INSTALLATION INSTRUCTIONS

Copyright © 1996 Honeywell Inc.  •            •   All Rights Reserved

T8501A,B,C,D

Microelectronic Thermostats

APPLICATION

The T8501 Microelectronic Thermostat provides electronic control of 24 Vac single-stage heating and cooling systems.
Refer to Table 1 for a general description of the thermostat. All T8501 Thermostats require a common wire to supply
power.

Table 1. Description of T8501 Thermostats.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do 

not place your old

control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

T8501

System

Changeover

System  

Selection

Fan

Selection

Comments

A

Heat only

None

None

None

B

Heat only  

None

Heat-Off

On-Auto

Select models have only a system switch or fan
switch and some models have both.

C

Heat-Cool

Manual

Heat-Off-Cool

On-Auto

System and fan selections are done by
switches.

D

Heat-Cool

Automatic

Heat-Off-Cool-Auto

On-Auto

System and fan selections are done by
keyboard.

CAUTION

Disconnect power supply to prevent electrical
shock or equipment damage.

Location

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.

Do not install the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall or
on a 2 in. x 4 in. wiring box. Position wallplate horizontally
on the wall or on a 2 in. x 4 in. wiring box.

Position and level the wallplate (for appearance
only). The thermostat will function properly even
when not level.

69-0959

Summary of Contents for t8501A

Page 1: ...g installation use these instructions to check out the product operation T8501 System Changeover System Selection Fan Selection Comments A Heat only None None None B Heat only None Heat Off On Auto Select models have only a system switch or fan switch and some models have both C Heat Cool Manual Heat Off Cool On Auto System and fan selections are done by switches D Heat Cool Automatic Heat Off Coo...

Page 2: ...he holes 쐂 Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 through 5 for typical hookups A letter code is located near each terminal for identifica tion CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 쐃 Loosen the terminal screws on the wallplate and connect the system wires See Fig 6 IMPORTANT U...

Page 3: ...O G Y W OUTDOOR TEMPERATURE SENSOR COOL CHANGEOVER VALVE OR DAMPER HEAT CHANGEOVER VALVE OR DAMPER THERMOSTAT 1 2 2 M4826 FOR WRAPAROUND INSERTION STRIP 7 16 IN 11 MM FOR STRAIGHT INSERTION STRIP 5 16 IN 8 MM L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AVAILABLE ON SELECT MODELS JUMPER Rh TO Rc IN A SINGLE TRANSFORMER SYSTEM 1 HEATING RELAY OR VALVE COIL M48...

Page 4: ...with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard Temperature Settings The default setpoint for heat is 70 F 21 C and for cool is 78 F 25 5 C Press the increase or decrease key to change the present setting To change between heat and cool press the Information i key until the setting to be changed appears INSTALLER SETUP NOTE For most ap...

Page 5: ...on of key presses are required to use the Installer Setup feature To enter the Installer Setup mode press and hold the Information i key with the increase and decrease keys until the first mode number is displayed All display segments appear for approximately three seconds before the mode number is displayed See Figs 11 and 12 To advance to the next Installer Setup mode press the Information i key...

Page 6: ...perate Not used 25 thru 32 Minimum off time for the compressor 33 05 5 minute minimum off time for the compressor 00 01 02 03 or 04 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Heating setpoint range stopa 34 90 Heating setpoint can be set no higher than 90 F 40 thru 90 Number can be set anywhere between 40 and 90 in 1 F increments Cooling setpoint...

Page 7: ...two zeros appear Continued Em HeatOffCool Auto Only Heat Cool OnAuto System Fan Room Outdoor Em Ht Temporary Setting Wait Humid Aux Ht Remote Repl Batt M4844 M6792 TEST MODE NUMBER Test Number Self Test Description 10 19 Heating equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment T8501D only can be turned on and off 60 69 System key or system swi...

Page 8: ...ss Test Mode Number Description Key or Switch Operation Self Test a IMPORTANT Test Mode Numbers will only be displayed when the system is configured for the selected function EXAMPLE Numbers 60 61 and 62 are the only numbers that will be displayed when a system is configured for heat only SYSTEM KEY OR SWITCH SELF TEST When system switch is used move switch to see Test Mode Numbers i 60 Change fro...

Page 9: ...d tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat microprocessor is locked up Remove the thermostat from the wallplate for 2 minutes After 2 minutes replace the thermostat on the wallplate Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup mode number 37 and reconfigure the display Thermostat is configure...

Page 10: ...ostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup mode number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool System On indicator is lit but no heat is being delivered Fan operation set for 00 conventional heat when it should be set for 01 electric heat Enter Installer Setup mode ...

Page 11: ...69 0959 11 T8501A B C D MICROELECTRONIC THERMOSTATS ...

Page 12: ...uilding Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 69 0959 J H 10 96 Printed in Taiwan R O C Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com yourhome ...

Reviews: