PLD-25/NiMH

  SELF TESTING MAINTAINED EMERGENCY 

 ILLUMINATION SIGN 

LED

Page

 

1 from

 4

Page 4 from

 4

Thank  you  for  purchasing  this  product  of 
Olympia Electronics. A European manufacturer.

GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

 

where emergency light is needed.
E a c h   l u m i n a i r e   m u s t   b e   p e r m a n e n t l y  
connected to mains power supply

.

In normal operation the led strip lights and the 
battery is charging.
In  case  of  a  mains  power  supply failure  the  
luminaire  will  light the led strip automatically in 
emergency  mode  (powered  by  its  battery).   
When  the    mains    power    supply    is    restored 
the device turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 2,3,4.

Battery charging

The  battery  charging  is  completely  controlled

Therebuy, 

the 

best 

possible 

 

battery 

maintenance  is

 

achieved

as  well  as  the 

elongation of its duration

When the battery has 

completely  charged

it  charges  with  a 

maintenance current.

Battery Cut-off

The luminaire enters in this operation when the 
mains  power  supply  fails

 

and  battery  has  lost 

its  energy

During  this  operation  the  luminaire 

enters the idle state

 

and battery consumption is 

negligible,  in  order  to  be  protected  from  deep 
discharge.

Manual

 Test

This  test  can  be  done  by  pressing  the  test 

button.  The  light  source  and  the  emergency 
circuit  of  the  device  is  monitored.  The  manual 
test  can  be  conducted  only  if  the  main  power 
supply  and  the  battery  is  connected.  During 
this test period all indication LEDs are OFF. 

Automatic operational test

This  test  includes  all  the  operations  that 
provide  the  manual  test  and  is  conducted 
automatically  every  15  days.  In  order  to  be 
performed,  the  main  power  supply  and  the 
battery should be connected. 

Automatic Autonomous Test

The  Automatic  autonomous  Test  is  conducted 
and  measures  the  device’s  back  up  operation 
and emergency duration. This test is conducted 
automatically  every  6  months

In  order  to  be 

performed,  the  main  power  supply  and  the 
battery should be connected and fully charged

If  the  battery  is  not  fully  charged

the  test  is 

postponed

 

until  the  battery  is    completely 

charged.  If  during  this  test,  the  autonomy  is 
less  than  nominal  then  the  battery  fault  led 
turned on continuously and the battery must be 
replaced. 

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency  mode  is  at  least  the  one  that  is 
stated in the list of the technical characteristics. 
During  emergency  mode,  a  light  source  test  is 
also performed.

Resetting Errors

Push the Test button for more than 5 seconds, 
to delete all the indicated LED errors. Then  the 

Operation  temperature range

Relative humidity
Construction materials
External dimensions

 (

LxWxH)

Typical weight

Guarantee

Mains voltage

Maximum power consumption

Recharging  time

Battery protection
Indications / Control

Minimum emergency duration

Degrees of cover protection

Viewing distance

Produced in accordance with 

Light source intensity (230V / emerg.)

3h

24h

Overcharging and full discharging protection

Charge LED, Lamp Fault LED, Battery Fault LED / Test button

IP 44

26m

90lm / 100lm 

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

, EN 1838

5   40  C

o

to

up to 95% 

Fire retardant ABS

plexiglas

280x49x209mm

3 years (1 year for the battery)

890gr.

Battery (Ni-MH)

3.6V/1.5Ah

3.5W / 4VA

220-240V AC/50-60Hz

8

8

2γρ 

ME PVC

922502500_09_001

922502500_09_001

High Quality European based Manufacturers

HANGING INSTALLATION

A-1130, A-1131, A-1132 SET

(OPTIONAL AFTER REQUEST)

Battery replacement process

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained   

1: 

Maintained

 (*)   

A: 

Including test device

G: 

Internally illuminated safety sign

    

180: 

3 hour duration

1

   Power off the device

2

   Dismantle the luminaire by pushing the lock/unlock hooks on each side and pull it down. 

3

   

Remove the old battery and install the new battery’s connector to the appropriate P.C.B

 

  

     connector. 

4

   Place upwards the luminaire until the plastic hooks are securely locked.

5

   Power on the device

.

 

(*) 

Maintained operation: The luminaire lights its illumination 

source, when it is powered by the mains power supply or not

Non-Maintained operation: The luminaire lights its illumination 
source,

 

only in  power supply’s failure.

Α

Α-1130
Α-1131
Α-1132

Tube

Α=1

m

Α=0

.

5

m

Α=0

.

25

m

The light source contained in this luminaire shall only be replaced by the 

manufacturer, or his agent, or a similar qualified person.

3

2

1

GENERAL!!

 

Measure the distance of the 
mounting holes and after the drilling 
place on these spots the mounting 
plugs and fasten the base with the 
mounting screws.

LED MODULE CHARACTERISTICS

Manufacturer

Model Number
Voltage Range

Connections

Nominal Power

Temperature (tc)

olympia electronics S.A

45 °C max. across the board

Non reversible connection between main pcb and led module

11-14V DC

780mW

0409153

PLD-25/NiMH

        TECHNICAL CHARACTERISTICS (for LED MODULE SPECS. see page 4)