Model TY720

16.8 K-factor Pendent Sprinkler

Electronic Control

Page 1 of 2 

AUGUST 2018 

TFP325

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model TY720 Pendent 

Sprinkler is an electronically controlled 

sprinkler having a nominal K-factor of 

16.8 (Ref. Figure 1).
The TY720 sprinkler is designed as an 

integral component of the Electronic 

Sprinkler System for Storage Applica-

tions, a performance-based system 

addressing high-challenging high pile 

storage fire hazards. For more informa-

tion about the sprinkler system and  the 

system components, refer to technical 

data sheet TFP360.
In place of a traditional heat-sensitive 

glass bulb or solder element, the TY720 

sprinkler features an electronic linear 

actuator and tensile link with hook and 

strut arrangement holding a button and 

seal against the waterway. A Simplex   

Sprinkler Control Heat Sensor paired 

with the TY720 sprinkler is connected 

directly to the actuator and is in con-

tinuous communication with a Simplex 

4100ES Suppression Release Panel.
The panel software algorithm analyzes 

information from heat sensors in mul-

tiple locations and selects the optimal 

response in a fire event. A voltage is 

then sent from an algorithm-selected 

heat sensor to its companion TY720 

sprinkler, operating the actuator and 

breaking the tensile link, allowing 

waterflow from the sprinkler.

NOTICE

The TY720 Sprinkler described herein 

must be installed and maintained in 

compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associa-

tion, in addition to the standards of any 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

TY720

Technical 

Data

Approvals

UL Listed

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connections

3/4 in. NPT

Discharge Coefficient

K=16.8 GPM/psi

½

 (241,9 LPM/bar

½

)

Finish

Natural Brass

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass 

Deflector. . . . . . . . . . . . . . . . . . . . . . . . . . Bronze

Compression Screw  . . . . . . . . . . Stainless Steel

Hook. . . . . . . . . . . . . . . . . . . . . . . . . . . . .MONEL

Strut . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MONEL

Tensile Link  . . . . . . . . . . . . . . . . . . . . . . . Copper

Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass

Sealing Assembly . Beryllium Nickel w/TEFLON

Ejection Spring. . . . . . . . . . . . . . . . . . . INCONEL

Electrical Actuator . . . . . . . . . . . . . . . . . . . Brass

Electrical Actuator Housing. . . . . ABS/PC Resin

Temperature Rating

Temperature rating is determined by 

the panel and heat sensor paired with 

the TY720 sprinkler.

For more information, refer to the Elec-

tronic Sprinkler System for Storage 

Applications data sheet (document 

number TFP360).

Installation

Install the Model TY720 Pendent Sprin-

kler in accordance with this section.

General Instructions

Avoid damage to the actuator and 

tensile link during installation. Grasp 

the sprinkler only by the protec-

tor and frame wrench flats when 

hand-tightening.
A leak-tight 3/4 in. NPT sprinkler joint 

should be obtained by applying pipe-

thread sealant to the sprinkler threads 

and wrench-tightening using only the 

W-Type 21 Sprinkler Wrench (Ref. 

Figure 2).

Sprinkler Installation

Install the Model TY720 Pendent Sprin-

kler only in the pendent position in 

accordance with the following:

Step 1.

 Apply pipe-thread sealant to 

sprinkler threads.

Step 2.

 Hand-tighten sprinkler into 

sprinkler fitting. Do not apply force to 

the actuator and tensile link, handle 

only by the protector and frame wrench 

flats.

Step 3.

 Apply W-Type 21 Sprinkler 

Wrench to sprinkler by fully seating 

wrench recess on sprinkler wrench flats 

(Ref. Figure 1).

Step 4.

 Wrench-tighten sprinkler to 

obtain leak-tight joint either 1 to 1-1/2 

turns beyond hand-tightened or by 

applying a minimum-to-maximum 

torque of 10 to 20 lb-ft (13,4 to 26,8 

N

m).