background image

DATA LOGGER 
WITH WWW SERVER
SM61 TYPE

USER’S MANUAL
QUICK START

1. ZESTAW REGULATORA

1. data logger SM61........................... 1 pc
2. quick start manual...........................1 pc
3. guarantee card............................... 1 pc
4. CD with the software and
    user’s manual..................................1 pc

In the safety service scope, the meter meets to requirements of the
EN 61010-1 standard.

Observations concerning the operational safety:

·  All  operations  concerning  transport,  installation  and  commissioning 
as  well  as  maintenance  must  be  carried  out  by  qualified,  skilled  per-
sonnel, and national regulations for the prevention of accidents must be 
observed. 

1. DATA LOGGER SET

2. OPERATIONAL SAFETY

3.  DIMENSIONS AND FIXING WAY

 

Power  and  external  inputs  should  be  connect  according  to 

the pic. 2 and table 1  in which is described destiny of the individual 
terminals in SM61 data logger.

4. CONNECTION DIAGRAMS

Pic.1. Dimensions and fixing way

Termi-

nal

Description

1

Input line (positive terminal 
input 1) or
line of alarm 1

2

Input line (negative terminal 
input 1) or
line of alarm 1 

3

Input line (positive terminal 
input 2) or
line of alarm 2

4

Input line (negative terminal 
input 2) or
line of alarm 2

5

GND line

6

Line B (RS-485)

7

Line A (RS-485)

8

Line 5 V d.c.

9

Line + supply

10

Line - supply

11

not used

12

Output TxD  (RS-232)

13

Input RxD  (RS-232)

14

Line GND

15

Line A  (RS-485)

16

Line B  (RS-485)

Pic.2. Electrical connections of 

SM61 data logger. 

  

The SM61 data logger is fixing on rail bracket 35 mm. Dimen-

sions and fixing way are shown at pic. 1.

7. ROZPOCZÊCIE PRACY

 

After right - click on the selected device from the list a new 

menu shown in pic. 4.

Pic.4. This menu is shown after right-click.

 

Selecting option 

Change IP

 brings up a window allowing  the 

configuration of the  following settings as in pic. 5.

IP address

Subnet mask

Gateway

on/off DHCP

Restart module after set 

configuration

FTP server data port

FTP server command port

Web server port

Modbus TCP port

Pic.5. Change of settings IP

Table 1

Data logger SM61 has four communication interfaces::
    1. PORT 1 - serial interface:
        ·    purpose - communication with Master device,
        ·    bus - RS-232, RS-485,
        ·    terminals - 14, 15, 16 (RS-485) and 12, 13, 14 (RS-232),
        ·    galvanically isolated from  rest of the system,
       ·    maximum length of bus depends on the speed of transmission
          (for  high speeds of up to severals tens of meters,  for small,
              eg.  9600 bit/s to about 1.2 km).
 
     2. PORT 2 - serial interface:
        ·    purpose - communication with Slave device,
        ·    bus - RS-485,
        ·    terminals - 5, 6, 7, 8,
        ·    galvanically isolated from rest of the system,
       ·    maximum length of bus depends on the speed of transmission
          (for  high speeds of up to severals tens of meters,  for small,
              eg.  9600 bit/s to  about 1.2 km).

     3. USB - serial interface:
        ·    protocol of data exchange: Modbus RTU,
        ·    purpose - device configuration,
        ·    connection - mini USB.

     4. LAN:
        ·    protocol of data exchange: Modbus TCP,
        ·    purpose - device configuration,
        ·    allow to connect device to Ethernet network,
        ·    connection - RJ-45.

 

The  category  of  twisted  pair  according  to  European  norm

EN 50171 minimal: class D (category 5) – for fast local network, includes 
applications which uses  the frequency band up to 100 MHz. Descrip-
tion of the connection is shown at table 2.
·    EIA/TIA  568A  for  both  connectors  in  simple  connections  SM61
      to a hub or switch,
·    EIA/TIA  568A  for  first  connector  and  EIA/TIA  568B  for  second
      connector in connection   with crossover (connection SM61 to a computer).

 

After connection device to Ethernet network it is able to confi-

gure settings using HTTP protocol or Modbus TCP.  
 

The data logger set include CD with USB driver and software 

SM61Config, which is used to find devices in Ethernet network and con-
figure them by Modbus RTU (USB) or Modbus TCP (Ethernet) protocol.

5. DATA LOGGER CONFIGURATION

Notice:

 

To get full resistance of data logger on electromagnetic inter-

ference one should follow these rules:
·    do  not  supply    the  data  logger    from  the  network  which  is  near 
      pulse  noise  generators  (inverters)  and  do  not  use  common  with 
      them grounding circuits,
·    use network filters,
·  all  shields    should  be  grounded  or  connected  to  the
    protective  unit,  one  sided  the  nearest  to  the  data  logger,
·    

use the general rule, the wires leading different signals should be carried 

      out  in  the  greatest  distance  from  each  other  (no  less  then  30  cm),

      the intersection of these beams is performed  at 90

o

.

5.1. STARTING TO WORK

 

The  device  need  to  set  basic  information  about  IP  protocol

at the first start (IP address, subnet mask, gateway). Needed information 
should be given from local network administrator in which device will be 
joined. Software SM61Config let the user configure settings using USB 
protocol or using Ethernet network.
 

In the case of first configuration using Ethernet network please 

open the SM61Config application and show the list of found data log-
gers by choosing 

List of SM61 devices

 from the left menu as it’s shown 

in pic. 3. 

 

After making changes please left - click on 

OK

 to close a win-

dow and save changes to the device. 

 

Configuration  can  be  done  also  by  USB.    To  connect  with 

the  device  by  UBS,  please  select  from  the  software  menu 

Options

and choose type of communication as it’s shown at pic. 6.

 Pic.6. Selection of the type of communication.

Then  please  go  to  the  configuration  by  selection  the  option  from  left 
menu (see fig. 3). Selecting the option allow change the configuration. 
After changing the configuration one should save it and restart the devi-
ce to set the new configuration.

 

Language is changing by selection 

Option -> Language

 and 

then  selection  language  from  available  positions.  After  that  close  the 
application and open again.

Notice:

After changing the parameters the device should be reset.

Pic.3. Left menu of SM61Config

Shown the list of found modules

Configuration of Ethernet settings

Configuration of serial port settings

Note: 

The full version of the user’s manual is inserted in the 

www.lumel.com.pl/en/  web site.

·  Before switching the data logger on, one must check the correctness 
    of connections of the network.
·  Before the remove of the casing one should switch off data logger 
    power and measurement circuits.
·  The device is destined to be installed and used in industrial electro
    magnetic environment conditions.
·  A switch or a circuit - breaker should be located near the device, easy 
   accessible by the operator and suitable marked.

Symbols placed in the manual means:

Especially important, you should know before you connect 
the  data logger. Failure to follow the remarks could lead to 
damage of the data logger.

Notice:

The removal of the data logger casing during the guarantee 

contract period  lead to its cancellation.

Port 1

Port 2

LAN

Supply dependent on

code version

(85...230...253 V a.c./d.c.

or 20...24...50 V a.c./d.c.)

INPUT

or

Supply depend on the

code version

Reviews: