background image

©Copyright Task Force Tips LLC 2015-2020

1

LIZ-030 October 29, 2020 Rev13

TASK FORCE TIPS LLC

MADE IN USA · tft.com 

3701 Innovation Way, Valparaiso, IN 46383-9327 USA

800-348-2686 · 219-462-6161 · Fax 219-464-7155

INSTRUCTIONS FOR INSTALLATION, OPERATION, AND MAINTENANCE

Master Foam Fixed GPM

Self-Educting Foam Nozzle Series

WARNING

Understand  manual  before  use.  Operation  of  this  device  without  understanding  the  manual  and

receiving proper training is a misuse of this equipment. Obtain safety information at tft.com/serial-

number. 
This equipment is intended for use by trained and qualified emergency services personnel for

firefighting. All personnel using this equipment shall have completed a course of education

approved by the Authority Having Jurisdiction (AHJ).
This instruction manual is intended to familiarize firefighters and maintenance personnel with the

operation, servicing, and safety procedures associated with this product. This manual should be

kept available to all operating and maintenance personnel. 

Fixed Flow Rate:

250, 350, 500, or 750 gpm

950, 1325, 1900, or 2900 l/min

Nominal Pressure:

100 psi (7bar)

Nominal Foam Percentages:

0.5%, 1%, 3%, or 6%

Fixed Flow Rate:

1000 or 1250 gpm

3800 or 4800 l/min

Nominal Pressure:

100 psi (7bar)

Nominal Foam Percentages:

1% or 3%

Fixed Flow Rate:

1500 or 2000 gpm

5700 or 7600 l/min

Nominal Pressure:

100 psi (7bar)

Nominal Foam Percentages:

1% or 3%

RC Fixed Flow Rate:

1000 or 1250 gpm

3800 or 4800 l/min

1500 or 2000 gpm

5700 or 7600 l/min

Nominal Pressure:

100 psi (7bar)

Nominal Foam Percentages:

1% or 3%

Summary of Contents for Master Foam Series

Page 1: ...t shall have completed a course of education approved by the Authority Having Jurisdiction AHJ This instruction manual is intended to familiarize firefighters and maintenance personnel with the operat...

Page 2: ...ment you may be called upon to use 3 It is your responsibility to know that you have been properly trained in Fire ghting and or Emergency Response and in the use precautions and care of any equipment...

Page 3: ...vation Refer to LIM 030 and LIM 035 for effective stream trajectories of Task Force Tips Masterstream nozzles at 30 elevation This graph cannot be used to estimate maximum reach for elevation angles b...

Page 4: ...OUPLINGS 3 5 ELECTRIC INSTALLATION 4 0 OPERATION 4 1 PATTERN CONTROL 4 2 FLUSHING DEBRIS 5 0 USE WITH FOAM 5 1 FOAM ASPIRATING ATTACHMENTS 5 2 CLEANING AFTER USE 5 3 SETTING FOAM PERCENTAGE 5 3 3 ORIF...

Page 5: ...capable of supporting the nozzle reaction force FLOW REACTION FORCE gpm l min Pounds Kilograms 250 950 132 60 350 1325 185 84 500 1900 265 120 750 2900 397 180 1000 3800 529 240 1250 4800 661 301 1500...

Page 6: ...ble 3 1 Figure 3 1A RANGE SMALL MEDIUM LARGE INLET COUPLING 2 5 65mm NH NPSH or BSP 3 5 89mm NH NPSH or BSP 3 5 89mm NH 4 0 100mm BSP RATED PRESSURE 100 psi 7bar 100 psi 7bar 100 psi 7bar FLOW RATING...

Page 7: ...s LLC 2015 2020 7 LIZ 030 October 29 2020 Rev13 Figure 3 1B Figure 3 1C Stream Shaper Baffle Foam Inlet Coupling Serial Number Folding Handles Orifice Plate Override Knob Masterfoam 1000 1250 1500 200...

Page 8: ...reach Range SMALL MEDIUM LARGE Nominal Flow 250 gpm 950 l min 350 gpm 1325 l min 500 gpm 1900 l min 750 gpm 2900 l min 1000 gpm 3800 l min 1250 gpm 4800 l min 1500 gpm 5700 l min 2000 gpm 7600 l min...

Page 9: ...e air Generally the straight stream reach with foam is approximately 10 less than with water only Actual results will vary based on brand of foam hardness of water temperature etc For specific informa...

Page 10: ...mply push it into the bore at the foam inlet on the nozzle The orifice plate has an O ring to hold it in place To remove the orifice plate hook a small object such as a screwdriver or Allen wrench int...

Page 11: ...BRATION 0 5 and 1 Class A foam of 20 centipoise viscosity 3 3M ATC 3 AR AFFF product code ATC 603 6 3M ATC AFFF product code FC 600F PERCENT 1000 and 1250 gpm Nozzles FOAM USED FOR CALIBRATION 1 Willi...

Page 12: ...20 40 60 80 100 120 140 160 180 200 220 A B A TFT MASTER FOAM B TFT MASTER FOAM WITH FOAMJET LX 3 or 1 FOAM AT 350 GPM AND 100 PSI Ver cal Distance Feet 0 10 20 30 40 50 60 70 Horizontal Distance Met...

Page 13: ...0 140 160 180 200 220 240 260 280 300 0 10 20 30 40 50 60 Horizontal Distance Meter Ver cal Distance Meter Horizontal Distance Feet Ver cal Distance Feet 3 or 1 Foam at 1000 GPM 100 PSI 0 10 20 30 40...

Page 14: ...ge of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The orig...

Page 15: ...mum of annually Units failing any part of this test must be removed from service repaired and retested upon completion of the repair 8 3 REPAIR Factory service is available with repair time seldom exc...

Page 16: ...low is adequate as indicated by pump pressure and nozzle reaction BEFORE BEING PLACED BACK IN SERVICE nozzles must be inspected to this checklist 1 All controls and adjustments are operational 2 There...

Reviews: