background image

  1 / 16 

PI500A Series basic frequency inverter user manual 

1. 

 

Foreword 

Thank you for choosing POWTRAN PI500A serices basic frequency inverter . 
The diagram of operating manual ,Maybe slightly different from the product for convenience of 

explanation, Due to product upgrades, they may be slightly different. Please refer to the actual product. 

The end-users should hold this manual,and keep it well for furture maintenance & care . 
For any problem within the warranty period,please fill out the warranty card and fix it to our authorized 

dealer 

2. 

 

Instructions on nameplate 

 

Model designation 

POWTRAN Inverter

PI  500A  2R2    G   3

Rated output capacity
    2R2

2.2kW

    004

4kW

Serices Code

PI500A serices

Input Voltage Level
1:Single-phase 220V   2:Three-phase 220V
3:Three-phase 380V  4:Three-phase 480V

  Function code

F:  Light load ,

G:Standard load

 

3. 

 

Dimension 

A

B

H1

D1

D

W

H

E

d

 

Note:0.75 to 4kW G3 supports rail mounting 

0.75 to 4kW G3 dimensions 

 

A

B

H1

H

W

D

D1

d

 

5.5 to 11kW G3 dimensions 

D1

H

A

W

D

B

d

 

15

22kW G3 dimensions 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...

Page 16: ...yboard compartment Dimension drawing of keyboard compartment dimension unit mm PI500 pI500A keyboard installation opening dimension drawing Mounting panel Opening size of external mounting panel Openi...

Reviews: