5800SMOKEV 

Wireless Smoke/Heat Detector 

Installation and Setup Guide 

 

 

 

GENERAL INFORMATION 

This is a multi-criteria wireless smoke 
detector which employs advanced levels of 
detection and discrimination.  This reduces 
common cooking nuisance alarms and 
allows faster detection to different types of 
fire conditions.  It is intended for use with 
Control Panels that support 5800 series 
devices.

 

To remove the mounting bracket, 

turn 

the top of the detector 15 degrees 
counterclockwise and separate the 
mounting bracket and top cover.

 

 

 

5800SMOKEV 

 

Open 

ENROLLMENT  

The smoke detector must be enrolled in the Control Panel before it 
can operate in the system. The 5800SMOKEV smoke/heat 
protection zone must be enrolled as Loop 1 and “Input Type” 3 
(supervised RF). 

If programmed, this smoke detector is capable of monitoring the 
additional conditions of Maintenance (transmitted as Loop 2), and 
Low Temperature (transmitted as Loop 3). Tamper is transmitted as 
Loop 4, but does not require programming.  To take advantage of 
the value added features of Maintenance and Low Temperature, you 
must program each loop as a separate zone in the 5800 series 
wireless compatible panel. 

1.  Enter the Control’s Zone Programming mode. 

2.  Enter the zone number to be programmed. 

3.  Enter the applicable zone type when prompted.  Program 

  Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16),  

  Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 

19), and  

  Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8). 

NOTE

: Loop 2 High/Low Maintenance is supported only on 

commercial control panels such as the Vista-128FBP. 

4.  When prompted, enter Input Type 03 (3 on some control panels) 

– Supervised RF Transmitter. 

 

5.  When prompted for the serial number, transmit from the 

detector by activating the tamper switch.  To do this, hold 
the base of the detector in one hand, and rotate the 
detector counterclockwise on the base until it snaps 
open.  Then return to clockwise position until the detector 
snaps into place.  

6.  When the serial number is displayed, transmit from the 

detector a second time by activating the tamper switch 
again as described in Step 5.  The current loop number 
(4) will begin to flash. 

7.  Manually change the loop number to the desired loop 

number for the zone (according to the application). 

8.  When programming for this zone is complete, program 

other zones for the transmitter as necessary (except for 
Tamper Loop 4, which does not require programming).  

 

WARNING:  The fire protection zone enrolled must 
always be Loop 1.  Otherwise, fire annunciations will 
not be reported by the Control Panel. 

9.  Exit Programming mode when programming is complete 

and test the detector. Refer to the Testing Section. 

See the Control Panel’s installation instructions for further 
details.  

PROGRAM 

 

Consult the Control Panel’s instructions to program the device in the system.  This detector reports the following signals to the 
Control Panel: 

  Smoke and Heat detection 

-

  Smoke Alarm when smoke is detected 

-

  Heat Alarm when temperature of 135° F (57° C) or greater 

-

  Rate-of-Rise Alarm when temperature is >104° F (40° C) @ 15° F/minute (8.33° C/minute). 

  Maintenance:  Contaminated chamber that requires cleaning 

  End-of-Life 

  Base Tamper:  It sends a tamper signal to the Control Panel when the smoke head is removed from its base. 

  Supervision:  The detector will transmit its status every 60-70 minutes. 

 

TAMPER

 

When the detector is removed from its base, it sends a 
tamper signal to the Control Panel.  OPTIONAL:  The 
detector can be made tamper-proof to prevent unauthorized 
removal from its base.  Break off the small pillar on the 
base as shown. This causes the detector to latch to the 
base.  From this point on, to remove the detector from its 
base, you must use a small screwdriver to release the catch 
(push the catch towards the base) and twist the detector 
counterclockwise.  A screw can be added to prevent 
removal from the base. 

 

 

 

 