background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

JA-150ST Wireless combined smoke and heat detector

JA-150ST Wireless combined smoke and heat fire detector

1 / 2

MLW51707

The JA-150ST is a component of the 

JABLOTRON JA-100 

system. 

It is used to detect fire hazards in a building interior. The product is not 
designed to be installed in industrial premises. The detector is powered
by three LR6 (AA) type alkaline batteries, which are not included.
We recommend you buy them together with the detector. 
The JA-150ST consists of an optical smoke detector and a heat 
detector. The optical smoke detector is very sensitive to large dust 
particles which are present in dense smoke. It is less sensitive to 
smaller particles generated by the combustion of liquids such as 
alcohol. That is why the fire detector also contains a built-in heat 
detector which has a slower reaction but is much better at detecting fire 
which generates only a small amount of smoke. The detector has 
a status reaction (reports its activation and deactivation). The detector 
should be installed by a trained technician with a valid certificate issued 
by an authorized distributor.

Detector location

The smoke detector must be installed so that any smoke easily drifts 

into the detector owing to natural thermal circulation (usually on the 
ceiling). The detector can be used only in closed interiors. It is not 
suitable for interiors where smoke can disperse over a large area and 
cool down (e.g. interiors with extremely high ceilings – above 5 m) – the 
smoke would not reach the detector position.

The detector must be always placed in the section leading to the exit 

of the building (escape route), see Figure 1. If the building has a floor 
area greater than 150 m

2

, installation of an additional detector in some 

other suitable place is required, see Fig.2. 

1

2

3

4

5

1. kitchen, 

2. living room, 

3. – 6. bedrooms 

y

/

basic 

coverage

{

recommended 
coverage

Fig 1

1

2

3

4

5

6

Fig 2

1

2

3

6

Fig 3

In buildings and family houses with multiple floors, detectors 

should be installed above stairwells. It is recommended to place 
additional detectors in rooms where people sleep. See fig 3.

Installation on level ceilings

Place the detector in the centre of the room if possible. 

The detector 

must not be recessed into the ceiling

due to the possible existence 

of a warm air layer on the ceiling.

Never place the detector in the 

corner of the room 

(always keep at least 0.5 m distance from the 

corner) see Fig 4. There is an insufficient circulation of air in the 
corners.

Installation on sloping ceilings

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), then the detector can be installed as in Fig 5.

0.5m

TOP

Fig 4

0,9 m

Fig 5

centre of the room, best location

acceptable location

Walls, partitions, barriers and lattice ceilings

The JA-150ST detector must not be installed closer than 0.5 m

from any wall or partition. 

A narrow space with a width of less than 

1.2 m requires the detectors to be placed at a distance of at least one 
third of its width away. If a room is separated into sections with 
furniture, racks or semi partition walls, which do not reach the ceiling,
the space is considered to be fully separated if the gap between the top 
of these and the ceiling does not exceed 0.3 m. A free space of at least 
0.5m is required under and around the detector. Any irregularities of the 
ceiling (e.g. girders) exceeding 5% of the ceiling height should be 
considered a wall and the above-mentioned limitations should apply. 

Ventilation and air circulation

The detectors must not be installed directly by ventilation or air 

conditioning vents, etc…

If the air is supplied through a perforated 

ceiling, there must be no perforation within a radius of 0.6 m of the 
detector.

Avoid installing the detector in the following locations:

Places with poor air circulation (niches, corners, apexes of 
A-shaped roofs, etc.)

places exposed to dust, cigarette smoke or steam

Places with over-intense air circulation (close to ventilators, heat 
sources, air conditioning outlets, etc.)

In kitchens and other cooking places (because steam, smoke or 
oily fumes can reduce detector sensitivity, thus cause false alarms 
and detection faults).

Within a 1m radius of fluorescent tubes or energy-saving light bulbs 
(electrical interference may negatively affect the detector’s radio 
communication)

In areas with lots of small insects

Warning: The most false alarms are caused by an 

improper location of the detector.

See CEN/TS 54-14 standards for detailed installation 

guidelines.

Installation

Abide by the procedures recommended in the previous paragraphs.

Fig 6: 1 – detector cover opening; 2 – detector cover closing; 

3 – optical status signalling; 4 – arrow showing where to insert the detector 

onto the bottom part; 5 – production code; 6 – configuration jumpers; 

7 – battery holders

Reviews: