background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

JA-15E Wireless keypad 

JA-15E Wireless keypad 

1 / 3 

MNX53101 

The keypad is a component of the 

JA-10

  system used  

to control the control panel and display its current status. Using an 

external input a door detector can be connected to the keypad

.

 

It  is necessary to use this manual in combination with  

the 

JA-10

 installation and user manuals. 

The keypad contains 4 function buttons  (5), an LCD display (3), 

a system indicator (2), status indicators A, B, C, D (1), a keypad with 

an RFID chip card/tag reader (4). 

Figure 1: 1 – status indicators A,B,C,D; 2 – system indicator; 3 – LCD 

display; 4 – keypad and the RFID reader; 5 – function buttons A, B, C, D;  

6 – keypad opening tab; 7 – batteries; 8 – detachable  BUS terminals;  

9 – tamper contact; 10 – mini USB connector; 11 – production number. 

Installation 

1. Open the keypad housing

 

by pressing the tab on the bottom (6)

using a screwdriver which will release the keypad from its back

part.

2. Screw the back part on a selected place.
3. Insert two CR123A lithium batteries in the keypad.
4. Insert the keypad back into the back part.
5. Proceed according to the control panel installation manual.

Basic procedure:

a. The JA-111R radio module must be installed in the control

panel. The keypad must be in its communication range.

b. When the device is switched on, the system indicator (2)

will start showing  yellow  light  to indicate that the keypad

has not yet been enrolled to the system. 

c.  Open the 

N-Link

 software, select the required position in

the 

Devices

 window, and click on the 

Enroll

 button which

will open the enrollment mode. 

d. Press the keypad cover which will enroll the keypad and

the yellow LED indicator will  switch  off, which may take

a few seconds.  The enrollment signal can be sent by

inserting the batteries in the keypad or pressing the tamper

contact. 

Notes: 

Enrollment is also possible by entering its production code

(11) in the N-Link software or using a bar code scanner. All

numbers stated under the bar code must  be entered (e.g.

1400-00-0000-0001).

Installation of a magnetic contact 

The keypad supports connection of a  door detector. The IN 

input reacts to being disconnected from the common  GND 

contact.  The control panel’s reaction to an  activated IN input is 

configurable in the N-Link SW.  

Figure 2: connecting a magnetic contact 

Setting the properties 

Go to the 

Devices 

window in the 

N-Link

 software. When you are 

at the keypad position, click on the 

Internal settings

 option which will 

display a dialogue  window  to configure its settings and function 

buttons. Internal settings are separated into 2 basic tabs: 

Function

 

and 

Settings

The Function tab: 

Date and time

 – Displays the current time in the top-right corner of 

the display 

The system is not prepared to be Set

  – Indicates an obstacle 

preventing setting the control panel. 

User defined text

  –  Enables showing any text, for example the 

phone number of an installer company, etc. 

Buttons Function 

– On the left is a selection of button functions.  

On the right is a selection of Sections or  PG outputs to which the 

functions will be assigned. A function  button can be assigned with 

these functions: None,  Unsetting/setting,  Unsetting/partial setting, 

Unsetting/partially setting/setting, Section  indication, Panic, Fire, 

Audible panic, Medical Troubles, PG ON/OFF, PGON, PG OFF, PG 

indication, PG indicates inversely, Common functional button. 

Authorization

 – Setting and Unsetting requires user authorization. 

When this parameter is disabled the function buttons can be operated 

without authorization, however this does not apply to  Unsetting  

a  section which always requires authorization. Both ON and OFF 

statuses  of PG outputs can be configured to be operated with or 

without authorization.  

Section controlled by authorization

 – Selection of sections which 

can be controlled by authorization (using an RFID chip or a code) 

PG  control  – 

Selection of PG outputs which can be controlled  

by authorization (using an RFID chip or a code)

 

Import 

– Enables copying settings from other keypads of the same 

type and FW version, which have already been enrolled. For 

example, this can be utilized when the building has multiple entrances 

and it is necessary for all keypads to have identical functions.  

In addition, this function can also be used when replacing a faulty 

keypad with another. The Import button provides the history of 

keypad settings on a particular position of the device. 

Logo – 

The keypad can display a black and white picture of 128 x 

64 pixels (such as a company logo etc.) which stays on the screen for 

25 seconds after the last keypad operation. 

The Setting tab: 

Acoustic indication of selected sections: 

Higher volume

 – Increased volume of indication (it does not apply  

to alarm). 

Alarms

 – Indicates alarm (sounds a siren). 

Entrance delay

 – Continuous sound during the entrance delay. 

Exit delay 

– Slow beeping (1/s) 

Exit delay when partially set

  –  Slow beeping (deactivated by 

default). 

Button status change 

 

Beeps once when a status is changed.

 

Function: 

Optical indication setting: 

1.

Indicates permanently

 – The keypad indicates permanently.

When the mains electricity is disconnected  it indicates the

same way as option 3. When mains electricity is restored the

keypad indicates permanently again.

2.

Section/PG status change on keypad

  –  The status

change  of a section/PG  is indicated by  a  specific  function

button and a status indicator. Entrance delay and alarms

are indicated by all function buttons and status indicators.

3.

Section/PG status change on button

 – The keypad indicates

after a change of the section/PG status, entrance delay and

alarm only by a particular button and a section indicator.

4.

Button  status change on keypad

  –  The keypad indicates

after a change of the section/PG status by a particular button

and a section indicator.  Entrance delay and alarms  are

indicated acoustically only.

5. Entrance delay/Alarms on button

 – The keypad indicates

entrance delays and alarms with  a  function button and a

status indicator. Change of section/PG status is not

indicated visually or acoustically.

Reviews: