background image

 

 

 

EN 

BU 0505 

SK 54xE 

Users Manual for Frequency Inverters 

Summary of Contents for NORDAC PRO SK 5 E-111 CP Series

Page 1: ...EN BU 0505 SK 54xE Users Manual for Frequency Inverters...

Page 2: ...approved 3 Transport storage Information regarding transport storage and correct handling must be complied with 4 Installation The installation and cooling of the equipment must be implemented accord...

Page 3: ...rs are devices for stationary installation in control cabinets All details regarding technical data and permissible conditions at the installation site must be complied with Commissioning commencement...

Page 4: ...a size 10 and 11 Amendment of fuses types and sizes Update of EC EU Declaration of Conformity Revision of the section General conditions for ColdPlate technology BU 0505 July 2021 6075052 3021 V 2 3 R...

Page 5: ...Publisher BU 0505 EN 3021 5...

Page 6: ...Brake resistor BR 36 2 6 1 Electrical data for brake resistors 37 2 6 2 Dimensions of bottom mounted BR SK BR4 38 2 6 3 Dimensions of chassis BR SK BR2 40 2 6 4 Brake resistor assignments 40 2 6 5 Co...

Page 7: ...chnology 186 8 Additional information 189 8 1 Setpoint processing 189 8 2 Process controller 191 8 2 1 Process controller application example 191 8 2 2 Process controller parameter settings 192 8 3 El...

Page 8: ...requency inverter 38 Fig 6 Typical brake resistor connections 43 Fig 7 Diagram of a DC coupling 56 Fig 8 Diagram of a DC coupling with an input feedback unit 57 Fig 9 Modular assemblies SK 5xxE 77 Fig...

Page 9: ...NORD TTL HTL incremental encoders 74 Table 24 Colour and contact assignment for SIN COS encoders 74 Table 25 Signal details for SIN COS encoders 75 Table 26 Signal details for Hiperface encoders 75 Ta...

Page 10: ...ilable at the date of publication of this manual are listed by name in the relevant sections TI Pos 19 Anleitungen Elektronik FU und Starter 1 Allgemeines Allgemeines_Inhalt_Erg nzung SK 5xxE 6 mod_14...

Page 11: ...ion on digital input 5 possible above size 5 an additional thermistor input is available as standard Table 2 Overview of SK 500E performance grading features Pos 21 Anleitungen Elektronik FU und Start...

Page 12: ...e harmonic voltage which is superimposed on the mains voltage Result Overload up to total failure of the X2 capacitors Impermissible charging of the link circuit with error messages up to exceeding of...

Page 13: ...lter circuits c Sliding contacts in power rails may cause brief power interruptions e g transport carriages in high bay storage warehouses Pos 23 Anleitungen Elektronik FU und Starter 1 Allgemeines Li...

Page 14: ...TR SK TU3 PAR SK CSX 0 please see chapter 3 2 Overview of technology units Technology units for installation in the control cabinet For commissioning parameterisation and control of the device Type SK...

Page 15: ...processes Type SK BR2 please see chapter 2 6 Brake resistor BR Bottom mounted brake resistor Refer to Chassis mounted brake resistor Type SK BR4 please see chapter 2 6 Brake resistor BR Choke Output c...

Page 16: ...combination filter Reduction of radiated interference EMC and compensation of cable capacitances Type SK NHD please see chapter 2 8 1 Mains filter SK NHD up to size 4 Installation versions Mounting ra...

Page 17: ...F converter Signal converter for conversion of the 0 10 V analog signals from a potentiometer into pulse signals for evaluation at the digital input of the frequency inverter SK 500E SK 535E Type conn...

Page 18: ...are operating materials intended for use in industrial high voltage systems and are operated at voltages that could lead to severe injuries or death if they are touched The device and its accessories...

Page 19: ...carry hazardous voltages for up to 5 minutes after being switched off at the mains Follow the 5 Safety Rules 1 Switch off the power 2 Secure against switching on 3 Check for no voltage 4 Earthing and...

Page 20: ...mains choke must be installed Failure to comply with this may cause damage to the device due to impermissible currents in the components Pos 29 8 Anleitungen Elektronik FU und Starter 1 Allgemeines S...

Page 21: ...1800 5 1 E171342 CSA Canada C22 2 No 274 13 E171342 RCM Australia F2018L00028 EN 61800 3 133520966 EAC Eurasia TR CU 004 2011 TR CU 020 2011 IEC 61800 5 1 IEC 61800 3 N RU DE 27 0272 1 20 Table 4 Stan...

Page 22: ...2 9 2 0 1 7 50 0 IE2 112 323 4 0 2 3 3 4 2 2 1 7 3 1 2 0 1 7 50 0 IE2 152 323 3 4 1 9 2 7 1 6 1 3 2 3 1 4 1 2 50 0 IE2 182 323 3 5 1 9 2 9 1 7 1 3 2 4 1 5 1 2 50 0 IE2 550 340 3 9 3 4 3 7 3 3 3 2 3 6...

Page 23: ...4 11 0 37 8 40 50 200 V 240 V 152 323 19 5 15 0 51 1 40 50 200 V 240 V 182 323 23 9 18 5 62 6 40 50 200 V 240 V 550 340 1 2 0 6 1 7 40 50 380 V 480 V 750 340 1 6 0 8 2 3 40 50 380 V 480 V 111 340 2 1...

Page 24: ...requency Inverters 24 BU 0505 EN 3021 Electrical data Pos 33 Anleitungen Elektronik FU und Starter 1 Allgemeines Zulassungen UL und cUL Zulassung_Teil 2_Erg nzung SK 1xxE SK 2xxE SK 5xxE 7 mod_1433943...

Page 25: ...1 Suitable For Use On A Circuit Capable Of Delivering Not More Than 10 000 rms Symmetrical Amperes 120 Volts Maximum When Protected by A Circuit Breaker Having An Interrupting Rating Not Less Than 10...

Page 26: ...aximum Suitable For Use On A Circuit Capable Of Delivering Not More Than 65000 rms Symmetrical Amperes 500 V Maximum When Protected By CC J T or R Class Fuses or When Protected By A Circuit Breaker Ha...

Page 27: ...en Protected by A Circuit Breaker Having An Interrupting Rating Not Less Than 65 000 rms Symmetrical Amperes 480 Volts Maximum The specific Circuit Breaker ratings are shown in 1 1 7 2 Pos 35 Anleitun...

Page 28: ...t A Class A1 C2 or B C1 Mains voltage x12 115 V x23 230 V x40 400 V x50 500 V Number of mains phases 1xx single phase 3xx 3 phase Digits before comma for power 0 0 xx 1 0x x0 2 0xx 0 Device rated powe...

Page 29: ...position The installation position is normally vertical It must be ensured that the cooling ribs on the rear of the frequency inverter are covered with a flat surface to provide good convection Warm a...

Page 30: ...5xxE 401 Size 3 241 98 181 275 5 5 SK 5xxE 551 340 to SK 5xxE 751 340 Size 4 286 98 181 320 5 5 SK 5xxE 551 323 to SK 5xxE 751 323 Size 5 327 162 224 357 93 5 5 SK 5xxE 112 340 to SK 5xxE 152 340 Siz...

Page 31: ...fe of the inverter this also causes less thermal load on the inside of the control cabinet A further advantage of the ColdPlate version is the reduced installation depth of the device and the fact tha...

Page 32: ...exagon socket M4x16 4x Dimensions Type External heat sink kit Heat sink dimensions mm Weight Heat sink Approx kg HK BK TK SK TH1 1 157 70 100 1 5 SK TH1 2 200 70 110 1 7 TK BK HK Das verkn pfte Bild k...

Page 33: ...outside at the point of installation Pos 43 Anleitungen Elektronik FU und Starter 2 Montage und Installation Zubeh r 2 4 Hutschienenmontageset SK DRK1 BU 0500 0 mod_1325861903944_388 docx 5802 255 1 D...

Page 34: ...n umbenannt oder gel scht Stellen Sie sicher dass die Verkn pfung auf die korrekte Datei und den korrekten Speicherort zeigt Das verkn pfte Bild kann nicht angezeigt werden M glicherweise wurde die Da...

Page 35: ...6 SK EMC 2 4 Part No 275999041 TI 275999041 57 mm SK 5xxE 152 323 SK 5xxE 182 323 SK 5xxE 302 340 SK 5xxE 372 340 Size 7 SK EMC 2 5 Part No 275999051 TI 275999051 57 mm SK 5xxE 452 340 SK 5xxE 902 340...

Page 36: ...chopper electronic switch pulses the intermediate circuit voltage switching wave approx 420 V 775 V 825 V DC according to the mains voltage 115 V 230 V 400 V 500 V to the brake resistor Here the exces...

Page 37: ...2 30 1500 C 278282150 30 1500 45 14 4 8 2 2 16 SK BR2 22 2200 C 278282220 22 2200 66 20 7 0 3 3 17 SK BR2 12 4000 C 278282400 12 4000 120 38 12 6 0 18 SK BR2 8 6000 C 278282600 8 6000 180 57 19 9 0 19...

Page 38: ...ontage und Installation Zubeh r Bremswiderstand SK 500E2 6 2 Abmessungen Unterbau BW SK BR4 BU 0500 0 mod_1325862485335_388 docx 5894 3 1 2 6 2 Dimensions of bottom mounted BR SK BR4 Resistor type Siz...

Page 39: ...323 401 323 SK BR4 35 400 275991140 TI014 275991140 SK 5xxE 301 340 401 340 SK BR4 100 400 275991240 TI014 275991240 SK 5xxE 551 340 751 340 SK BR4 60 600 275991260 TI014 275991260 Pos 48 Anleitungen...

Page 40: ...C SK BR2 3 17000 C 795 490 260 770 380 10 5 33 0 All dimensions in mm kg SK BR2 FI size 3 and above Schematic diagram model varies according to power B A E D C Table 9 Dimensions of chassis brake resi...

Page 41: ...stors Pos 50 Anleitungen Elektronik FU und Starter 2 Montage und Installation Zubeh r Bremswiderstand SK 500EKombination von Bremswiderst nden SK 5xxE 6 mod_1421419498283_388 docx 199459 3 1 2 6 5 Com...

Page 42: ...Pulse energy kWs 4 115 0 25 240 250 112 2 2 b 300 0 2 0 6 0 8 0 37 190 370 112 2 2 2 b 450 0 3 0 4 0 5 0 55 140 550 112 3 3 3 b 225 0 6 0 8 1 0 0 75 100 750 112 3 3 3 b 225 0 6 0 8 1 0 1 1 75 111 112...

Page 43: ...20 b 12 30 53 52 45 0 8 452 340 20 21 21 b 9 41 71 78 55 0 8 552 340 21 21 21 b 9 51 71 78 1 Type of connection of standard brake resistors from Table chapter 2 6 1 Here connected in parallel connect...

Page 44: ...re of the brake resistor is reached The output of the frequency inverter is blocked The motor runs down to a standstill 21 22 23 24 25 42 40 41 15V motor PTC 2 6 6 2 Monitoring with current measuremen...

Page 45: ...rmer power In addition the use of chokes is advisable for very hard networks or capacitative compensation systems Chokes also reduce the negative effects of asymmetrical mains voltages Above an invert...

Page 46: ...kg Table 12 Input choke data for SK CI1 1 240 V Inverter ID SK 500E Input choke 3 x 200 240 V L1 W1 D Detail Fastening Connection Weight Type Continuous current A Inductivity mH L2 B2 Assembly 0 25 0...

Page 47: ...60 160 3 x 0 18 352 140 268 240 105 M8 M8 27 0 90 kW SK CI1 480 280 C Part No 276993280 280 3 x 0 10 352 169 268 240 133 M10 M16 40 5 110 132 kW SK CI1 480 350 C Part No 276993350 350 3 x 0 08 352 169...

Page 48: ...240 V Inverter ID SK 5xxE Output choke 3 x 380 480 V L1 W1 D Detail Fastening Connection Weight Type Continuous current A Inductivity mH L2 B2 Assembly 0 55 1 5 kW SK CO1 460 4 C Part No 276996004 4 3...

Page 49: ...0 340 A 750 340 A SK NHD 480 3 F 278273003 TI 278273003 SK 5xxE 111 340 A 221 340 A SK NHD 480 6 F 278273006 TI 278273006 SK 5xxE 301 340 A 401 340 A SK NHD 480 10 F 278273010 TI 278273010 SK 5xxE 551...

Page 50: ...5 150 255 65 50 SK 5xxE 550 340 A SK 5xxE 221 340 A SK HLD 110 500 8 190 45 75 180 20 4 SK 5xxE 301 340 A SK 5xxE 551 340 A SK HLD 110 500 16 250 45 75 240 20 4 SK 5xxE 751 340 A SK HLD 110 500 30 270...

Page 51: ...korrekten Speicherort zeigt Das verkn pfte Bild kann nicht angezeigt werden M glicherweise wurde die Datei verschoben umbenannt oder gel scht Stellen Sie sicher dass die Verkn pfung auf die korrekte D...

Page 52: ...ekten Speicherort zeigt Das verkn pfte Bild kann nicht angezeigt werden M glicherweise wurde die Datei verschoben umbenannt oder gel scht Stellen Sie sicher dass die Verkn pfung auf die korrekte Datei...

Page 53: ...witch the frequency inverter is configured for TN TT network operation or for IT network operation also refer to Section 8 3 and 8 3 3 Frequency inverter Jumper A 1 Jumper B Comments Leakage current S...

Page 54: ...mal position Position 3 Size 5 7 Operation in IT network Position 0 reduced leakage current Top side of device Normal position Position 4 Jumper B motor output Size 1 4 Operation in IT network Positio...

Page 55: ...ve which is acting as a generator can be fed back to the drive which is acting as a motor The advantages are lower energy consumption and the sparing use of braking resistors In addition the energy ba...

Page 56: ...at the coupling is only made after readiness is reported Otherwise there is a danger that all the frequency inverters will be charged by a single one 4 Ensure that the coupling is disconnected as soon...

Page 57: ...nection and protection of the devices in the DC circuit must be carried out for cable protection and the maximum cross section of the device 2 The link circuits of the individual frequency inverters m...

Page 58: ...d the cable screening must also be connected to a large area of the metallic screening angle of the EMC Kit however at least to the electrically conducting mounting surface of the control cabinet 6 Ab...

Page 59: ...rter on an IT network is possible after modification of the integrated mains filter It is urgently recommended that the frequency inverter is only operated on a IT network if a braking resistor is con...

Page 60: ...is a common reference potential for analog and digital inputs Furthermore it must be taken into account that with SK 5x5E size 1 4 frequency inverters terminal 44 is used to feed in the control voltag...

Page 61: ...Terminals X4 11 12 14 16 17 VO 10V GND 0V AIN1 AIN2 AOUT1 Name Terminal Function factory setting Data Description wiring suggestion Parameter 11 10V Reference voltage 10V 5mA not short circuit resista...

Page 62: ...put S3 must be OFF Pos 82 Anleitungen Elektronik FU und Starter 2 Montage und Installation Elektrischer Anschluss SK 500E 2 10 5 Elektrischer Anschluss Steuerteil Klemmenblock X5 Digital In SK 54xE 2...

Page 63: ...h internal 15V 21 22 23 24 39 38 42 40 motor PTC 15V Connection with external 7 5 30V 21 22 23 24 39 38 42 40 motor PTC GND 0V 7 5 30V P420 01 22 Digital input 2 ON left P420 02 23 Digital input 3 par...

Page 64: ...put available Size 1 4 Potential isolated thermistor input which cannot be disabled for monitoring the motor temperature with a PTC 38 Thermistor input 41 5V supply voltage output available size 5 and...

Page 65: ...additional set point functions or positioning An encoder system with 10 30V supply voltage must be used in order to compensate for voltage drop in long cable connections Note Encoders with 5V supply a...

Page 66: ...Digital output 15V max 20 mA With inductive loads provide protection via free wheeling diode The digital input DIN7 can also be used as a digital output DOUT3 If P434 05 and P420 07 are parameterised...

Page 67: ...n a High signal for the DIN function P434 05 5 Output 3 DOUT1 no function For evaluation in a control system The scope of functions corresponds to that of the relay P434 P434 03 7 Output 4 DOUT2 no fu...

Page 68: ...0530 Fail safe input 89 Input Safe Pulse Block Relevance SK 540E SK 545E Terminal X8 86 87 88 89 VO_S 24V VO_S 0V VI_S 0V VI_S 24V Designation Terminal Function factory setting Data Description wiring...

Page 69: ...d for the evaluation of an absolute encoder Further details can be found in manual BU 0510 Recommendation Provide strain relief e g with EMC Kit P503 P509 2 3 CAN GND 4 No function 5 6 Cable shield 7...

Page 70: ...Baud rate 9600 38400Baud 5 6 Internal 5V supply voltage 5 V 20 optional Adapter cable RJ12 to SUB D9 for RS232 communication for direct connection to a PC with NORD CON Length 3 m Assignment of the SU...

Page 71: ...tion Elektrischer Anschluss SK 500E 2 10 5 Elektrischer Anschluss Steuerteil Klemmenblock X13 Motor PTC SK 54xE 2 mod_1355475568437_388 docx 52306 5 1 Terminal block X13 motor PTC only size 5 7 Releva...

Page 72: ...allation Elektrischer Anschluss SK 500E 2 10 5 Elektrischer Anschluss Steuerteil Klemmenblock X15 Motor PTC und 24V input SK 54xE 2 mod_1355475594559_388 docx 52330 5 1 Terminal block X15 motor PTC an...

Page 73: ...both tracks must jump between 0 8V and 0 8V If the voltage only jumps between 0 and 0 8V the relevant rack is faulty The position can no longer be reliably determined via the incremental encoder We r...

Page 74: ...er Inkrementalgeber Info Nullspur SK 54xE 6 mod_1417517741329_388 docx 191579 1 Information Zero track connection The zero track of an incremental encoder can only be evaluated if the universal encode...

Page 75: ...nterface to the external counter in the controller which then continues counting incrementally from this absolute value using the analog sine cosine signal During operation the counted position is con...

Page 76: ...ussmodul Allg 0 mod_1325866182423_388 docx 6170 2 1 2 11 RJ45 WAGO Connection module This adapter module can be used for the simple wiring of functions of the RJ45 connection 24V supply voltage CANope...

Page 77: ...tionen SK 5xxE 3 1 Modulare Baugruppen SK 5xxE 0 mod_1327492754652_388 docx 6283 2 1 3 1 Modular assemblies SK 5xxE By the use of various modules for display control and parameterisation the SK 5xxE c...

Page 78: ...o 5 inverters 4 line LCD display illuminated keyboard 275900100 BU 0040 SK TU3 POT PotentiometerBox Direct contol of the FI ON OFF R L 0 100 275900110 BU 0500 chapter 3 3 1 Table 29 Overview of Techno...

Page 79: ...les and Modbus RTU No optional modules are required for communication via USS or Modbus RTU The protocoles are integrated into all SK 5xxE series devices An interface is available via terminal X11 or...

Page 80: ...tungen Elektronik FU und Starter 3 Anzeige Bedienung und Optionen SK 5xxE 3 3 SimpleBox SK CSX 0 0 mod_1327493009711_388 docx 6329 255555 1 3 3 SimpleBox SK CSX 0 This option is used as a simple param...

Page 81: ...isplay When the frequency inverter is ready for operation any initial value P104 P113 for keyboard operation is indicated by a flashing display This frequency is immediately used on being enabled Duri...

Page 82: ...press or by switching off the mains voltage Menu structure with the SimpleBox P0 _ _ _ _ P1 P2 P4 P5 P6 P7 P001 P002 P100 P101 P114 P200 P201 P220 P400 P401 P483 Operating value display or operational...

Page 83: ...PotentiometerBox must be activated via parameter P549 PotentiometerBox Function using the setting 1 Setpoint frequency I O key START STOP green red To enable or block the output signal Potentiometer 0...

Page 84: ...kBaud P515 CAN bus address 32 34 36 38 40 42 44 46 To adopt the addresses the 24 V supply of the CAN bus must be completely switched off for approx 30 sec 4 Connect the parameterisation tool as usual...

Page 85: ...rs supplied by Getriebebau NORD are pre programmed with the default setting for standard applications with 4 pole IE1 three phase motors same voltage and power For use with motors with other powers or...

Page 86: ...manent Magnet Synchronous Motor however various constraints must be complied with In principle all these methods are flux oriented control methods Pos 115 3 Anleitungen Elektronik FU und Starter 4 Inb...

Page 87: ...ssible with the open loop method i e in operation without an encoder Here the speed and position detection are determined by observation of measurements and setting values Precise setting of the curre...

Page 88: ...und in the Drive optimisation guideline AG 0101 Please contact our Technical Support 1 Carry out the motor connection as usual note Y Connect the encoder if present 2 Connect the mains supply 3 Carry...

Page 89: ...a P 4 Control terminals P 5 Additional parameter P 7 Information As standard the actual output frequency is displayed P102 Acceleration time 0 320s Motor data See 4 1 Default Settings P400 Analog inpu...

Page 90: ..._ _ P1 Basic parameter P 2 Motor data P 4 Control terminals P 5 Additional parameter P 7 Information P201 Nominal motor frequency 10 400Hz P406 Mode analog input 2 P406 1 0 10V P207 Motor switching S...

Page 91: ...ER key is confirmed the value is saved in P113 The next time the device is started the value will be added or subtracted immediately As soon as the inverter is enabled the ControlBox switches to the o...

Page 92: ...control SK 520E or higher P3 Settings for the control parameters current controller speed controller etc with speed feedback Control terminals P4 Analog input and output scaling specification of digi...

Page 93: ...kann nicht angezeigt werden M glicherweise wurde die Datei verschoben umbenannt oder gel scht Stellen Sie sicher dass die Verkn pfung auf die korrekte Datei und den korrekten Speicherort zeigt Das ve...

Page 94: ...ernating voltage present at the device output 6 Link voltage V DC The Link voltage Vdc is the FI internal DC voltage Amongst other things this depends on the level of the mains voltage 7 cos Phi Curre...

Page 95: ...ting Setting value Description Note Supervisor Parameter set Pos 128 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P100 P199 Parameter P100 Parametersatz 0 mod_13275747578...

Page 96: ...requency to 0 Hz P105 If an actual setpoint 100 is being used the deceleration time reduces accordingly The braking time can be extended by certain circumstances e g by the selected Switch off mode P1...

Page 97: ...4 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P100 P199 Parameter P106 Rampenverrundungen 0 mod_1327575116954_388 docx 7619 1 P106 Ramp smoothing Ramp smoothing P 0 100...

Page 98: ...Parameter P107 Einfallzeit Bremse_Info Ansteuerung durch FU SK 5xxE 4 mod_1396520689350_388 docx 123926 1 Information Brake control For the control of electromagnetic braking especially for lifting e...

Page 99: ...not being driven at the maximum output frequency P105 This results in an approximately similar braking distance for different frequencies NOTE This function cannot be used as a positioning function Th...

Page 100: ...0 mod_1327587790393_388 docx 7746 1 P111 P factor torque limit P factor torque limit S P 25 400 100 Directly affects the behaviour of the drive at torque limit The basic setting of 100 is sufficient...

Page 101: ...inverter to switch off with an overcurrent report This release time can be taken into account in parameter P114 Brake control During the adjustable ventilation time the FI supplies the set absolute mi...

Page 102: ...0 73 0 The factory settings for the motor data can be changed with this parameter The factory setting in parameters P201 P209 is a 4 pole IE1 DS standard motor with the nominal FI power setting By se...

Page 103: ...100T2 4 20 1 1 kW 400V 50 22 0 kW 400V 80 22 0 kW 230V 110 3 00kW 400V 90T3 4 21 1 5 PS 460V 51 30 0 PS 460V 81 30 0 PS 230V 111 4 00kW 230V 100T5 4 22 1 5 kW 230V 52 30 0 kW 400V 82 30 0 kW 230V 112...

Page 104: ...ee information The motor cos is a decisive parameter for the current vector control Information Default setting The default setting is dependent upon the FI nominal power and the setting in P200 Pos 1...

Page 105: ...flistung P000 P200 P299 Parameter P212 Schlupfkompensation 0 mod_1327590275572_388 docx 8140 1 P212 Slip compensation Slip compensation S P 0 150 100 The slip compensation increases the output frequen...

Page 106: ...ung P000 P200 P299 Parameter P217 Schwingungsd mpfung 0 mod_1327590520707_388 docx 8255 1 P217 Oscillation damping Oscillation damping S P 0 400 10 With the oscillation damping idling current harmonic...

Page 107: ...pplications where a more rapid build up of the torque is required as otherwise there would be overcurrent switch offs or inversion of the motor on sudden changes of load because the missing field woul...

Page 108: ...ower of the FI A maximum motor cable length of 20m must be adhered to for reliable identification Before starting motor identification the motor data must be preset in accordance with the rating plate...

Page 109: ...ik FU und Starter 5 Parameter Parameterauflistung P000 P200 P299 Parameter P245 Pendeld mpfung PMSM VFC 6 mod_1417605252683_388 docx 191743 1 P245 Osc damping PMSM VFC Oscillation damping PMSM VFC S P...

Page 110: ...ng this can be compensated for by selecting the corresponding negative pulse numbers 8 16 0 500 pulses 1 512 pulses 2 1000 pulses 3 1024 pulses 4 2000 pulses 5 2048 pulses 6 4096 pulses 7 5000 pulses...

Page 111: ...lead to high frequency vibrations at low speeds On the other hand excessively high values in P316 generally produce low frequency vibrations across the whole speed range If the value Zero is entered...

Page 112: ...000 P300 P399 Parameter P325 Funktion Drehgeber 0 mod_1327677283553_388 docx 8819 1 P325 Rotary encoder function Rotary encoder function 0 4 0 The actual speed list value supplied by an incremental en...

Page 113: ...arting position of the rotor can only be used if there is no counter torque from the machine e g flywheel drive at frequency zero If this condition is fulfilled this method of determining the position...

Page 114: ...Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P300 P399Parameter P330 Regelverfahren PMSM _ Hinweis IG mit 0 Spur SK 54xE 6 mod_1417690875847_388 docx 192085 1 NOTE If the...

Page 115: ...zero pulse encoder Synchronisation of zero track of the incremental encoder 0 3 0 The zero track of an incremental encoder can only be evaluated if the universal encoder interface X14 is not occupied...

Page 116: ...he relevant array of parameter P400 The possible analog functions can be found in the following table Assignment of digital functions to the analog inputs 1 and 2 of the motor controller is carried ou...

Page 117: ...ocess controller 46 Setpoint Torque Process controller Process controller torque setpoint 48 Motor temperature Motor temperature measurement with KTY 84 details in Section 0 53 d correction F process...

Page 118: ...change of the direction of rotation 1 0 10V If a setpoint smaller than the programmed adjustment 0 P402 is present this can cause a change in direction rotation This allows rotation direction reversal...

Page 119: ...10V with shut down on Error 1 If the value of the 0 adjustment in P402 is undershot the error message 12 8 Undershoot of Analogue In Min is activated If the value of the 100 adjustment in P402 is und...

Page 120: ...Starter 5 Parameter Parameterauflistung P000 P400 P499 Parameter P403 Abgleich Analogeingang 100 SK 1x0E SK 54xE 0 mod_1327681136791_388 docx 9257 1 P403 01 06 Adjustment 100 Analog input adjustment 1...

Page 121: ...0 mod_1327681617600_388 docx 9464 1 P410 Min freq a in 1 2 Minimum frequency a in 1 2 auxiliary setpoint value P 400 0 400 0 Hz 0 0 The minimum frequency that can act on the setpoint via the auxiliary...

Page 122: ...9_388 docx 9582 1 P415 PID control D comp D component of PID controller S P 0 400 0 ms 1 0 This parameter is only effective when the function PID actual frequency is selected If there is a rule deviat...

Page 123: ...s Pos 245 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P400 P499 Parameter P418 Funktion Analogausgang_Erg nzung_01 SK 54xE 11 mod_1460120425642_388 docx 316810 1 NOTE Us...

Page 124: ...output is controlled via a bus system The process data is directly transferred P546 P547 P548 20 33 Freq of setpt source Frequency of setpoint source above SW version 1 6 60 Reserved above SK540E BU...

Page 125: ...unctions are available Of these inputs analog inputs 1 and 2 of the frequency inverter do not comply with EN61131 2 Type 1 digital inputs 01 Digital input 1 DIN1 Enable right default terminal 21 02 Di...

Page 126: ...quency according to the programmed fast stop time from P426 Low 12 Error acknowledgement 2 Error acknowledgement with an external signal If this function is not programmed an fault can also be acknowl...

Page 127: ...error detection are deactivated NOTICE There is no overload monitoring e g lifting gear High 71 Motor pot F and Save SW 1 6 and above Motor potentiometer function frequency with automatic saving With...

Page 128: ...tual setpoint 100 is being used the emergency stop time is reduced correspondingly Pos 263 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P400 P499 Parameter P427 Schnellha...

Page 129: ...0 P400 P499 Parameter P433 Festfrequenz 5 0 mod_1328001008409_388 docx 10181 1 P433 Fixed frequency 5 Fixed frequency 5 P 400 0 400 0 Hz 0 0 For a description of the function of the parameter see P429...

Page 130: ...I Low 09 Overcurrent warning At least 130 of the nominal FI current was supplied for 30 seconds Low 10 Motor overtemperature warning Motor overtemperature warning The motor temperature is evaluated vi...

Page 131: ...nce between switch on and switch off point to prevent oscillation of the output signal 01 Output 1 MFR1 relay output 1 02 Output 2 MFR2 relay output 2 03 Output 3 DOUT1 digital output 1 04 Output 4 DO...

Page 132: ...depending on installation and wiring it can be compensated for by selecting the corresponding negative pulse numbers Pos 290 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000...

Page 133: ...d of parameter P300 is set to ON In this case the TTL encoder is used for speed control In this way e g 2 rotary encoders a TTL encoder via P300 and an HTL encoder via P468 can be alternately activate...

Page 134: ...via control terminals Pos 298 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P400 P499 Parameter P481 Funktion Bus I O Out Bits SK 5xxE 0 mod_1328002703095_388 docx 10802...

Page 135: ...1 to the Motor overtemperature function P481 07 Function 12 2 Specify the reaction Set Flag 1 to the function Setpoint 1 On Off P480 09 Function 19 It should be noted that depending on the function w...

Page 136: ...Value analog input 1 18 Value analog input 2 19 Frequency master value 20 Setpoint freq after ramp 21 Actual freq w o slip 22 Speed encoder 23 Actual freq with slip SW V2 0 and above 24 Act freq with...

Page 137: ...tput which occur before enabling may possibly not be detected correctly Pos 309 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Parameter P505 Absolute Minimalfreq...

Page 138: ...ol word 4 Profibus control word 5 InterBus control word 6 CANopen control word 7 DeviceNet control word 8 Ethernet TU control word 9 CAN Broadcast 10 CANopen Broadcast Keyboard control ControlBox Para...

Page 139: ...d Pos 319 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Parameter P513 Telegrammausfallzeit_Erg nzung_01 SK 1x0E 2xxE SK 5xxE 10 mod_1456911365722_388 docx 31127...

Page 140: ...inactive Pos 323 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Parameter P517 Ausblendbereich 1 0 mod_1328092662665_388 docx 11272 1 P517 Skip freq area 1 Skip f...

Page 141: ...incremental encoder is used Pos 329 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Parameter P520 Fangschaltung_Erg nzung_03 SK 5xxE 11 mod_1460119668325_388 doc...

Page 142: ...that the function is switched off No monitoring is performed This is also the basic setting for the FI Pos 335 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Par...

Page 143: ...toring is inactive during acceleration phases Pos 338 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Parameter P525 P529 Last berwachung 0 mod_1328093390150_388 d...

Page 144: ...ies do not need to be sorted according to their magnitude in the elements 0 1 and 2 as the frequency inverter does this automatically Pos 339 Anleitungen Elektronik FU und Starter 5 Parameter Paramete...

Page 145: ...a sufficiently high overload capacity Switch off class 5 60s at 1 5x IN Switch off class 10 120s at 1 5x IN Switch off class 20 240s at 1 5x IN IN at 0Hz P535 IN at 0Hz P535 IN at 0Hz P535 100 1 100 9...

Page 146: ...to the original value Pos 345 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P599 Parameter P538 Netzspannungs berwachung 0 mod_1328093765682_388 docx 11686 1 P538 Che...

Page 147: ...restriction of the direction of rotation 1 Dir key disabled the direction key of the ControlBox SK TU3 CTR is disabled 2 CW only only clockwise direction is possible The selection of the incorrect ro...

Page 148: ...mal code is entered directly when the ControlBox is used ParameterBox Each individual output can be separately called up in plain text and activated NOTE The setting is not saved in the EEPROM and is...

Page 149: ...nt frequency master value after ramp 5 Digital IO status 4 21 Act freq without slip master value Actual frequency without slip master value 6 7 Reserved 22 Speed encoder only possible with SK 520E and...

Page 150: ...uency limited 48 Motor temperature SK 540E and above 9 Actual PID frequency monitored 49 reserved from SK 540E and above BU 0510 10 Torque servo mode P300 53 d correction F process SK 540E and above 1...

Page 151: ...eable NOTE If parameterisation from old FI s need to be loaded into FIs with new software P707 then the ControlBox must previously be written to by the new FI P550 1 The dataset to be copied from the...

Page 152: ...Parameter P553 The description of the PLC relevant parameter above P3550 can be found in the manual BU 0550 Pos 368 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P500 P59...

Page 153: ...ontinuous power nominal power of the resistor to display the actual utilisation in P737 For a correctly calculated value the correct value must be entered into P556 and P557 0 00 Monitoring disabled P...

Page 154: ...tus 0 0 25 4 Display of current messages for the present operating status of the frequency inverter such as faults warnings or the reason why switch on is disabled please see chapter 6 Operating statu...

Page 155: ...P000 P700 P799 Parameter P705 Zwischenkreisspannung letzte St rung 1 5 0 mod_1328170720639_388 docx 12433 1 P705 01 05 Last link circuit error Last link circuit error 1 5 S 0 1000 V DC This parameter...

Page 156: ...e 01 Analog input 1 analog input 1 integrated into the FI 02 Analog input 2 analog input 2 integrated into the FI 03 External analog input 1 External analog input 1 Analog input 1 of the first IO exte...

Page 157: ...eterauflistung P000 P700 P799 Parameter P715 Freigabedauer 0 mod_1328172731474_388 docx 12686 1 P715 Running time Enablement time 0 00 ___ h This parameter shows the time for which the FI was enabled...

Page 158: ...8 docx 12916 1 P725 Current Cos phi Actual cosj 0 00 1 00 Displays the actual calculated cos of the drive Pos 404 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P700 P799 P...

Page 159: ...P799 Parameter P735 Drehzahl Drehgeber SK 54xE 0 mod_1328173990708_388 docx 13169 1 P735 01 03 Speed encoder Speed encoder S 9999 9999 rpm Displays the actual rotation speed supplied by the increment...

Page 160: ...x 13336 1 P740 01 23 Process Data Bus In Process data Bus In S 0000 FFFF hex This parameter informs about the actual control word and the setpoints that are transferred via the bus systems For display...

Page 161: ...021821_388 docx 13405 1 P742 Data base version Database version S 0 9999 Displays the internal database version of the FI Pos 425 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung...

Page 162: ...Bit 5 System bus Additional module 2 online I O module e g SK xU4 IOE Bit 6 Protocol of the CAN module is 0 CAN or 1 CANopen Bit 7 free Bit 8 Bootsup Message sent Bit 9 CANopen NMT State Bit 10 CANop...

Page 163: ...Stat Timeout Time out statistics S 0 9999 Number of Time out errors during the operating period P714 Pos 438 Anleitungen Elektronik FU und Starter 5 Parameter Parameterauflistung P000 P700 P799 Param...

Page 164: ...wledge Switching the mains off and on again By an appropriately programmed digital input P420 By switching off the enable on the device if no digital input is programmed for acknowledgement By Bus ack...

Page 165: ...mod_1361803456862_388 docx 59874 5 1 Error messages Display in the SimpleBox ControlBox Fault Text in the ParameterBox Cause Remedy Group Details in P700 01 P701 Pos 450 Anleitungen Elektronik FU und...

Page 166: ...nt P537 pulse current switch off was reached 3x within 50 ms only possible if P112 and P536 are disabled FI is overloaded Drive sluggish insufficiently sized Ramps P102 P103 too steep Increase ramp ti...

Page 167: ...6 EEPROM copy used 8 7 EEPROM copy not the same 8 8 EEPROM is empty 8 9 EEPROM Ctrlbox too small The EEPROM of the ControlBox is too small to completely save the data set for the frequency inverter P...

Page 168: ...interference by laying control and power cables separately Earth the devices and shields well Pos 462 Anleitungen Elektronik FU und Starter 6 Meldungen zum Betriebszustand St rmeldungen Auflistung Fe...

Page 169: ...docx 46826 1 E016 16 0 Motor phase error A motor phase is not connected Check P539 Check motor connection 16 1 Magnetisation current monitoring Magnetisation current monitoring Required exciting curre...

Page 170: ...uflistung Fehler E024 reserviert PLC SK 180E SK 5xxE 6 mod_1423644411761_388 docx 201828 1 E024 Reserved Error message for PLC see supplementary instructions BU 0550 Pos 474 Anleitungen Elektronik FU...

Page 171: ...Warning pulse switch off is active The limit for activation of pulse switch off P537 has been reached only possible if P112 and P536 are switched off FI is overloaded Drive sluggish insufficiently siz...

Page 172: ...t block P420 31 73 or Enable left block P420 32 74 The frequency inverter switches to Ready for switching on status 0 9 Left direction blocked Pos 485 Anleitungen Elektronik FU und Starter 6 Meldungen...

Page 173: ...1 Operation IEC 60721 3 3 Vibration 3M4 Climate 3K3 Waiting period between 2 x Mains on 60 s for all devices in normal operating cycle Protective measures against Overtemperature of the frequency inve...

Page 174: ...with SK 520E 530E 2x DOUT 15 V 20 mA or Additionally with SK 535E 545E 2x DOUT 18 30 V depending on VI 20 mA or 2x DOUT 18 30 V 200 mA Size 5 and above Output 3 4 DOUT1 2 Analogue output 0 10 V scala...

Page 175: ...50 0 IE2 112 323 4 0 2 3 3 4 2 2 1 7 3 1 2 0 1 7 50 0 IE2 152 323 3 4 1 9 2 7 1 6 1 3 2 3 1 4 1 2 50 0 IE2 182 323 3 5 1 9 2 9 1 7 1 3 2 4 1 5 1 2 50 0 IE2 550 340 3 9 3 4 3 7 3 3 3 2 3 6 3 2 3 2 8 5...

Page 176: ...240 V 112 323 14 4 11 0 37 8 40 50 200 V 240 V 152 323 19 5 15 0 51 1 40 50 200 V 240 V 182 323 23 9 18 5 62 6 40 50 200 V 240 V 550 340 1 2 0 6 1 7 40 50 380 V 480 V 750 340 1 6 0 8 2 3 40 50 380 V...

Page 177: ...10 47 63 Hz Input current rms 8 9 A 11 0 A 13 1 A 20 1 A 23 5 A FLA 8 9 A 10 8 A 13 1 A 20 1 A 23 5 A Output voltage 230 V 3 AC 0 2x mains voltage Typical output rms 1 7 A 2 2 A 3 0 A 4 0 A 5 3 A FLA...

Page 178: ...A FLA 3 7 2 4 A 4 8 3 1 A 6 5 4 2 A 8 7 5 6 A Output voltage 230 V 3 AC 0 Mains voltage Typical output rms 1 7 A 2 2 A 3 0 A 4 0 A FLA 1 7 A 2 2 A 2 9 A 3 9 A Min brake resistor Accessories 240 190 14...

Page 179: ...2 5 A 16 0 A FLA 5 4 A 6 9 A 8 8 9 3 A 12 3 A 15 7 A Min brake resistor Accessories 75 62 46 35 26 Pulse frequency range 3 16 kHz Factory setting 6 kHz Ambient temperature S1 40 C 40 C 40 C 40 C 40 C...

Page 180: ...g 6 kHz Ambient temperature S1 40 C 40 C 40 C 40 C 40 C S3 80 10 min S3 70 10 min Type of ventilation Fan cooling temperature controlled switching thresholds 1 ON 57 C OFF 47 C Weight Approx kg 8 10 3...

Page 181: ...180 130 Pulse frequency range 3 16 kHz Factory setting 6 kHz Ambient temperature S1 40 C 40 C 40 C 40 C 40 C S3 80 10 min 50 C 50 C 50 C 50 C 50 C S3 70 10 min 50 C 50 C 50 C 50 C 50 C Type of ventil...

Page 182: ...es 91 74 60 44 Pulse frequency range 3 16 kHz Factory setting 6 kHz Ambient temperature S1 40 C 40 C 40 C 40 C S3 80 10 min 50 C 50 C S3 70 10 min 50 C 50 C 50 C 50 C Type of ventilation Fan cooling t...

Page 183: ...sories 29 23 18 15 Pulse frequency range 3 16 kHz Factory setting 6 kHz Ambient temperature S1 40 C 40 C 40 C 40 C S3 80 10 min S3 70 10 min Type of ventilation Fan cooling temperature controlled swit...

Page 184: ...setting 6 kHz 4 kHz Ambient temperature S1 40 C 40 C 40 C 40 C 40 C S3 80 10 min S3 70 10 min Type of ventilation Fan cooling temperature controlled switching thresholds 1 ON 57 C OFF 47 C ON 56 C OF...

Page 185: ...trolled switching thresholds 1 ON 56 C OFF 52 C Fan speed control Between 52 C and approx 70 C 2 there is no speed control 3 Weight Approx kg 30 46 49 52 General fuses AC recommended slow blowing 315...

Page 186: ...ing area m 1 SK 5xxE 250 112 O CP 12 0 2 33 0 12 SK 5xxE 250 112 O CP 16 5 1 70 0 17 SK 5xxE 550 112 O CP 23 9 1 17 0 24 SK 5xxE 750 112 O CP 35 7 0 78 0 36 SK 5xxE 111 112 O CP 53 5 0 39 0 54 1 Requi...

Page 187: ...he SK 5xxE 221 323 A CP is only available in size 3 for S1 operation Table 35 Technical data ColdPlate 230V devices three phase operation 3 400V devices Pv module W Max Rth K W Cooling area m 1 SK 5xx...

Page 188: ...ace The ColdPlate and the mounting plate must lie flat against each other max air gap 0 05 mm The contact area of the mounting plate must be at least as large as the area of the ColdPlate A suitable h...

Page 189: ...ut 2 Bus setpoint 1 2 3 Main setpoint sources Analog input 1 Analog input 2 Bus setpoint 3 Bus setpoint 2 P411 P410 Scaling Fixed frequency 1 5 P429 P433 P509 P400 P405 P549 P547 Interface Auxiliary s...

Page 190: ...setpoint function fmax mmax Torque limit Maximum frequency SETPOINT FREQUENCY Current limit Imax PID controller fs t Frequency ramp P102 P103 P106 P107 P108 P114 Limitation Frequency setpoint Fig 14 S...

Page 191: ...er 9 Zusatzinformationen BU 0500 BU 0200 Prozessregler Anwendungsbeispiel Prozessregler SK 1x0E SK 2xxE SK 5xxE 0 mod_1328186990203_388 docx 14190 3 1 8 2 1 Process controller application example M M...

Page 192: ...input 4 frequency addition P411 setpoint frequency Hz Set frequency with 10 V at analog input 1 Example 50 Hz P412 Process controller setpoint CR middle position Default setting 5V adjust if necessary...

Page 193: ...This method only applies to radio transmitter equipment The devices only have an intrinsic function when they are connected to other equipment e g to a motor The base units cannot therefore carry the...

Page 194: ...lektronik FU und Starter 8 9 Zusatzinformationen BU 0500 BU 0200 EMV _EMV des Ger tes SK 1xxE SK 2xxE SK 5xxE 5 mod_1396881798744_388 docx 124694 3 1 8 3 3 EMC of device NOTICE EMC The drive system ca...

Page 195: ...r 8 9 Zusatzinformationen BU 0500 BU 0200 EMV _EMV des Ger tes _ Grenzwertklassen 2 mod_1347443407776_388 docx 46088 1 EMC overview of standards that are used in accordance with EN 61800 3 as checking...

Page 196: ...Brake resistance option 3 shield angle 4 Functional earthing PE Protective earth Figure 16 Wiring recommendation Pos 501 9 Anleitungen Elektronik FU und Starter 8 9 Zusatzinformationen BU 0500 BU 020...

Page 197: ...505 EN 3021 197 8 3 4 EC Declaration of Conformity Pos 502 Anleitungen Elektronik FU und Starter 9 Zusatzinformationen BU 0500 BU 0200 Reduzierte Ausgangsleistung Reduzierte Ausgangsleistung 0 mod_132...

Page 198: ...ive heat dissipation in the frequency inverter For 400V devices the reduction begins at a pulse frequency above 6kHz size 8 above 4kHz For 230V devices the reduction begins at a pulse frequency above...

Page 199: ...fgrund der Ausgangsfrequenz 0 mod_1328188934696_388 docx 14351 3 1 8 4 3 Reduced overcurrent due to output frequency To protect the power unit at low output frequencies 4 5Hz a monitoring system is pr...

Page 200: ...41 Overcurrent relative to pulse and output frequency Pos 506 Anleitungen Elektronik FU und Starter 9 Zusatzinformationen BU 0500 BU 0200 Reduzierte Ausgangsleistung _Reduzierter Ausgangsstrom aufgrun...

Page 201: ...rs have a low power consumption and are therefore highly efficient In addition with the aid of Automatic flux optimisation Parameter P219 the inverter provides a possibility for increasing the overall...

Page 202: ...P105 UAIN V 10V 100 16384 INT 4000hex 16384dez C000hex 16385dez 4000hex fsetpoint Hz P105 P105 Torque current limit 2 0 10V 10V 100 P112 UAIN V 10V 0 100 16384 INT 4000hex 16384dez 4000hex I A P112 P...

Page 203: ...slip Actual frequency at motor X X 19 Setpoint frequency master value Setpoint frequency from setpoint source Master value free from enable correction X X 20 Setpoint frequency n R master value Setpo...

Page 204: ...fore normal connection to the mains Long term storage for 1 3 years 30 min with 25 mains voltage 30 min with 50 mains voltage 30 min with 75 mains voltage 30 min with 100 mains voltage Long term stora...

Page 205: ...turn Please note the reason for sending in the component device and specify a contact for any queries that we might have You can obtain a return note from our web site Link or from our technical suppo...

Page 206: ...ermanent Magnet Synchronous motor permanently excited synchronous motor DO DOUT Digital output S Supervisor Parameter P003 I O Input Output SH Safe stop function EEPROM Non volatile memory SW Software...

Page 207: ...nctions 116 123 Analog input mode P401 118 Analog input voltage P709 156 Analog output offset P417 123 Analog output voltage P710 157 Analogue input filter P404 121 Analogue inputs 116 123 Apparent po...

Page 208: ...me P103 96 delay on off switch P475 133 Delivery condition 89 Digital functions 117 124 126 Digital input function P400 116 Digital inputs P420 125 Digital output Hyst P436 131 Scaling of P435 131 Dig...

Page 209: ...y array P465 133 Flux delay P558 153 Flux feedback fact PMSM P333 114 Flying start P520 141 Flying start offset P522 141 Flying start resolution P521 141 Function 2 encoder P461 132 Function analog ou...

Page 210: ...ay P528 142 Load monitoring mode P529 143 Long term storage 173 Low Voltage Directive 2 M Mains choke 45 46 Mains voltage monitoring 146 Mains voltage monitoring P538 146 Maintenance 204 Mass Inertia...

Page 211: ...e limit P111 100 P set last error P706 155 Parameter identification 108 Parameter identification P220 108 Parameter set P100 95 Parameter set P731 159 Parameter saving mode P560 154 Parameterisation 9...

Page 212: ...8 Setpoints 202 SimpleBox 80 SIN COS encoder 74 Sine Cosine encoder 74 Sine encoder 74 SK BR2 SK BR4 37 SK CI1 46 SK CO1 47 SK CSX 0 80 SK DCL 45 SK EMC 2 35 SK TU3 POT 83 Skip frequency 1 P516 140 Sk...

Page 213: ...ture Motor 90 Time boost precontrol P216 106 Torque P729 158 Torque current controller I P313 111 Torque current controller P P312 111 Torque current limit P112 100 Torque disconn limit P534 144 Torqu...

Page 214: ...SK 54xE Users Manual for Frequency Inverters 214 BU 0505 EN 3021...