CW-7500

INDUSTRIAL CHILLER

USER MANUAL

Summary of Contents for CW-7500

Page 1: ...CW 7500 INDUSTRIAL CHILLER USER MANUAL ...

Page 2: ...tions 3 2 Contour and parts introduction 4 3 Installation 5 4 Unit introduction and parameters adjustment 6 5 Alarm and communication output 12 6 MODBUS RS 485 communication function 13 7 Specifications 17 8 Simple troubleshooting 18 ...

Page 3: ...el of 50Hz or 60Hz according to actual circumstance 4 To protect the pump it s strictly forbidden to run the chiller without water in the storage water tank The new machine is packed after draining whole water in the tank so please make sure the tank has water inside before machine starting otherwise it s easily to have the pump damaged When the water level is below the green NORMAL range of the w...

Page 4: ...ction AIR OUTLET AIR INLET WATER SUPPLY INLET WATER INLET WATER OUTLET WATER LEVEL GAUGE WATER DRAIN WASTE WATER DRAIN OVERFALL GAP TEMPERATURE CONTROLLER WATER PRESSURE LOW PRESSURE HIGH PRESSURE POWER ALARM AND COMMUNICATION OUTPUT POWER SWITCH ...

Page 5: ...ter temperature is under the set value it is normal that fans and other components of the machine do not work The temperature controller will automatically control the working conditions of the compressor magnetic valve fans and other parts based on the set controlling parameters 5 As it takes a longer time to start over the compressor and other components according to different conditions the tim...

Page 6: ...ower button Set button Set Quick Set button Quick Set and Quit button Quit Turn off the chiller by pressing the Power button for 3 sec while other operations can be completed by short press 2 User parameters quick adjusting under normal operation condition press Quick Set button to set the user menu When it displays the set item press Quick Set to enter into parameter adjustment interface Press or...

Page 7: ...old Set button and Power button for 10 sec to have the password input interface popped up then input password 615 to enter into administrator setting parameters restoration function and it will display RECOVERY SUCCESS and turn to operation condition after 2 sec If the password is incorrect it will quit the password input interface and turn to operation condition 6 Unit operation condition query t...

Page 8: ...sor failure alarm delay 0 180 10 Second 0x040b 12 F12 Water flow detection delay of machine startup 0 180 5 Second 0x040c 13 F13 Flow alarm delay 0 180 2 Second 0x040d 14 F14 Heating hysteresis 0 10 0 8 0 1 resolution ratio 0x040e 15 F15 Water pump stop delay 0 180 5 Second 0x040f 16 F16 Startup delay 0 180 30 Second 0x0410 17 F17 Compressor activate protection 0 180 30 Second 0x0411 18 F18 Turn o...

Page 9: ...ooling hysteresis 0 5 2 0 1 0 0 8 4 F4 Way of control 1 0 0 0 5 F5 The highest set temp 31 30 30 35 6 F6 The lowest set temp 25 5 5 20 7 F7 Ultra high room temp alarm 45 45 45 45 8 F8 Ultra high water temp alarm 10 5 4 10 9 F9 Ultra low water temp alarm 10 10 14 15 10 F10 Temp alarm delay 5 5 5 5 11 F11 Sensor failure alarm delay 10 10 10 10 12 F12 Water flow detection delay of machine startup 5 5...

Page 10: ...ature alarm will be on when water temperature is 10 lower than normal temperature Case 3 cooling water temperature is controlled by constant mode Requiring water temperature is constant in 25 and the fluctuate does not exceed 1 The ultrahigh water temperature alarm will be on when water temperature is higher than 30 and the ultralow water temperature alarmwill be on when water temperature is lower...

Page 11: ...eater shut down Manual clearing E07 water pump overload alarm E07 shown with alarm sound The water pump compressor condenser fans and heater shut down Manual clearing E08 Refrigeration system high pressure alarm E08 shown with alarm sound The compressor and condenser fans shut down Manual clearing E09 Refrigeration system low pressure alarm E09 shown with alarm sound The compressor and condenser f...

Page 12: ...in buzzer of temp controller OUT H1 H2 OUT H1 H3 ILUS Working normally No Sound Disconnection Breakover E00 E01 E05 E06 E07 E08 E09 E11 Sounds Breakover Disconnection E02 E10 E13 E14 Sounds Disconnection Breakover E03 E04 Sounds Breakover Disconnection Optional E12 Sounds Breakover Disconnection Activate after output terminal delaying Note The flow alarm is connected to the normally open relay and...

Page 13: ...g address is 1 requests 108 110 command of slave read register and send 01 03 00 6B 00 03 XX YY thereinto 01 as slave address 03 as function code 00 6B as initial address 00 03 as register number and XX YY as the result of CRC verification Slave response 01 03 06 02 2B 00 00 00 64 XX YY thereinto 01 as slave address 03 as function code 06 as number of bytes 02 2B 00 00 00 64 corresponding to the v...

Page 14: ...tion Range Default Unit Data resolution Symbol 0x0100 Room temp sensor temperature 25 100 0 1 bit yes 0x0101 Water temp sensor temperature Low temp 25 100 0 1 bit yes 0x0102 Water temp sensor temperature High temp 25 100 0 1 bit yes 0x0103 Compressor exhaust temperature 25 140 0 1 bit yes 0x0104 Flow of the first waterway 0 1 200 L Min 0 1 bit yes 0x0105 Flow of the second waterway 0 1 200 L Min 0...

Page 15: ...ankcase heating 0 Off 1 On Bit4 Low temp heating rod 0 Off 1 On Bit3 Low temp refrigerant solenoid valve 0 Off 1 On Bit2 Condensing fan 0 Off 1 On Bit1 Compressor relay 0 Off 1 On Bit0 LSb Low temp water pump 0 Off 1 On 0x0801 Digital input switch status MSByte Bit7 MSb Retain Bit6 Retain Bit5 Retain Bit4 Retain Bit3 Retain Bit2 Retain Bit1 Retain Bit0 LSb Retain LSByte Bit7 MSb Retain Bit6 Retain...

Page 16: ... temp sensor failure alarm 0 No alarm 1 Alarm 0x0803 Alarm status low 16 bit MSByte Bit7 MSb Low temp system water temp sensor failure 0 No alarm 1 Alarm Bit6 Room temp sensor failure 0 No alarm 1 Alarm Bit5 Refrigeration system low pressure 0 No alarm 1 Alarm Bit4 Refrigeration system High pressure 0 No alarm 1 Alarm Bit3 High temp water pump overload 0 No alarm 1 Alarm Bit2 Low temp water pump o...

Page 17: ...1 23 6A Compressor power 4 95KW 4 54KW 4 95KW 4 70KW 6 73HP 6 05HP 6 73HP 6 39HP Nominal cooling capacity 49474 Btu h 47765 Btu h 49474 Btu h 49133 Btu h 14 5 KW 14 KW 14 5 KW 14 4 KW 12467Kcal h 12039Kcal h 12467Kcal h 12381 Kcal h Refrigerant R 22 R407c R 22 R407c R 22 R407c R407c Refrigerant charge 4400g 3800g 4400g 3600g Precision 1 Reducer Capillary Protection Overcurrent protection for compr...

Page 18: ... Water circulation pipes are blocked or a pipe bending deformation Check water circulation pipe Ultra high temperature alarm controller displays E04 Blocked dust gauze bad thermolysis Unpick and wash the dust gauze regularly Poor ventilation for air outlet and inlet To ensure a smooth ventilationfor air outlet and inlet Voltage is extremely low or astable To improve the power supply circuit or use...

Page 19: ...CW 7500 Series 19 CW 7500 工业循环冷水机 使用安装说明书 ...

Page 20: ...CW 7500 Series 20 目 录 一 使用注意事项 21 二 外形及部件名称 22 三 安装说明 23 四 机组介绍与参数调整 24 五 报警与通讯输出 29 六 MODBUS RS 485 通讯功能 30 七 技术参数 33 八 简单故障处理 34 ...

Page 21: ...电源电压比较敏感 我公司标准产品的正常工作电压为 额定电压 10 如果确实需要更宽的工作电压范围 可以另行定制 3 电源频率不匹配会导致机器损坏 请根据实际情况 使用 50Hz 或 60Hz 的机型 4 为保护循环水泵 严禁无水运行 新机装箱前都排空了储水水箱 请确保水箱注入足够水后再开机 否则水 泵极易损坏 当水箱水位在水位计绿色 NORMAL 范围以下时 冷却机 制冷量会轻微下降 请保证水箱水位在水位计的绿色 NORMAL 范围内 严禁使用循环泵排水 5 请确保冷水机入风 出风通道顺畅 冷水机上面的出风口距离障碍物要留有 100cm 以上的距离 侧面的入风 口离障碍物要求距离在 50cm 以上 6 请注意冷凝水的影响 当水温低于环境温度 并且环境湿度较大时 循环水管与被冷却器件表面 会产生冷凝水 当出现以上情况时 建议调高水温或对水管与被冷却器件进 行保温 7 开机时要先开冷水机 再开...

Page 22: ...CW 7500 Series 22 二 部件介绍 温度控制器 冷媒低压表 水压表 冷媒高压表 电源 报警信号输出端口 电源开关 入风口 注水口 冷却水出口 冷却水入口 出风口 排水口 水位计 排污口 溢水口 ...

Page 23: ...路中会有较多的气泡导致机器偶尔流量报警 水泵 连续运行数分钟后就会恢复正常 3 第一次开机后 必须马上检查水管管路有无漏水 4 按温控器开关键启动制冷系统后 运行指示灯亮 如果水温低于设定温 度 机器的风扇等器件不工作是正常现象 温控器会根据设定的控制参 数自动控制压缩机 电磁阀 风扇等器件的工作状态 5 由于压缩机等器件有一个较长的启动过程 根据不同的工况从几十秒到 数分钟不等 所以不要频繁启停冷水机 5 检查水箱水位 新机开机后排空了水管中的空气 水箱水位会略有下降 为了保持水位 在绿色区域 可以再次适量加水 观察并记下当前的水位情况 等冷水机 运行一段时间后再次观察水位计 如果水位下降明显 就要再次检查水管 管路的渗漏情况 6 调整温控器参数 CW 7500 系列冷水机使用的新型智能控制器的出厂设置为恒温控制模 式 水温设定为 25 度 用户可以根据需要调整 一般情况下 不需要调整控...

Page 24: ...ng 上键 下键 电源键 设置键 Set 快速设置键 Quick Set 退出键 Quit 关机需要长按电源键三秒 其他操作都是短按按键即可 显示 界面如下 2 用户参数快速设置 在正常运行状态下 按下 quick set 键可以进行用户 菜单设置 在显示设定项目时 按 quick set 键 可进入参数调整界面 按上 下键可以进行参数项的切换 如需对参数进行修改 按 quick set 键进入参数 值 按上 下键进行具体参数值调整 调整完毕后 再按 quick set 键保存参 数值并返回参数界面 按 quit 键可退出参数快速设置界面 同时保存所有参数 无按键操作 15 秒后 系统自动退出设置界面 同时保存修改好的参数 3 用户设置菜单 正常运行状态下 长按 set 键 5 秒以上 显示用户输入 密码界面 使用上 下键输入 168 按 set 键后可进入用户设置菜单进行参数 设置 如密...

Page 25: ...quit 键可以退出故障查看状态 5 恢复出厂参数设置 在正常运行状态下 长按 set 键 电源键 10 秒以上 弹出密码输入界面 输入密码 615 密码错误 退出密码输入界面 转入正常 运行状态 密码正确进入管理员设置参数恢复功能 恢复成功后 界面显示 参 数恢复成功 2 秒后转入运行状态 6 机组运行状态查询 同时按 quick set 键 上键并松手 界面显示压缩机 水泵等运行状态和室温排气温度等参数 按上下键翻页 显示 5 秒后自动退出 7 时钟调整 在正常运行状态下 长按 quick set 键 5 秒以上 进入时钟调 整界面 时间年闪烁 用上下键调整年 按 quick set 键确认年 小时闪烁 用上下键调整小时 按 quick set 确认 分钟闪烁 用上下键调整分钟 再按 quick set 键保存时钟设置 8 语言切换 在出厂前系统默认中文界面显示运行状态 如需切换到英文...

Page 26: ...0 180 10 秒 0x040b 12 F12 开机水流量延时检测 0 180 5 秒 0x040c 13 F13 流量报警延时 0 180 2 秒 0x040d 14 F14 制热回差 0 10 0 8 分辨率 0 1 度 0x040e 15 F15 水泵关闭延时 0 180 5 秒 0x040f 16 F16 开机延时 0 180 30 秒 0x0410 17 F17 压缩机启动保护 0 180 90 秒 0x0411 18 F18 相序保护开启设定 On 开启 off 关闭 On 开启 0x0412 19 F19 外部输入功能开启设置 启动及待机 On 开启 off 关闭 off 关闭 0x0413 20 F20 外部输入功能常开常闭设置 NO NC NC NO 常开 NC 常闭 0x0414 21 F21 外部输入启动延时 0 180 0 秒 0x0415 22 F22 外部输入...

Page 27: ...延时检测 5 5 5 5 13 F13 流量报警延时 2 2 2 2 14 F14 制热回差 0 8 0 8 0 8 0 8 15 F15 水泵关闭延时 5 5 5 5 16 F16 开机延时 30 30 30 30 17 F17 压缩机启动保护 30 30 30 30 18 F18 相序保护开启设定 19 F19 外部输入功能开启设 置 启动及待机 off 关闭 off 关闭 off 关闭 off 关闭 20 F20 外部输入功能常开常 闭设置 NC NC NC NC 21 F21 外部输入启动延时 0 0 0 0 22 F22 外部输入待机延时 0 0 0 0 23 F23 开关机按键锁 1 1 1 1 24 F24 上电自启动 off 关闭 off 关闭 off 关闭 off 关闭 1 案例一 智能温控模式控制冷却水温度 要求水温最高不超过 31 度 最 低不低于 25 度 目标水温...

Page 28: ... E01 有报警声 关闭压缩机 冷凝风机 发热棒 自动消除 E02 室温超高报警 显示 E02 有报警声 各制冷部件按正常逻辑运行 自动消除 E03 水温超低报警 显示 E03 有报警声 关闭压缩机 冷凝风机 发热棒 自动消除 E04 水温超高报警 显示 E04 有报警声 各制冷部件按正常逻辑运行 自动消除 E05 错相缺相报警 显示 E05 有报警声 关闭水泵 压缩机 冷凝风机 发热棒 手动消除 E06 压缩机过载报警 显示 E06 有报警声 关闭压缩机 冷凝风机 发热棒 手动消除 E07 水泵过载报警 显示 E07 有报警声 关闭水泵 压缩机 冷凝风机 发热棒 手动消除 E08 制冷系统高压报警 显示 E08 有报警声 关闭压缩机和冷凝风机 手动消除 E09 制冷系统低压报警 显示 E09 有报警声 关闭压缩机和冷凝风机 自动消除 E10 室温传感器故障报警 显示 E10 有报警声 转...

Page 29: ... 1 报警及 MODBUS RS 485 通讯输出接线示意图 2 报警信号工作状态表 机组状态 温度控制器 内置报警器 输出端口 H1 H2 输出端口 H1 H3 说明 正常工作 不响 断路 导通 E00 E01 E05 E06 E07 E08 E09 E11 响 导通 断路 E02 E10 E13 E14 响 断路 导通 E03 E04 响 导通 断路 可选 E12 响 导通 断路 输出端口延时 后动作 注 报警信号端口连接机内继电器一组常开 常闭触点 要求工作电流小于 5A 工作电压小于 300V 报警原因参看故障代码表 ...

Page 30: ...发送的数据字节数 02 2B 00 00 00 64 分别对应寄存器 108 110 中的数值 XX YY 是校验码 如果从机接收到数据有误 则返回数据 01 83 01 XX YY 其中 01 为从 机地址 83 为差错码 01 为异常码 XX YY 为校验码 2 06 命令格式 主机发送命令 从机响应 错误 如 主机发送地址为 1 请求将数据 00 03 写入寄存器 2 的命令 主机发送 01 06 00 02 00 03 XX YY 其中 01 为从机地址 06 为功能码 00 02 为寄存器地址 00 03 为要写入的数据 XX YY 为 CRC 校验码 功能码 1 个字节 0x03 起始地址 2 个字节 0x0400 至 0x044a 0x0100 至 0x0108 0x0800 至 0x0803 寄存器数量 2 个字节 1 到 10 差错码 1 个字节 0x83 异常码 1 个...

Page 31: ...Min 0 1 bit 有 0x0105 电导率 0 1 500 μs cm 0 1 bit 有 0x0106 压缩机电流 三相平均 0 50 A 0 1 bit 有 0x0107 低温水泵电流 0 50 A 0 1 bit 有 0x0108 高温水泵电流 0 50 A 0 1 bit 有 4 只读参数 状态 只读 寄存器地址 描述 位定义 0x0800 继电器输出 状态 MSByte Bit7 MSb 保留 Bit6 保留 Bit5 保留 Bit4 保留 Bit3 保留 Bit2 报警输出继电器 0 关闭 1 打开 Bit1 电导率下限继电器 0 关闭 1 打开 Bit0 LSb 高温发热棒 0 关闭 1 打开 LSByte Bit7 MSb 高温水泵继电器 0 关闭 1 打开 Bit6 高温制冷继电器 0 关闭 1 打开 Bit5 压缩机曲轴箱加热 0 关闭 1 打开 Bit4 低温发...

Page 32: ...温超低报警 0 无报警 1 报警 Bit2 电导率超低报警 0 无报警 1 报警 Bit1 电导率超高报警 0 无报警 1 报警 Bit0 LSb 高温系统水温传感器故障 0 无报警 1 报警 0x0803 报警状态 低 16 位 MSByte Bit7 MSb 低温系统水温传感器故障 0 无报警 1 报警 Bit6 室温传感器故障 0 无报警 1 报警 Bit5 制冷系统低压 0 无报警 1 报警 Bit4 制冷系统高压 0 无报警 1 报警 Bit3 高温水泵过载 0 无报警 1 报警 Bit2 低温水泵过载 0 无报警 1 报警 Bit1 压缩机过载 0 无报警 1 报警 Bit0 LSb 缺相错相 0 无报警 1 报警 LSByte Bit7 MSb 高温系统水温超高 0 无报警 1 报警 Bit6 高温系统水温超低 0 无报警 1 报警 Bit5 低温系统水温超高 0 无报警 1...

Page 33: ...义制冷量 49474 Btu h 48450 Btu h 49474 Btu h 49133 Btu h 14 5 KW 14 2 KW 14 5 KW 14 4 KW 12467Kcal h 12209Kcal h 12467Kcal h 12381 Kcal h 制冷剂 R 22 R407c R 22 R407c R 22 R407c R407c 充注量 4400g 3800g 4400g 3600g 温控精度 1 节流器 毛细管 安全保护 压缩机过流保护 流量报警 超温报警 水泵功率 0 37 1 1KW 水箱容量 75L 出入水口 Rp 1 最大扬程 28 53M 最大流量 70 116L min 净重 325Kgs 毛重 410Kgs 机器尺寸 129 X70 X 149 cm L X W X H 包装尺寸 145 X 92 X 178 cm L X W X H 说明 制冷量标定...

Page 34: ...水位计显示窗 加水到水位显 示的绿色区域 并检查水循环管路 有无漏水 连接设备使用时流量报警 温控器 面板显示 E01 但用水管直接连接 出水口 入水口时有水流 不报警 水循环管路有堵塞或水管折弯 变形 检查水循环管路 水温超高报警 温控器面板显示 E04 防尘网堵塞 散热不良 定期拆下防尘网清洗 出风口或入风口通风不良 保证出风口 入风口通风顺畅 电压严重偏低或者不稳定 改善供电线路或使用稳压器 温控器参数设置不当 重新设定控制参数或恢复出厂设置 冷却机频繁开关机 保证冷水机有足够的制冷时间 五分钟以上 热负荷超标 降低热负荷 或选用更大制冷量的 机型 室温超高报警 温控器面板显示 E02 冷水机使用环境温度偏高 改善通风 保证冷水机运行环境在 40 度以下 冷凝水凝结现象严重 水温低于环境温度较多 湿度大 调高水温或给管路保温 换水时排水口排水缓慢 注水口没有打开 打开注水口 ...

Reviews: