Programmable Controller

FP-XH Expansion Analog Unit

User’s Manual

[Applicable models]
AFPXHEAD4
AFPXHEAD8
AFPXHEDA4
AFPXHEA21

WUME-FPXHAIO-01

2022.2

panasonic.net/id/pidsx/global

Summary of Contents for AFPXHEAD4

Page 1: ...Programmable Controller FP XH Expansion Analog Unit User s Manual Applicable models AFPXHEAD4 AFPXHEAD8 AFPXHEDA4 AFPXHEA21 WUME FPXHAIO 01 2022 2 panasonic net id pidsx global...

Page 2: ...MEMO 2 WUME FPXHAIO 01...

Page 3: ...rpose of use Manual name Manual code FP XH Control Unit FP XH User s Manual Basic Edition WUME FPXHBAS FP XH Programming Manual WUME FPXHPGR Positioning Function PWM Output High speed Counter Function...

Page 4: ...characteristics and performance values of the product Do not disassemble or modify this product Doing so may result in abnormal heat generation or smoke generation Do not touch any terminals while th...

Page 5: ...Indicates operation procedures WUME FPXHAIO 01 v...

Page 6: ...MEMO vi WUME FPXHAIO 01...

Page 7: ...Other Devices 2 4 2 2 2 Terminal Layout AFPXHEAD4 AFPXHEAD8 2 4 2 2 3 Terminal Layout AFPXHEDA4 2 5 2 2 4 Terminal Layout AFPXHEA21 2 7 2 3 Wiring to the Connector 2 8 2 3 1 Suitable Parts and Tools...

Page 8: ...mes 64 times 128 times 5 2 5 1 3 Enabling Averaging Processing Setting 5 3 5 2 Disconnection Detection 5 5 6 Troubleshooting 6 1 6 1 What to Do If an Error Occurs Analog Input 6 2 6 1 1 Failure in Rea...

Page 9: ...1 3 1 2 1 Expansion to the FP XH Control Unit 1 3 1 2 2 Restrictions on Using the FP X Expansion FP0 Adapter 1 3 1 3 Names and Functions of Parts 1 5 1 3 1 Analog Input Unit AFPXHEAD4 1 5 1 3 2 Analog...

Page 10: ...A21 1 1 2 Expansion Cables Applicable cables An 8 cm expansion cable is provided with the Expansion Unit When the expansion cable is used an I O check error may occur due to noise etc In such a case i...

Page 11: ...9F WY50 to WY59 4th Expansion Unit X600 to X69F WX60 to WX69 Y600 to Y69F WY60 to WY69 5th Expansion Unit X700 to X79F WX70 to WX79 Y700 to Y79F WY70 to WY79 6th Expansion Unit X800 to X89F WX80 to WX...

Page 12: ...n be connected when using the FP X Expansion FP0 Adapter 3 FP X Expansion FP0 Adapter Connect it to the right of the FP XH Expansion Analog Unit Only one unit can be connected 4 FP0 Expansion Unit Up...

Page 13: ...ed to connect analog input devices CH0 to CH3 5 Terminator setting DIP switch Turn ON all the switches on the DIP switch for the terminal Expansion Unit Turn OFF all the switches on the DIP switch for...

Page 14: ...r setting DIP switch Turn ON all the switches on the DIP switch for the terminal Expansion Unit Turn OFF all the switches on the DIP switch for the Expansion Units other than the terminal Expansion Un...

Page 15: ...or setting DIP switch Turn ON all the switches on the DIP switch for the terminal Expansion Unit Turn OFF all the switches on the DIP switch for the Expansion Units other than the terminal Expansion U...

Page 16: ...CH0 to CH1 and an analog output device CH0 5 Terminator setting DIP switch Turn ON all the switches on the DIP switch for the terminal Expansion Unit Turn OFF all the switches on the DIP switch for t...

Page 17: ...al Layout 2 3 2 2 Wiring the Analog I O 2 4 2 2 1 Connecting to Other Devices 2 4 2 2 2 Terminal Layout AFPXHEAD4 AFPXHEAD8 2 4 2 2 3 Terminal Layout AFPXHEDA4 2 5 2 2 4 Terminal Layout AFPXHEA21 2 7...

Page 18: ...LC Power supply sequence The power supply sequence should be set up so that the power supply of the PLC turns off before the power supplies for input and output If the power supplies for input and out...

Page 19: ...2 1 3 Terminal Layout Power supply terminal 24V 0V 1 2 3 Pin No Name Function 1 24 V Power supply input 2 0 V Power supply input 3 GND Power supply GND 2 1 Wiring the Power Supply WUME FPXHAIO 01 2 3...

Page 20: ...se double core twisted pair shielded wires It is recommended to ground them However depending on the conditions of the external noise it may be better not to ground the shielding Do not place the anal...

Page 21: ...XHEAD8 only VI4 COM VI5 COM COM COM VI6 VI7 CH4 CH5 CH6 CH7 1 2 3 4 5 6 7 8 Pin No Name Function Channel 1 VI4 Voltage current signal input CH4 2 COM Input common 3 VI5 Voltage current signal input CH...

Page 22: ...terminals are connected within the unit Analog terminal block 2 COM COM CH2 CH3 NC V3 I3 V2 I2 NC 1 2 3 4 5 6 7 8 Pin No Name Function Channel 1 V2 Voltage signal output CH2 2 I2 Current signal output...

Page 23: ...signal input Input CH0 2 COM Input common 3 VI1 Voltage current signal input Input CH1 4 COM Input common 5 NC Not used 6 V0 Voltage signal output Output CH1 7 I0 Current signal output 8 COM Output c...

Page 24: ...ntact Co Ltd 0 25 mm2 AWG24 AI 0 25 6 YE 0 50 mm2 AWG20 AI 0 5 6 WH 0 75 mm2 AWG18 AI 0 75 6 GY 1 00 mm2 AWG18 AI 1 6 RD Crimping tool dedicated to rod terminals Manufacturer Model number Product No P...

Page 25: ...tion number Phoenix Contact Co Ltd SZS 0 4x2 5 1205037 The following precautions should be observed to avoid broken or disconnected wires When removing the wire s sheath be careful not to scratch the...

Page 26: ...MEMO 2 10 WUME FPXHAIO 01...

Page 27: ...es 3 8 3 3 2 Input Range Setting Area 3 8 3 3 3 Averaging Processing Setting 3 10 3 3 4 Output Range Setting Area 3 11 3 4 Analog Input Functions 3 12 3 4 1 Analog Input Specifications 3 12 3 4 2 Anal...

Page 28: ...X70 WX80 WX90 WX100 Analog input value CH1 WX31 WX41 WX51 WX61 WX71 WX81 WX91 WX101 Analog input value CH2 WX32 WX42 WX52 WX62 WX72 WX82 WX92 WX102 Analog input value CH3 WX33 WX43 WX53 WX63 WX73 WX83...

Page 29: ...t value CH4 WX34 WX44 WX54 WX64 WX74 WX84 WX94 WX104 Analog input value CH5 WX35 WX45 WX55 WX65 WX75 WX85 WX95 WX105 Analog input value CH6 WX36 WX46 WX56 WX66 WX76 WX86 WX96 WX106 Analog input value...

Page 30: ...unit 4th unit 5th unit 6th unit 7th unit 8th unit I O numbers occupied by the unit WY30 WY39 WY40 WY49 WY50 WY59 WY60 WY69 WY70 WY79 WY80 WY89 WY90 WY99 WY100 WY109 Analog output value CH0 WY30 WY40...

Page 31: ...WX74 WX84 WX94 WX104 Output contact WY Item Expansion location 1st unit 2nd unit 3rd unit 4th unit 5th unit 6th unit 7th unit 8th unit I O numbers occupied by the unit WY30 WY39 WY40 WY49 WY50 WY59 WY...

Page 32: ...on is valid only when the range setting is set to 4 to 20 mA or 1 to 5 V If a disconnection state is detected H8000 K 32768 is stored The detection level for disconnection detection is as follows Inpu...

Page 33: ...PXHEA21 CH0 Analog output status Bit OFF Normal Bit ON Error Operation of the analog output status error An error is notified when the data stored in the analog output values CH0 to CH3 exceeds the se...

Page 34: ...0 mA K0 to K 32000 For 4 to 20 mA K0 to K 25600 I O allocation Channel Expansion location 1st unit 2nd unit 3rd unit 4th unit 5th unit 6th unit 7th unit 8th unit CH0 WY30 WY40 WY50 WY60 WY70 WY80 WY90...

Page 35: ...nit 7th unit 8th unit Input range setting area 1 CH0 to CH3 WY30 WY40 WY50 WY60 WY70 WY80 WY90 WY100 Input range setting area 2 CH4 to CH7 WY31 WY41 WY51 WY61 WY71 WY81 WY91 WY101 I O contents Input r...

Page 36: ...n Channel Expansion location 1st unit 2nd unit 3rd unit 4th unit 5th unit 6th unit 7th unit 8th unit Averaging processing setting 1 CH0 to CH3 WY32 WY42 WY52 WY62 WY72 WY82 WY92 WY102 Averaging proces...

Page 37: ...to 10 V H5 5 to 5 V H6 1 to 5 V H7 4 to 20 mA H0 H8 to F Do not use the analog input I O allocation Channel Expansion location 1st unit 2nd unit 3rd unit 4th unit 5th unit 6th unit 7th unit 8th unit C...

Page 38: ...al input range 10 to 10 V DC 5 to 5 V DC K 32000 to K 32000 0 to 10 V DC 0 to 5 V DC K 0 to K 32000 1 to 5 V DC K 0 to K 25600 0 to 20 mA K 0 to K 32000 4 to 20 mA K 0 to K 25600 Conversion speed 1 ms...

Page 39: ...lue is entered in the Input range setting area using the user program the analog input range is set in the unit When H1 to H7 is entered in the Input range setting area the analog input is started If...

Page 40: ...r each channel data is allocated from the lower level in the order of CH0 CH1 CH2 and CH3 Input range setting area 2 The range setting data for each channel data is allocated from the lower level in t...

Page 41: ...each input range are as follows Input range Digital conversion value For 10 to 10 V 5 to 5 V K 32000 to K 32000 For 0 to 10 V 0 to 5 V K0 to K 32000 For 1 to 5 V K0 to K 25600 For 0 to 20 mA K0 to K...

Page 42: ...3 4 Analog Input Functions 3 16 WUME FPXHAIO 01...

Page 43: ...5 V DC K 0 to K 25600 0 to 20 mA K 0 to K 32000 4 to 20 mA K 0 to K 25600 Conversion speed 1 ms all channels Output impedance voltage output 0 5 or less Maximum output current voltage output 10 mA Ou...

Page 44: ...he user program to set the 10 to 10 V range to CH0 and CH1 and the 4 to 20 mA range to CH2 and CH3 R0 F0 MV H7744 WY36 Output range setting value H1 0 to 10 V H2 0 to 5 V H3 0 to 20 mA H4 10 to 10 V H...

Page 45: ...ersion values Digital conversion values for each output range are as follows Output range Digital conversion value For 10 to 10 V 5 to 5 V K 32000 to K 32000 For 0 to 10 V 0 to 5 V K0 to K 32000 For 1...

Page 46: ...3 5 Analog Output Functions 3 20 WUME FPXHAIO 01...

Page 47: ...4 Analog I O Conversion Characteristics 4 1 Input Conversion Characteristics 4 2 4 2 Output Conversion Characteristics 4 6 WUME FPXHAIO 01 4 1...

Page 48: ...the rated range Analog input value Converted value 10 V or more 32 000 10 V or less 32 000 Voltage input range 5 to 5 V Input range 5 to 5 V Analog input value V Digital conversion value K 5 32 000 2...

Page 49: ...ange Analog input value Converted value 10 V or more 32 000 0 V or less 0 Voltage input range 0 to 5 V Input range 0 to 5 V Analog input value V Digital conversion value K 5 32 000 4 25 600 3 19 200 2...

Page 50: ...og input value Converted value 5 V or more 25 600 1 V or less 0 Current Input range 0 to 20 mA Input range 0 to 20 mA Analog input value mA Digital conversion value K 20 32 000 16 25 600 12 19 200 8 1...

Page 51: ...Analog input value mA Digital conversion value K 20 25 600 16 19 200 12 12 800 8 6 400 4 0 0 0 When exceeding the rated range Analog input value Converted value 20 mA or more 25 600 4 mA or less 0 4...

Page 52: ...value Analog output value 32 640 or more Output at 10 2 V 32 640 or less Output at 10 2 V Voltage output range 0 to 10 V Output range 0 to 10 V Digital input value K Analog output value V 32 000 10 25...

Page 53: ...log output value 32 640 or more Output at 5 1 V 640 or less Output at 0 1 V Voltage output range 1 to 5 V Output range 1 to 5 V Digital input value K Analog output value V 25 600 5 19 200 4 12 800 3 6...

Page 54: ...ue 32 640 or more Output at 5 1 V 32 640 or less Output at 5 1 V Current output range 0 to 20 mA Output range 0 to 20 mA Digital input value K Analog output value mA 32 000 20 25 600 16 19 200 12 12 8...

Page 55: ...put value K Analog output value mA 25 600 20 19 200 16 12 800 12 6 400 8 0 4 When exceeding the rated range Digital input value Analog output value 26 240 or more Output at 20 4 mA 640 or less Output...

Page 56: ...MEMO 4 10 WUME FPXHAIO 01...

Page 57: ...Analog Input Average Processing 5 2 5 1 1 Moving average 10 times 5 2 5 1 2 Number of averaging times 64 times 128 times 5 2 5 1 3 Enabling Averaging Processing Setting 5 3 5 2 Disconnection Detection...

Page 58: ...and the remaining eight values are averaged and stored in the external input area WX If a fraction results from the calculation it is rounded off Operation Timing chart Analog input value Read timing...

Page 59: ...tion is carried out with the average of data for 64 times or 128 times Method for setting the number of averaging times The number of averaging times can be changed by being written to the output rela...

Page 60: ...tting 2 CH4 to CH7 WY33 WY43 WY53 WY63 WY73 WY83 WY93 WY103 I O contents Averaging processing setting 1 The range setting data for each channel data is allocated from the lower level in the order of C...

Page 61: ...detection The disconnection detection is valid only when the analog input range setting is set to 4 to 20 mA or 1 to 5 V If a disconnection state is detected H8000 K 32768 is stored in the Analog inpu...

Page 62: ...MEMO 5 6 WUME FPXHAIO 01...

Page 63: ...Input Data 6 2 6 1 2 Unstable Analog Input Values 6 2 6 1 3 No Proper Conversion Values Obtained with Current Input 6 2 6 2 What to Do If an Error Occurs Analog Output 6 3 6 2 1 Unstable Analog Output...

Page 64: ...ot placed close to AC lines or high tension lines or bundled with the lines 3 Check that there are no power lines high tension lines high capacity relays or noise generating equipment such as inverter...

Page 65: ...program again 6 2 2 Unchanged Analog Output Value Situation The analog output value remains unchanged Solution 1 Check that the unit is in RUN mode 2 Check again that I O allocations are correct 3 Che...

Page 66: ...pply to the FP XH Expansion Analog Unit is turned OFF or the expansion cable is disconnected Use the special data registers DT90010 and DT90011 to check the Expansion Unit whose connection state has b...

Page 67: ...7 Specifications 7 1 General Specifications 7 2 7 2 Analog Input Specifications 7 3 7 3 Analog Output Specifications 7 4 7 4 External Dimensions Unit mm 7 5 WUME FPXHAIO 01 7 1...

Page 68: ...earth terminals 500 V AC for 1 minute Isolation resistance Test voltage 500 V DC Between analog I O terminal and power supply terminal function earth terminals 100 M or more Vibration resistance 5 to...

Page 69: ...ess at 0 to 55 Current 0 3 F S or less at 25 0 6 F S or less at 0 to 55 Input impedance Voltage Approx 1 M Current Approx 250 Absolute max input Voltage input 15 to 15 V DC voltage input Current input...

Page 70: ...to 20 mA K 0 to K 25600 Conversion speed 1 ms all channels Output impedance voltage output 0 5 or less Maximum output current voltage output 10 mA Output allowable load resistance current output 500...

Page 71: ...7 4 External Dimensions Unit mm AFPXHEAD4 AFPXHEA21 82 60 90 AFPXHEAD8 AFPXHEDA4 60 90 82 7 4 External Dimensions Unit mm WUME FPXHAIO 01 7 5...

Page 72: ...MEMO 7 6 WUME FPXHAIO 01...

Page 73: ...Record of Changes The manual code is shown at the bottom of the cover page Date Manual code Record of changes Feb 2022 WUME FPXHAIO 01 1st edition WUME FPXHAIO 01...

Page 74: ...the high level of reliability and safety Acceptance inspection In connection with the Products you have purchased from us or with the Products delivered to your premises please perform an acceptance...

Page 75: ...MEMO WUME FPXHAIO 01...

Page 76: ...ju Road Suzhou New District Jiangsu China Telephone 86 512 6843 2580 panasonic net id pidsx global For our sale network please visit our website Panasonic Industrial Devices SUNX Co Ltd 2022 February...