PRODUCT DATA

68-0075-2

® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc.
 All Rights Reserved 

T834C, T8034C

Heating/Cooling Thermostats

APPLICATION

T834C and T8034C Thermostats provide low voltage control 

of single-stage heating, cooling or heating-cooling systems.

FEATURES

• Integral switches control Heat-Off-Cool System 

switching and Auto-On or On-Auto Fan switching.

• Standard heating-cooling, single-stage heat pump, and 

electric heat models available.

• Coiled bimetal operates silent, dust-free spdt mercury 

switch.

• T834C models have vented cover to provide better air 

flow for temperature sensing.

• Adjustable heat anticipator and fixed cool anticipator 

on all models.

• T834C models mount directly on wall or on a 

vertical

 

outlet box.

• T8034C models mount directly on wall or on a 

horizontal 

outlet box.

• SUPER TRADELINE® T8034C includes horizontal 

wallplate for covering marks from old thermostat.

• Accessory mounting plate assembly allows mounting 

T834C on horizontal outlet box or T8034C on vertical 

outlet box.

Contents

Application.........................................................................1

Features ............................................................................1

Specifications ....................................................................2

Ordering Information .........................................................2

Installation .........................................................................3

Settings and Adjustments..................................................7

Checkout ...........................................................................8

Summary of Contents for T834C

Page 1: ...ed bimetal operates silent dust free spdt mercury switch T834C models have vented cover to provide better air flow for temperature sensing Adjustable heat anticipator and fixed cool anticipator on all models T834C models mount directly on wall or on a vertical outlet box T8034C models mount directly on wall or on a horizontal outlet box SUPER TRADELINE T8034C includes horizontal wallplate for cove...

Page 2: ...rd cooling systems mounts horizontally adjustable heat anticipator 0 18 to 1 0A Additional SUPERTRADELINE Features Fan can be controlled from thermostat or plenum switch Wallplate for covering marks from old thermostat T8034C only TRADELINE Models T843C Heating Cooling Thermostat for use in single stage heat pump electric furnace and standard heating cooling systems mounts vertically adjustable he...

Page 3: ... the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Hazard Can cause personal electrical shock or equipment da...

Page 4: ...he thermostat and mounting plate if used to the wall or outlet box with a screw through the top mounting hole Adjust thermostat so it is approxi mately level and start the second screw through the bottom mounting hole Do not tighten 8 Level the thermostat exactly using a level device Tighten the mounting screws IMPORTANT This thermostat is calibrated at the factory mounted at true level Any inaccu...

Page 5: ...le to the wall or outlet box with a screw through the left mounting hole Adjust thermostat so it is approximately level and start the second screw through the right mounting hole Do not tighten 8 Level the thermostat exactly using a level device Tighten the mounting screws IMPORTANT This thermostat is calibrated at the factory mounted at true level Any inaccuracy in leveling during the mounting ca...

Page 6: ...SYSTEM SWITCH HEAT OFF COOL FAN SWITCH AUTO ON H1 TEMP FALL C1 ANTICIPATOR FAN RELAY HEAT OFF COOL C1 H1 ANTICIPATOR G R Y L1 HOT L2 W HEAT RELAY 1 1 H1 TEMP FALL C1 L1 HOT L2 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED INSTALL JUMPER BETWEEN W AND Y TERMINALS WHEN HEAT RELAY IS NOT USED HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTE...

Page 7: ...urrent draw of the primary control Use this thermostat only on systems with current draws that fall within the range of the heat anticipa tor do not use this device on Powerpile millivolt systems 1 A current rating is usually stamped in the nameplate of the primary control Set the adjustable heat anticipator indicator to match the value given on the nameplate 2 If the current rating is not availab...

Page 8: ...iately 3 Move temperature setting lever about 10 F 6 C above room temperature Cooling and fan should shut off Fan 1 With System switch set to Off and Fan switch set to On the fan runs continuously 2 Move Fan switch to Auto In gas fired or oil fired sys tems fan operation is controlled by thermostat in cool ing and by plenum fan control in heating In heat pump and some central electric heat systems...

Reviews: