background image

CAPVEL-ICT

Capacitance Level Transmitter

INSTRUCTION MANUAL

Version 2.0

Summary of Contents for CAPVEL-ICT

Page 1: ...CAPVEL ICT Capacitance Level Transmitter INSTRUCTION MANUAL Version 2 0 ...

Page 2: ... 6 10 Measurement Specification 6 11 Installation Guidelines 7 11 1 Tank Mounting Installation 7 12 Electrical Connections 7 13 Calibration 7 14 Error Display and Remedy 10 15 Menu and Description 11 16 RS 485 Serial Commands for Communication with Capvel 12 17 Settings 13 18 Maintenance 13 19 Support Training 13 20 Customer Support 13 List of Figures 1 Capvel 5 2 Connection Diagram 5 3 Calibratio...

Page 3: ...chanical Specifications 6 2 Electrical Specifcations 6 3 Measurement Specifications 6 4 Error Display and Remedy 10 5 Menu 11 6 Menu 12 7 Percentage Level Information 12 8 Configuring and Asking Sensor ID on Network 13 Sapcon Instruments Pvt Ltd R 3 ...

Page 4: ...l instrument housing in terms of dimensions color and design Please refer to GA drawings for dimensional details Values of performance described in this manual were obtained under ideal testing conditions Hence they may differ under industrial environment and settings General Instructions Instrument shouldn t block the material filling inlet Secure the cover of housing tightly Tighten the cable gl...

Page 5: ...in process of converting the level to 4 20 mA signal Two DIP switches are provided to calibrate the 4 mA and 20 mA points The calibration is easy and a complete procedure is given in Calibration page The two wires connected at the back are pre connected sensor wires and should not be disturbed Also while calibration try to keep hands away from the wires of terminal 6 and 7 Now referring to the Con...

Page 6: ...SS Overall Dimensions Please refer enclosed probe drawing Table 1 Mechanical Specifications 9 Electrical Specification For Electrical Specification please refer Table 2 PARAMETER VALUE Mains Capvel BT 9V to 55V DC Capvel ICT 9V to 30V DC Power Consumption Capvel BT Max 0 5 watt 12 V Capvel ICT Max 1 watt 12 V Table 2 Electrical Specifcations 10 Measurement Specification For Measurement Specificati...

Page 7: ...tion all electrical connections must be powered OFF and the fuel tank must be empty 11 1 Tank Mounting Installation Note It is recommanded that the tank must be empty while following steps in this section 12 Electrical Connections 13 Calibration Sapcon Instruments Pvt Ltd R 7 ...

Page 8: ...is in RUN MODE again We can Calibrate 4mA and 20mA in any order according to our choice The order of empty fill or fill empty is immaterial Calibrating HIGH L evel Upper Calibration has done DOWN 2 Press and Hold This Key UP For 3 Seconds Wait for around 5 Seconds 3 Wait for around 5 Seconds Press and Hold This Key For 3 Seconds Fill the tank at High Level High SCAL Low SCAL Figure 3 Calibration S...

Page 9: ...if measured mA is between 13 25mA 15 5mA 64L 8L 2 25mA x measured mA 4 if measured mA is between 15 5mA 17 75mA 72L 6L 2 25mA x measured mA 4 if measured mA is between 17 75mA 20 0mA 42L 12L 2 25mA x measured mA 4 if measured mA is between Volume at various strapping level can be found by taking notes of amount of fluid needed to raise the level or it can be calculated mathematically from tank dim...

Page 10: ...ase recalibrate correctly 4 PrHI Over Capacitance Tank and probe dimen sions are not matched 5 PrLO Under Capacitance Tank and probe dimen sions are not matched 6 RFOP Internal reference got open circuited Internal fault in sensor 7 RFSC Internal reference got short circuited Internal fault in sensor 8 RFHI Internal reference satu rated Internal fault in sensor 9 RFLO Internal reference negligi bl...

Page 11: ...Higher Set point Only in Pump Controlling SPH must be higher than SPL rLdr Relay Drive r SPL L 000 L 099 Lower Set point Only in Pump Controlling SPH must be higher than SPL rLdr Relay Drive r Cd C 000 C 100 Cover Delay in Seconds rLdr Relay Drive r Ud U 000 U 100 Uncover Delay in Sec onds SCAL Scal Factor SC H H 020 H 100 Higher SCALE LEVEL SCAL HIGH must be 20 or more Higher than SCAL LOW SCAL S...

Page 12: ...ion othr o PRF PR 1 PRF 9 Profile Only for optimization InFo i SEr 12345678 Serial No Factory Sated and Read Only InFo i dAt 12345678 Mfd Date in DD MM YY format Factory Sated and Read Only Table 6 Menu 16 RS 485 Serial Commands for Communication with Capvel For RS 485 Serial Commands please refer Table 7 COMMAND DESCRIP TION COMMAND TO BE SEND TO SENSOR EXPECTED RESPONSE FROM INSTRUMENT EXPLAINAT...

Page 13: ...ructions given in this manual To further ease the process of installation and use we have developed special demo videos which are hosted on YouTube Sapcon s YouTube channel SAPCON INSTRUMENTS lists all these videos https goo gl dnxfcz Should you require further information regarding installation use or working of the instrument please don t hesitate to contact us Kindly provide the following infor...

Reviews: