Quick Start Guide 

– 5000-6000VA RT230 Models 

 
 
The Liebert GXT3 is shipped with the following items: 

• 

Terminal Block Communication terminals 

• 

Compact disc with: 

o

 

Liebert MultiLink® 

o

 

Configuration program 

o

 

User manual (electronic version) 

• 

USB cable, one; 2m (6-1/2 ft.) long 

• 

Rack handles with mounting hardware 

• 

Plastic tower support base, one set 

• 

Plastic Bezel 

• 

Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance) 
 

If the UPS is intended to be installed in the Tower orientation, locate the support base and spacers then assemble the two 
stand assemblies with an even number of spacers in each assembly.  Insert the UPS between the support base 
assemblies with adequate space between the assemblies as shown in the picture below.  

Note the display should be 

located on the upper half of the unit in the Tower orientation.  To rotate the display with the bezels removed, depress the 
grooved tabs on the sides and rotate it 90 degrees clockwise.

  If the USP is to be installed in a rack enclosure, follow the 

instructions provided with the rack mounting hardware for proper installation. 

 

 
The UPS is hardwired input with a conduit entry knockouts provided.  Input and output wiring should be installed in 
separate conduits.  All wiring should be done in accordance to all local and national electrical codes.  Before wiring the 
UPS ensure that the breaker in the external upstream panelboard is OFF. 
 

UPS Model 

Recommended 

(Maximum) External 

Over Current 

Protection  

Recommended Wire 

(All wires) 

75 degC Copper Wire 

Maximum Wire 

Accepted by 

Terminal Block 

Terminal Block 

Torque 

GXT3-5000RT230 
GXT3-6000RT230 

32A 

4mm

(10 AWG) 

6mm

(8 AWG) 

2.26 Nm (20 in-lb) 

 
Terminal Block Connections 
 

5000-6000 VA models 

 

 

OUTPUT 

INPUT 

 
 
The UPS is equipped with a POD containing output receptacles; connect the equipment to be protected to the output 
receptacles. 