AVAILABLE IN 5 VDC AND 10 to 30 VDC VERSIONS 

!

0.3" (7.6 mm) HIGH, 6 DIGIT DISPLAY

!

BI-DIRECTIONAL TIMING

!

DISPLAY SCROLLING (SELECTABLE)

!

SOLID-STATE CURRENT SINKING OUTPUTS

!

PROGRAMMABLE TIMED OUTPUTS

!

REMOTE RESET CAPABILITY

!

SIMPLIFIED FRONT PANEL PROGRAMMING

!

ABILITY TO LOCK OUT FRONT PANEL FUNCTIONS

!

ON-LINE SELF-TEST

!

SEALED FRONT PANEL CONSTRUCTION (NEMA 4X/IP65)

!

NON-VOLATILE MEMORY (E

2

PROM)

!

4 TIME RANGES

0.01 SECONDS
0.01 MINUTES
0.001 SECONDS
0.001 MINUTES

DESCRIPTION

The LNXNT presettable Timer is an economical and reliable solution to dual

preset level timing requirements. This unit features current sinking input
configurations, programmable timed outputs, non-volatile memory, and many
other features that satisfy most dual preset timing applications.

The LNXNT Timer has two main timing actions, Reset to Zero 

(RTZ)

and

Reset to Preset (

RTP

). There are sixteen modes of operation.

All parameters are programmed through the front panel buttons. The LNXNT

Timer has an internal non-volatile memory device which eliminates the need for
battery back-up. When power is removed or interrupted, this device maintains all
data set-ups necessary for system operation. A Program Disable terminal is
provided, which prevents accidental changes or tampering by unauthorized
personnel to the presets or timed output values. The front panel reset button can
be enabled or disabled by a rear panel DIP switch. This timer has an on-line self-
test, which can be run at any time without losing time or missing a preset value.

Power, input, and output connections are made via fixed terminal blocks at

the rear of the unit. DIP switches at the rear of the unit are used to set the input
configuration and the desired mode of operation.

The LNXNT Timer has a sealed high impact plastic bezel and meets NEMA

4X/IP65 specifications for wash-down and/or dust, when properly installed.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

Do not use this unit to directly command motors, valves, or other actuators

not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit.

SPECIFICATIONS

1. 

DISPLAY

: 6-digit, 0.3" (7.6 mm) high LCD display.

2. 

POWER REQUIREMENTS

: 25 mA @ 5 VDC (±5%) or

25 mA @ 10 to 30 VDC. 

Power supplies must be Class 2 or SELV rated.

3. 

RUN INPUT

: Accepts switch contact closures and NPN Open Collector

outputs and similar types of current sinking sensors. 
V

IL

= 0.5 V max., internally pulled up to 5 VDC through a 10 K

resistor

(I

SNK

= 0.5 mA). Response time = 1 msec. 

(This unit operates with VCM E

through H modules)

4. 

TIME ACCURACY

: ±0.01%

5. 

TIME RANGES:

Time

Max. Display

0.01 sec

9999.99

0.001 sec

999.999

0.01 min

9999.99

0.001 min

999.999

6. 

CONTROL INPUTS: 

Activate low (V

IL

= 0.5 V max.), internally pulled up

to 5 VDC through a 10 K

resistor (I

SNK

= 0.5 mA).

Remote Reset

: Response time = 10 msec. A low resets the unit and

deactivates outputs.

Program Disable

: A low inhibits the changing of presets and timed outputs,

as well as testing outputs in self-test.

MODEL LNXNT - SHORT CASE DUAL PRESET TIMER

DIMENSIONS  In inches (mm)

Note: Recommended minimum clearance (behind the panel) for 

mounting clip installation is 2.7" (68.6)H x 4.0" (101.6)W.

CAUTION:

Read complete instructions prior to

installation and operation of the unit.

Bulletin No.  LNXNT-B
Drawing No.  LP0308
Released  9/02

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com

1

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Summary of Contents for LNXNT Series

Page 1: ...own and or dust when properly installed SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety...

Page 2: ...et S2 to S5 These are the mode select DIP switches See Modes of Operation for the switch settings of a specific mode S6 0 00 Sets the timer to display two decimal places 0 000 Sets the timer to displa...

Page 3: ...m zero when preset 1 is reached output 1 turns on When preset 2 is reached output 1 turns off and output 2 turns on for the amount of time programmed Time continues to accumulate after the preset leve...

Page 4: ...o decrement after the preset levels have been reached When a manual reset is performed the time resets to preset 2 the outputs turn off and the cycle starts again MODE 9 TIMED OUTPUTS AT PRESET 1 AND...

Page 5: ...urns on When zero is reached output 2 turns on The outputs turn off at the end of their respective programmed time values At zero the time automatically resets to preset 2 and the cycle starts again M...

Page 6: ...priate standards of good installation local codes and regulations It is recommended that power supplied to the unit AC or DC be protected by a fuse or circuit breaker Strip the wire leaving approximat...

Page 7: ...nt affecting the timed output durations or interfering with control functions This test verifies that all digits operate Also the DIP switch settings and the outputs can be tested If the outputs are n...

Page 8: ...nit Installation The unit meets NEMA 4X IP65 requirements for indoor use when properly installed The units are intended to be mounted into an enclosed panel with a gasket to provide a water tight seal...

Reviews: