Installation Instructions

Document No. A6V11200850

May 1, 2018

OpenAir™ Electronic Fusible Link
Used with Siemens Fire and Smoke
Damper Actuators

Item number A6V11200850, Rev. DA

Page 1 of 4

Product Description

The Electronic Fusible Link (EFL) is a heat responsive
device used with the Siemens OpenAir™ UL listed fire
and smoke control damper actuator.

Upon approaching the temperature rating of the EFL
model ordered and installed, the EFL cuts power to the
electronic damper actuator and the actuator’s spring
return mechanism closes the damper.

NOTE:

The EFL must be factory-installed. The UL
rating carried by the specific damper and
actuator is assigned as an assembly and
cannot be added in the field.

Replacement EFLs may be field-installed with local
authority approval.

Contents

  Electronic Fusible Link

  Two 1.5-inch (38.1 mm) No. 8 pan head self-drilling

screws

Product Numbers

ASK791.165

165°F (74°C)

ASK791.212

212°F (100°C)

ASK791.250

250°F (121°C)

ASK791.350

350°F (177°C)

NOTE:

The EFL is compatible only with OpenAir

GJD,

GRD, GKD, or GVD

fire and smoke damper

actuators.

Warning/Caution Notations

WARNING:

Personal injury or loss of life may
occur if you do not follow the
procedures as specified.

CAUTION:

Equipment damage may occur if
you do not follow the procedures
as specified.

Required Tools

 

1-3/8-inch (35 mm) drill or hole punch

 

No. 2 Phillips bit

Expected Installation Time

15 minutes

Prerequisites

Appropriate OpenAir GJD, GRD, GKD, or GVD series
damper actuator.

Operation

When the EFL detects that its temperature rating is
being approached, the power to the electronic damper
actuator is shut off and the spring mechanism closes the
damper.

NOTE:

  Depending on the application environment, the

EFL may trip before the listed temperature
rating.

The manual override reset button (see Figure 1) on the
EFL can be pressed when the temperature has cooled
below the EFL setpoint. The EFL device will again be
operational.

Figure 1.  Parts Description.

Summary of Contents for OpenAir ASK791.165

Page 1: ...t Numbers ASK791 165 165 F 74 C ASK791 212 212 F 100 C ASK791 250 250 F 121 C ASK791 350 350 F 177 C NOTE The EFL is compatible only with OpenAir GJD GRD GKD or GVD fire and smoke damper actuators Warning Caution Notations WARNING Personal injury or loss of life may occur if you do not follow the procedures as specified CAUTION Equipment damage may occur if you do not follow the procedures as spec...

Page 2: ...extremely hot to the touch Installation Figure 2 The EFL and OpenAir Fire and Smoke Damper Actuator WARNING The internal external mounting orientation or position in the duct will affect the time and or temperature the EFL requires to switch NOTE Notice the position of the top clip before attempting to couple the actuator with the EFL sensor Figure 3 Proper Clip Positioning Internal Mounting For i...

Page 3: ...ecified mounting screw torque may damage the housings External Mounting For external mounting make a 1 3 8 inch 35 mm diameter hole in the duct wall or damper sleeve The sensor will protrude into the duct or damper for proper temperature sensing Figure 5 Providing Proper Sensor Temperature Detection Access CAUTION Exceeding the specified mounting screw torque may damage the housings ...

Page 4: ...chweiz AG Other product or company names mentioned herein may be the trademarks of their respective owners 2018 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No A6V11200...

Reviews: