background image

Manual LMSmodular Hardware

Section 2

Cerberus

®

 LMSmodular

Cerban Splitter CBS-3

Technical Manual

Siemens Building Technologies

Cerberus Division

Cerberus
Security
for People
and Assets

Summary of Contents for Cerban Splitter CBS-3

Page 1: ...Manual LMSmodular Hardware Section 2 Cerberus LMSmodular Cerban Splitter CBS 3 Technical Manual Siemens Building Technologies Cerberus Division Cerberus Security for People and Assets ...

Page 2: ...ument and in the subject thereof By accep tance of the document the recipient acknowledges these rights and un dertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior ex press written authorization nor to use it for any purpose other than for which it was delivered to him ...

Page 3: ... 4 3 CPU board configuration 5 3 1 Introduction 5 3 2 Configuration by dip switches 5 3 2 1 Subsystem setting 5 3 2 2 Cerban vitality telegram 6 3 3 Configuration by Flash EPROM 6 4 Hardware installation 7 4 1 Inside the CS4 7 4 2 Inside the CS11 8 4 3 Power supply 8 5 Cables and connections 9 5 1 Connection to GW 20 9 5 2 Connection to GW 21 9 5 3 Connection to an user provided device 10 6 Baud r...

Page 4: ......

Page 5: ...e The manual is divided into 5 chapters and 1 annex a Table of Contents and an Index allow easy referencing to the arguments Chapter 1 is an introduction to the manual Chapter 2 describes the product Chapter 3 shows how to install the CBS 3 to supply and connect it Chapter 4 shows how to configure the CBS 3 Chapter 5 describes how you can identify problems that can possibly arise Annex A lists the...

Page 6: ...8 7 6 4 3 2 1 5 2 8 7 6 4 3 5 NC Fig 1 The CPU board On this board there are the CPU the RAM and Flash EPROM the Real Time Clock RTC two UART chips that manage the four GW 21 serial lines the Neuron Chip that lets the GW 21 to communicate with the LonWork network four dip switch blocks S1 S4 used to configure the GW 21 as described later one reset push button used to reset the board one service pu...

Page 7: ...ll the UARTs from 1 to 4 are accessible through screw connectors located on the right side of the connection board Only the TX RX and GND signals are available In the lower right corner of the connection board there is the power supply block with two pins marked and You must connect here the voltage source 10 to 30 V d c GND RX4 TX4 GND RX3 TX3 GND RX2 TX2 GND RX1 TX1 Vdc Fig 2 The connection boar...

Page 8: ...otocol to two independent serial lines The two lines can be connected to any device able to understand the Cerban protocol The following table sums up the UARTs connections to other network elements USART NUMBER DEVICE PROTOCOL 1 CS11 CS4 CERBAN 2 GATEWAY or USER DEVICE CERBAN 3 GATEWAY or USER DEVICE CERBAN 4 NONE NONE Any user provided device Cerban line Cerban line Cerban line GW 0x GW 0x CSxx ...

Page 9: ... intrusion detection control unit manufactured by Cerberus CC60 gas detection unit manufactured by Cerberus What to configure The switch S1 1 is used to discriminate between Flash EPROM configuration or dip switches configuration If it is set OFF the dip switches are irrelevant for configuration purposes Otherwise they set the CBS 3 parameters as described in the following sec tion S1 1 Function O...

Page 10: ...nal function to filter the Cerban vitality telegram the dip switch is valid for all of the Cerban line which are defined on the gateway The only reason to filter the vitality telegram is to limit the traffic of messages to the LMS station s Note that if the vitality check is e nabled at LMS level then this dip switch must be set to ON else LMS will generate false fault events S1 2 Function OFF Vit...

Page 11: ...ware installation 4 1 Inside the CS4 In the CS4 intrusion detection control unit the gateway can be mounted on some of the standard housings You need 2 plastic spacers 2 self tapping screws 4 metal spacers 2 short screws 2 long screws 2 board supports Fig 4 Inside the CS4 ...

Page 12: ... be mounted on some of the standard housings You need 4 plastic spacers 4 self tapping screws 2 board supports Fig 5 Inside the CS11 4 3 Power supply The gateway GW 21 is powered using the connector located on the connection board Please refer to Fig 2 Please pay attention to pin polarities The supply voltage must be in the range 10 to 30 V d c ...

Page 13: ...8 8 10 9 7 5 6 11 1 3 2 4 UART2 UART3 UART4 UART1 7 6 5 4 2 1 8 9 3 Net M Pad in GW 20 Male connector Fig 6 GW 21 GW 20 connection screw terminal block 5 2 Connection to GW 21 The figure below shows how to connect the Cerban Splitter CBS 3 to the GW 21 asyn chronous port CBS 3 15 17 16 14 12 13 18 8 10 9 7 5 6 11 1 3 2 4 GND Rx3 Tx4 GND Tx3 Rx2 GND Rx4 Tx1 GND Rx1 Tx2 UART2 UART3 UART4 UART1 GND R...

Page 14: ...T1 Fig 8 Connection to an user provided device 6 Baud rates The only protocol available with CBS 3 is Cerban that requires a baud rate setting of 300 bauds The following baud rates apply to the subsystems connected either to the CPU or the expansion board BAUD RATE UART Spare 9600 4800 2400 1200 600 300 150 1 S1 7 ON OFF ON OFF ON OFF ON OFF S1 8 ON ON OFF OFF ON ON OFF OFF S2 1 ON ON ON ON OFF OF...

Page 15: ...m type UART 4 S3 7 subsystem type UART 4 S3 8 subsystem type UART 4 S4 2 baud rate UART 4 S4 3 baud rate UART 4 S4 4 baud rate UART 4 BAUD RATE UART Spare 9600 4800 2400 1200 600 300 150 1 S1 7 ON OFF ON OFF ON OFF ON OFF S1 8 ON ON OFF OFF ON ON OFF OFF S1 9 ON ON ON ON OFF OFF OFF OFF 2 S2 5 ON OFF ON OFF ON OFF ON OFF S2 6 ON ON OFF OFF ON ON OFF OFF S2 7 ON ON ON ON OFF OFF OFF OFF 3 S3 3 ON O...

Page 16: ......

Page 17: ...dex A Asynchronous board 1 C CC60 6 Cerban vitality 6 CMS 1 Connection board 3 CPU board 2 5 CS11 1 4 5 6 8 CS4 6 7 8 CZ10 1 6 8 CZ12 1 6 D Dip switch 6 E EPROM 5 F Flash EPROM 5 6 G GW 00 1 L LMS 1 M Message traffic 6 P Power supply 8 S Subsystem setting 5 T Traffic 6 ...

Page 18: ...rus Division CH 8708 Männedorf Alte Landstrasse 411 Tel 41 1 922 61 11 Fax 41 1 922 64 50 www cerberus ch Doc no e1148c Siemens Building Technologies Cerberus Division Replaces e1148b Edition 06 2000 Cerberus Security for People and Assets ...

Reviews: