 50V NiMH 1 h 0 65C 1 5 W 15 mA 16 mA 15 11 mA 1 9 W 2 2 W 1 9 1 4 ...

Страница 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Страница 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Страница 5: ...ssociated battery In normal mains mode all LED modules are operated by the mains LED Driver Meaning of marking Double or reinforced insulation for built in electronic LED Drivers The control gear relies upon the luminaire enclosure for protection against accidental contact with live parts 2 Thermal details and life time 2 1 Life time Average life time 50 000 hours under rated conditions with a fai...

Страница 6: ...ED PRO with a standard LED LED Driver and one LED module for mains and emergency operation EM converterLED PRO with a standard LED LED Driver and series operation of LED modules Neutral P O Lout Lin N Dali Dali L L N EM ConverterLED PRO Neutral Dali Dali Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear Battery Battery LED Module Emerge...

Страница 7: ...itched Line Switched Line out Switched Line in One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4...

Страница 8: ...nducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads to the LED module must not be exceeded...

Страница 9: ...M converterLED PRO MH LiFePO4 50V 90 130 130 130 180 260 260 260 10 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver i...

Страница 10: ...tery discharge current tolerance EM converterLED PRO 203 MH LiFePO4 50V Article number 89800628 NiMH battery 3 6 V battery voltage 890 960 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 770 830 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 204 MH LiFePO4 50V Article number 89800629 NiMH battery 4 8 V battery vol...

Страница 11: ...mand from the control system If the DALI bus is disconnected the EM converterLED PRO does not revert to self testing mode Note If the battery is connected the DALI communication is only possible after power reset Addressing The EM converterLED PRO includes the EZ easy addressing system which allows addressing and identification by using the bi colour LED Binary address codes given by the LED can b...

Страница 12: ...nitiate a 5 seconds function test press 200 ms T 1 s Execute function test as long as switch pressed press 1 s Reset selftest timer adjust local timing press 10 s Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off the LED output If the Inhibit Mode ...

Страница 13: ...B CON 28002319 side by side 4 x 1 Accu LiFePO44B CON 28002323 side by side 5 x 1 Accu LiFePO45B CON 28002326 EM converterLED PRO 1 2 3 h NiMH Type EM converterLED PRO 202 MH LiFePO4 50V EM converterLED PRO 203 MH LiFePO4 50V EM converterLED PRO 204 MH LiFePO4 50V Article no 89800627 89800628 89800629 Duration 1 h 2 3 h 1 h 2 3 h 1 h 2 3 h Battery charge time Initial charge 20 h Fast recharge 10 h ...

Страница 14: ...n life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number discharge cycles 50 cycles total Max storage time 12 months at 5 C to 25 C Only use Tridonic batteries Comply with UN 38 3 and IEC 62133 safety testing protected against over charge over discharge charging at excessive temperatures short circuit and over c...

Страница 15: ...arameters provide information about the mains battery LED output and emergency operation The BlackBox can be read out with the masterCONFIGURATOR and deviceANALYSER In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no b...

Отзывы: