1.  Unpack the monitor, antenna and the data/power cable. The 25-

pin connector plugs onto the front of the OmniMetrix

®

 monitor. 

This cable includes wires to power the monitor as well as wires 
for alarm inputs, relay outputs and analog inputs. Take a 
moment to inspect all components to verify there is no shipping 
damage. 

2.  Place the antenna vertically on the roof of the generator and 

route the antenna cable into the area of the generator control. 
The antenna used for transmitting must be installed to provide a 
separation distance of at least 20 cm from all persons and must 
not transmit simultaneously with any other antenna transmitters. 
BE SURE to provide a drip loop lower than the monitor to keep 
water from running down the antenna cable into the monitor 
connection.   

3. 

Attach the monitor via its magnetic feet, on top of the engine 
controller or other appropriate location. Horizontal surfaces are 
best, but the unit may be mounted vertically or even upside down 
if necessary.

 Note: If mounted vertically, install the monitor with 

the cables down to prevent water from entering the enclosure. 

4.  Route the data/power cable into the generator control enclosure.  
5.  The monitor wires to the Basler terminal board using the wiring 

definitions as shown in Table 1 (next page)..  

6.  Attach the antenna cable to the front of the monitor, and tighten 

thumb tight

 

7.  Turn on the monitor and confirm that the LEDs light up and blink. 

If not, check for power on the terminal strip. If, after 5 minutes, 
the only LED lit is the Power LED, check the antenna mount and 
cable connection

 

8.  Allow 15 minutes for the monitor to log into the network and then 

call OmniMetrix at 770-209-0012 to confirm installation. Access to 
machine data is through the OmniView

®

 web interface at 

www.omnimetrix.net

. Contact OmniMetrix for login instructions 

and web training.

 

Data/Power Cable 

DGC2020 Controller 

DGC2020 Wiring 